background image

(1)

Other colors and finishes are available. Consult factory for details.

Note:

Paint or any other coatings applied over the factory finish

will void all approvals and warranties.

Standard Finishes

(1)

Sprinkler

FP Escutcheon

F2 Escutcheon

Cover Plate

White/ Chrome /

Raw Bronze

White / Chrome White / Chrome /

Bright Brass

White

Finishes

( 1 )

Approval Type:

Quick Response, Extended Coverage.

Approved for installation in accordance with NFPA 13

for Light hazard occupancies.

UL Listing Category

Sprinklers, Automatic

and Open.

Quick Response Sprinklers.

Installation Wrench

Model GFR1 Sprinkler Wrench

Installation Aid

For concealed, a protective plastic

cap is included for use during

installation.

Escutcheon Data:

FP cup/escutcheon

assembly-

1

2

²

(13mm)adjustment

F2 -

1

2

²

(13mm) adjustment

*

DuPont Registered Trademark

K Factor

Thread

Size

Temperature Rating

Maximum

Ambient

Temperature

Sprinkler

Identification

Number

(SIN)

US Metric

Sprinkler

SWC

Cover

8.0 115,3

3

4

²

155°F

(68°C)

135°F

(57

°

C)

135°F

(57°C)

100°F

(38°C)

RA0362

Technical Data*:

*

Minimum spacing of 12 feet (3,7m).

removing the wrench from the sprinkler cup, care must be

taken to prevent damage to the sprinkler. Wrench only on

the square boss. DO NOT WRENCH ON ANY OTHER

PART OF THE SPRINKLER. It is recommended that the

sprinkler be protected during plastering and painting

operations by using the protective cap P/N 6802710003.

Thesemustbeorderedseparately. Installationiscompleted

by removing the protective cap and inserting the push-on

Escutcheon. Turn to adjust the Escutcheon.

DH80 Recessed, F2 Escutcheon

To install the DH80 with the F2 Escutcheon as a recessed

sprinkler cut a 2 ¼” diameter hole in the wall as shown in

Figure 2. Thread the DH80 into the collar hand tight. Apply a

Teflon* based sealant to the sprinkler threads and install in

the fitting. Wrench only on the square boss. NOTE: The

GFR1 wrench has a notch in it to accommodate the deflector

top. This wrench can only be inserted one way. When

inserting or removing the wrench from the sprinkler cup care

must be taken to prevent damage to the sprinkler. DO NOT

WRENCH ON ANY OTHER PART OF THE SPRINKLER. It is

recommended that the sprinkler be protected during

plastering and painting operations by using the protective

cap P/N 6999991009. These must be ordered separately.

Installation is completed by removing the protective cap and

inserting the F2 Escutcheon over the collar.

DH80 with SWC Cover Plate Concealed

Toinstallthesprinkler,cuta2

5

8

²

diameterholeintothewall

as shown in Fig.1. A Teflon* based thread sealant should be

applied to the sprinkler threads only. Remove the protective

cap (P/N 6802710003) and then position the GFR1 wrench

into the sprinkler/cup assembly until the wrench engages the

flats of the square boss. Then tighten the sprinkler into the

pipe fitting. When inserting or removing the wrench from the

sprinkler/cup assembly, care should be taken to prevent

damage to the sprinkler. DO NOT WRENCH ON ANY

OTHER PART OF THE SPRINKLER. The protective caps

should be reinstalled for protection during plastering and

painting. Remove caps only when covers are being

installed.The cover assembly is then pushed onto the cup.

Cover assemblies provide ½

²

(13mm) of adjustment. Final

adjustment is made by turning the cover clockwise until the

skirt flange makes full contact with the wall surface. Cover

removalrequiresturninginthecounter-clockwisedirection.

Concealed cover/cup assemblies are listed only for use

with specific sprinklers. The use of any other concealed

cover/cup assembly with the Model DH80 Horizontal Sidewall

Sprinkler or the use of the concealed cover assembly on any

sprinkler with which it is not specifically listed will void all

guarantees, warranties, listings and approvals.

Ordering Information

Specify:

DH80

- Sprinkler Finish

DH80 Recessed

-Sprinkler Finish

FP or F2 Escutcheon

-Escutcheon Finish

SWC Concealed

-Cover-Plate Finish

Protective cap for

use with F2 or FP

escutcheons

Maintenance

Model DH80 should be inspected quarterly and the

sprinkler maintained in accordance with NFPA 25. Do not

clean sprinklers with soap and water, ammonia or any

othercleaningfluids. Removedustbyusingasoftbrushor

gentlevacuuming. Removeanysprinkler/coverassembly,

which has been painted (other than factory applied) or

damaged in any way. A stock of spare sprinklers should

be maintained to allow quick replacement of damaged or

operated sprinklers. Prior to installation, sprinklers should

be maintained in their original cartons and packaging until

used to minimize the potential for damage to sprinklers that

would cause improper operation or non-operation.

2.

Coverage Area

Flow Rate

gpm (L/min)

Pressure

psi (bar)

Maximum Coverage Area

Width x Length

ft x ft (m xm)

40 (151,4)

25 (1,7)

28 x 14 (8,5 x 4,3)

Summary of Contents for F1-300

Page 1: ...f brass copper or beryllium nickel At normal temperatures the glass bulb contains fluid in both the liquid and vapor phases The vapor phase can be seen as a small bubble As heat is applied the liquid...

Page 2: ...m NPT R 5 6 80 2 2 56mm R5515 17 32 20mm NPT R 8 0 115 2 4 61mm R5512 Installation Data Sprinkler Type Nominal Orifice Size Thread Size Nominal K Factor Sprinkler Height Sprinkler Identification Numbe...

Page 3: ...sprinkler that has been painted other that factory applied or damaged in any way A stock of spare sprinklers should be maintained to allow quick replacement of damaged of operated sprinklers Prior to...

Page 4: ...echanical sprinkler alarms Pressure gauges Electrical sprinkler alarm switches Identification signs Water flow detectors Fire department connections The equipment presented in this bulletin is to be i...

Page 5: ...ols to fit accurately against the ceiling The fire protection system need not be shut down to adjust or remove the cover plate assembly Product Description The Reliable Model G4FR Standard Response Co...

Page 6: ...he United States Canada and foreign countries The Reliable Automatic Sprinkler Co Inc 800 431 1588 Sales Office 800 848 6051 Sales Fax 914 668 3470 Corporate Offices www reliablesprinkler com Internet...

Page 7: ...sprinkler that uses Reliable s push on thread off sidewallcover Thissprinklerhasthecupfactorymountedand is shipped with a protective cap that protects the 3mm frangible glass bulb during shipping and...

Page 8: ...t be ordered separately Installation is completed by removing the protective cap and inserting the F2 Escutcheon over the collar DH80 with SWC Cover Plate Concealed Toinstallthesprinkler cuta25 8 diam...

Page 9: ...3 Figure 1 Figure 2 Figure 3...

Page 10: ...hout the United States Canada and foreign countries Reliable For Complete Protection Reliable offers a wide selection of sprinkler components Following are some of the many precision made Reliable pro...