background image

2

The F1S5 Series Automatic Sprinkler utilizes a special 

response 5.0 mm frangible glass bulb. The glass bulb 
consists of an accurately controlled amount of special fluid 
hermetically sealed inside of a precisely manufactured glass 
capsule. This glass bulb is specially constructed to provide 
fast thermal response.

At normal temperatures, the glass bulb contains the fluid 

in both the liquid phase and in the vapor phase. The vapor 
phase can be seen as a small bubble. As heat is applied, the 

Pendent

Conventional

Upright

liquid expands forcing the bubble smaller and smaller as the 
liquid pressure increases. Continued heating forces the liquid 
to push out against the bulb, causing the glass to shatter, 
opening the waterway and allowing the deflector to distribute 
the discharging water.

The F1S5 Series Sprinkler temperature rating is identified 

by the color of the glass bulb capsule as well as frame color 
where applicable.

F1S5 LO Pendent

F1S5 LO Upright

Model F1S5-56 Upright, Pendent and Conventional Sprinklers

Model F1S5 LO Upright and Pendent Sprinklers

Installation Wrench: 

Model D Sprinkler Wrench

Installation Data: 

Nominal Orifice

Thread Size

Nominal K Factor

Sprinkler 

Height

Sprinkler Identification

RTI (fts

1

/

2

) [ms

1

/

2

]

US

Metric

Upright

Pendent

Standard-Upright (SU) and pendent Deflectors Marked to Indicate Position

(90-130)

[50-70]

1

/

2

” (15 mm)

(1)

1

/

2

” NPT (R 

1

/

2

)

5.6

80

2.25” (57 mm)

SU

SP

Conventional-Install in Upright or Pendent Position

15 mm

(1)

1

/

2

” NPT (R 

1

/

2

)

5.6

80

57 mm

C u/p

Model F1S5 Large Orifice Upright and Pendent Sprinklers

(90-150)

[50-80]

20 mm

1

/

2

8.0

115

58 mm

SU

SP

Summary of Contents for F1S5 Series

Page 1: ...SU K115 Certificate G411006 Product Description The F1S5 Series Glass Bulb Sprinkler combines the durability of a standard sprinkler with the attractive low profile of a decorative sprinkler Whether installed on exposed piping or in an office ceiling it is functional and attractive Beautifully versatile is the description for the Reliable Model F1S5 Series Recessed glass bulb sprinkler Recessing t...

Page 2: ... to shatter opening the waterway and allowing the deflector to distribute the discharging water The F1S5 Series Sprinkler temperature rating is identified by the color of the glass bulb capsule as well as frame color where applicable F1S5 LO Pendent F1S5 LO Upright Model F1S5 56 Upright Pendent and Conventional Sprinklers Model F1S5 LO Upright and Pendent Sprinklers Installation Wrench Model D Spr...

Page 3: ...ler Height Sprinkler Identification 1 RTIc fts1 2 ms1 2 US Metric 1 2 15 mm 1 2 NPT R1 2 5 6 80 2 25 57 mm SP 2 110 150 60 80 Model F1S5 Large Orifice Recessed Pendent Sprinklers 3 90 150 50 80 20 mm R1 2 8 0 115 58 mm SP 1 c 1 09 ft s 1 2 0 60 m s 1 2 2 VdS Approval for 155 F 68 C 175 F 79 C and 200 F 93 C only 3 Currently not VdS Approved other recessed escutcheon will void all approvals and neg...

Page 4: ...off Max Recessed Min Recessed 7 16 11 mm 15 16 24 mm 11 2 38 1 mm 1 25 mm Maintenance The Models F1S5 56 F1S5 LO F1S5 56 Recessed and F1S5 LO Recessed Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25 Do not clean sprinklers with soap and water ammonia or any other cleaning fluid Remove any sprinkler which has been painted other than factory ap...