background image

Model G4FR
Concealed
Automatic
Sprinkler

The Reliable Automatic Sprinkler Co., Inc.,

525 North MacQuesten Parkway, Mount Vernon, New York10552

The Concealer

®

A Concealed Sprinkler
With a ½

²

(13mm) or 1

1

2

²

(38mm)

Adjustment

Features

1. Cover plate assembly with ½

²

(13mm)

adjustment.

2. Smooth aesthetic ceiling profile.
3. As heat sensitive as an exposed

sprinkler.

4. Available in brass, chrome or black plated or

white painted finishes.

5. Ordinary temperature rating.
6. Multiple orifices for design flexibility.
7. Installation does not require clips or springs.

Application

The Reliable Model G4FR

Concealer is the most versatile
concealed sprinkler available.
It provides the best form of fire
protection while offering an
attractive appearance and ½

²

(13mm) of cover adjustment
for ease of installation. The small diameter cover plate
assembly is easily and positively attached and blends
into the ceiling, concealing the most dependable fire
protection available, an automatic sprinkler system.

The Concealer

®

is designed for use where aesthetic

appearance is important. Offices, hospitals, motels and
restaurants are but a few of the applications where it can
be used. It is available in different orifice sizes allowing the
designer to optimize system performance, thereby
achieving a very efficient installation.

The Concealer

®

can eliminate the need for precise

cutting of drop nipples. The cover plate assembly can be
adjusted without tools to fit accurately against the ceiling.
The fire protection system need not be shut down to
adjust or remove the cover plate assembly.

Product Description

The Reliable Model G4FR Standard Response

Concealer uses a proven fast response fusible element in
a standard style sprinkler frame with a drop–down
deflector. This assembly is recessed into the ceiling and
concealed by a flat cover plate assembly. This threaded
engagement provides ½

²

(13mm) of cover adjustment.

The flat cover plate is attached to the skirt using 135°F
(56

°

C) ordinary temperature classification solder.

When the ceiling temperature rises, the solder holding

the cover plate to skirt melts, the cover plate released thus
exposing the sprinkler inside to the rising ambient
temperature.

The subsequent fusing of the element opens the

waterway and causes the deflector to drop into position
for distributing the water. Any secure engagement
between the cover plate and cup will assure that the
drop–down deflector is properly located below the
ceiling.

Bulletin 122

Rev.

N

Bulletin

122

Rev.

N

U.S. Patent No. 4,880,063

Listings & Approvals

1.

Underwriters Laboratories, Inc. (UL)

2.

Underwriters’ Laboratories of Canada. (ULC)

3.

N.Y.C. BS&A No. 587-75-SA

4.

Factory Mutual Corporation (FM)

•Light Hazard Occupancies
•Ordinary Hazard Occupancies—

Groups 1 & 2, Wet Systems Only

Note:

Approvals are for ordinary hazard except for small

orifice sprinklers, which are limited to light hazard. The cup
and skirt are fabricated from plated steel and are intended for
interior, non-corrosive applications. Small orifice sprinklers are
limited to light hazard occupancies.

Summary of Contents for F1-300

Page 1: ...f brass copper or beryllium nickel At normal temperatures the glass bulb contains fluid in both the liquid and vapor phases The vapor phase can be seen as a small bubble As heat is applied the liquid...

Page 2: ...m NPT R 5 6 80 2 2 56mm R5515 17 32 20mm NPT R 8 0 115 2 4 61mm R5512 Installation Data Sprinkler Type Nominal Orifice Size Thread Size Nominal K Factor Sprinkler Height Sprinkler Identification Numbe...

Page 3: ...sprinkler that has been painted other that factory applied or damaged in any way A stock of spare sprinklers should be maintained to allow quick replacement of damaged of operated sprinklers Prior to...

Page 4: ...echanical sprinkler alarms Pressure gauges Electrical sprinkler alarm switches Identification signs Water flow detectors Fire department connections The equipment presented in this bulletin is to be i...

Page 5: ...ols to fit accurately against the ceiling The fire protection system need not be shut down to adjust or remove the cover plate assembly Product Description The Reliable Model G4FR Standard Response Co...

Page 6: ...he United States Canada and foreign countries The Reliable Automatic Sprinkler Co Inc 800 431 1588 Sales Office 800 848 6051 Sales Fax 914 668 3470 Corporate Offices www reliablesprinkler com Internet...

Page 7: ...sprinkler that uses Reliable s push on thread off sidewallcover Thissprinklerhasthecupfactorymountedand is shipped with a protective cap that protects the 3mm frangible glass bulb during shipping and...

Page 8: ...t be ordered separately Installation is completed by removing the protective cap and inserting the F2 Escutcheon over the collar DH80 with SWC Cover Plate Concealed Toinstallthesprinkler cuta25 8 diam...

Page 9: ...3 Figure 1 Figure 2 Figure 3...

Page 10: ...hout the United States Canada and foreign countries Reliable For Complete Protection Reliable offers a wide selection of sprinkler components Following are some of the many precision made Reliable pro...

Reviews: