Model F1 LO sprinklers are standard response sprinklers 

intended for installation as specified in NFPA 13. They must 
also be installed with the Model D Sprinkler Wrench or Mod-
el W2 Sprinkler Wrench specifically designed by Reliable for 
use with these sprinklers.

The Model F1 LO Recessed Sprinklers are to be installed 

with a maximum recess of ¾ inch (19mm). The Model F1   
Escutcheon  illustrated  is  the  only  recessed  escutcheon  to 
be used with the Model F1 LO Pendent and EC Sprinklers. 
The use of any other recessed escutcheon will void all ap-
provals and negate all warranties. When installing Model F1 
LO Recessed Pendent and EC Pendent Sprinklers, use the 
Model  GFR2  Sprinkler  Wrench.  Any  other  type  of  wrench 
may damage these sprinklers. 

Note:

 A leak tight 1/2” NPT 

(R1/2) sprinkler joint can be obtained with a torque of 8 - 18 
ft-lbs (11 - 24 N-m). Do not tighten sprinklers over maximum 
recommended torque. It may cause leakage or impairment 
of the sprinklers.

Glass  bulb  sprinklers  have  orange  covers  to  protect  the 

bulb  during  the  installation  process.  REMOVE  THIS  PRO-
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO-
STATICALLY TESTED AND, WHEN APPLICABLE, THE ES-
CUTCHEONS HAVE BEEN INSTALLED. RASCO wrenches 
are designed to install sprinklers when covers are in place.

Maintenance

The Models F1 LO and F1 LO Recessed Sprinklers should 

be  inspected  and  the  sprinkler  system  maintained  in  ac-
cordance with NFPA 25. Do not clean sprinklers with soap 
and  water,  ammonia  or  any  other  cleaning  fluid.  Remove 
any sprinkler which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprinklers 
should be maintained to allow quick replacement of dam-
aged or operated sprinklers. Prior to installation, sprinklers 
should be maintained in the original cartons and packaging 
until used to minimize the potential for damage to sprinklers 
that would cause improper operation or non-operation.

Ordering Information

Specify:

1.  Sprinkler Model: F1 LO
2.  Sprinkler Type
3. Temperature Rating
4.  Sprinkler Finish
5. Thread Type: [¾” NPT] [ISO 7-1R¾]
6.  Escutcheon Finish (where applicable)

Temperature Ratings

&ODVVLÀFDWLRQ

Sprinkler

Temperature

Maximum

Ambient

Temperature

Bulb 

Color

°F

°C

°F

°C

Ordinary

135

57

100

38

Orange

Ordinary

155

68

100

38

Red

Intermediate

175

79

150

66

Yellow

Intermediate

200

93

150

66

Green

High

(1)

286

141

225

107

Blue

Extra High

(1)

360

182

300

149

Mauve

(1)

 Not Available for F1 LO Recessed

Maximum Working Pressure

175 psi (12 bar)
SIN R1712, R1722 & R1742 cULus listed for 250 psi (17 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)

Finishes

(1)

Standard Finishes

Sprinkler

Escutcheon

Bronze
Chrome
Polyester Coated

(6)(7)

Brass
Chrome
White Painted

Special Application Finishes

Sprinkler

Escutcheon

Electroless Nickel PTFE

(8)

Bright Brass

(2)

Black Plated

Black Paint

(3)(4)

Off White

(3)

 

Chrome Dull

Lead Plated

(3)(4)

Wax Coated

(3)(4)(5)

Wax Over Lead

(3)(4)

Electroless Nickel PTFE  

Bright Brass

Black Plated

Black Paint

Off White

Chrome Dull

(1)

 Other colors and finishes are available on special order.

Consult factory for details. Custom color painted sprin-
klers may not retain their UL Corrosion resistance list-
ing.

(2)

 200°F (93°C) maximum.

(3)

 UL and ULC listed, and NYC approved only.

(4)

 155°F to 200°F (68°C to 93°C) ratings only.

(5)

 286°F (141°C) sprinklers may be coated for ambient 

    conditions not exceeding 150°F (66°C). 

(6)

 UL listed corrosion resistant SIN number:  

R1722 in standard Black or White. Corrosion resistance 
in other polyester colors is available upon request.

(7)

 FM Approved for SIN R1722, R1712.

(8)

 cULus listed  Corrosion Resistant  SIN R1722, R1712 &  

   R1742 in Electroless Nickel PTFE Plated.