Low air pressure switch to indicate loss of air pressure 
in system piping.  Pressure switch shall be [cULus List-
ed][ FM Approved] and of the bellows activated type 
enclosed in a weatherproof NEMA 4/4X rated enclosure 
incorporating tamper proof screws.  There shall be two 
sets of SPDT (form C) contacts rated 10.0 A @ 125/250 
VAC and 2.5 A @ 6/12/24 VDC. The pressure switch 
shall have a maximum service pressure rating of 250 
psi (17.2 bar) and shall be factory adjusted to operate 
at a pressure of 4 to 8 psi (0.27 to 0.55 bar) with adjust-
ment up to 15 psi (1.03 bar). Switch shall be provided 
with a ½” NPT male pressure connection. Low air su-
pervisory switch shall be Potter PS10-2.

• 

Pressure alarm switch to indicate water flow in system.  
Pressure switch shall be [cULus Listed] [FM Approved] 
and of the bellows activated type enclosed in a weather 
proof NEMA 4/4X rated enclosure incorporating tamper 
proof screws.  There shall be two sets of SPDT (form 
C) contacts rated 10.0 A @ 125/250 VAC and 2.5 A @ 
6/13/24 VDC.  The pressure switch shall have a maxi-
mum service pressure rating of 250 psi (17,2 bar) and 
shall be factory adjusted to operate at a pressure of 4 
to 8 psi (0,27 to 0,55 bar) with adjustment up to the 15 
psi (1,03 bar).  Switch shall be provided with a 1/2” NPT 
male pressure connection.  Pressure alarm switch shall 
be Potter PS10-2.

• 

Pressure maintenance device for maintaining a con-
stant pneumatic system pressure regardless of pres-
sure fluctuations in the compressed air (or nitrogen) 
source.  The pressure maintenance device shall consist 
of galvanized trim and brass parts, including a strainer, 

a field adjustable air pressure regulator and associated 

pressure gauge.  The pressure regulator shall have an 
adjustable outlet pressure range of 5 to 100 psi (0.34 
to 6.8 bar).  The pressure maintenance device shall 
have a working pressure of 175 psi (12.1 bar).  Recom-
mended supervisory pressure shall be 7 to 10 psi (0.5 
to 0.7 bar).  Pressure maintenance device shall be Reli-
able  Model A.

Double Interlock Preaction System shall be Reliable Dou-

ble Interlock Type D Preaction System, Bulletin 750.

Pneumatic Supervisory Pressure Supply Op-
tions

Note:

 See Reliable Bulletins 254 and 251 for complete infor-

mation on air and nitrogen regulating equipment.

Owner’s Air supply

Supervisory air supply shall be provided by an owner sup-

plied air system in conjunction with a listed automatic pres-
sure maintenance device, capable of maintaining a con-
stant system pressure regardless of pressure fluctuations in 
the compressed air source. 

Compressed Air Supply

Supervisory air supply shall be provided by an automatic 

tank-mounted air compressor sized for the capacity of the 
double interlock preaction system piping, and be capable 
of restoring normal air pressure in the system within the 

time limits specified by NFPA 13.  Unit shall include a mo

-

tor mounted, oil-less, piston compressor, pressure gauge, 
pressure switch, check valve, drain valve and safety relief 
valve.  Single-phase motor shall have internal thermal pro-
tection.

Nitrogen

Nitrogen cylinders provided by an approved source shall 

provide the nitrogen supply. The nitrogen cylinder pressure 
shall be regulated and supervised through the use of nitro-
gen regulating device and low-pressure trim kit. This device 
shall consist of a brass, single stage pressure regulator, 
equipped with high pressure inlet and low pressure outlet 
gauges, and ¼” copper connection tubing with galvanized 
¾” x ¼” reducer bushing. This kit shall include a low-pres-
sure switch with associated galvanized connection trim. As-
sembly shall be a Reliable Nitrogen Regulating Device. This 
device is to be used in conjunction with the Reliable  Model 
A Pressure Maintenance Device.

Optional System Accessories

System Control Valve

Preaction system control valve shall be a slow close, [cU-

Lus Listed] indicating butterfly type valve with a pre-wired 
supervisory tamper switch assembly. The valve shall be 
rated for a working pressure of [300 psi (20.7 bar)]. System 
control valve shall be for a [2” (50 mm)] Reliable RBVG But-
terfly Valve or [2½” (65 mm)][3” (80 mm)][4” (100 mm)][6” 
(150 mm][8” (200 mm] - Reliable BFG-300 Butterfly Valve. 

Detection System

To initiate actuation of the preaction system’s deluge valve, 

a supplemental electric detection system shall be provided 

[Insert applicable product specification].

Releasing/Control Panel

A releasing/control panel shall be used to operate the 

preaction system. The releasing/control panel shall be a 
conventional, microprocessor-controlled panel containing 
two initiating device circuits, and waterflow and supervi-
sory inputs. Output circuits shall include alarm, waterflow, 
supervisory, and releasing circuits. Mode of operation shall 
be set for cross zoned operation, requiring both a detec-
tion device input and a low air pressure switch input (sprin-
kler operation) to energize the solenoid valve, causing the 
deluge valve to operate.  Releasing/control panel shall be 
equipped with a local tone alarm to annunciate loss of AC 
power, system trouble, circuit trouble, and low auxiliary DC 
power supply. Panel shall be [cULus Listed] [FM Approved] 
and be capable of providing power for compatible detectors 
and auxiliary devices used. Audible alarms shall be able to 
be silenced at releasing panel. Auxiliary DC power supply 
shall consist of (2) 12-volt lead acid batteries of the same 
ampere-hour rating, providing [60 hours – cULus Listed] 
[90 hours – FM Approved]. Dry contacts shall be provided 
for remote annunciation of alarm, trouble, and supervisory 
panel signals. Main power supply to be a dedicated a 120 
VAC / 60 Hz circuit.

7.

Summary of Contents for DDX

Page 1: ...m 165 mm 8 200 mm Bulletin 750 October 2022 Bulletin 750 October 2022 Technical Specifications and Instructions for Installation Operation and Maintenance Available with 175 psi 12 1 bar or 300 psi 20 7 bar Rated Solenoid Valve Externally Resettable Clapper One Main Drain 7 to 10 psi 0 5 to 0 7 bar Pneumatic Supervising Pressure Electric Electric Actuation Image subject to change ...

Page 2: ...in on 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes alarm devices air supply and required pressure gauges This trim set is avail able in individual loose parts in time saving segmented assembled kit forms or fully assembled to the Model DDX Deluge Valve with or without a control valve Listings Approvals Only when used with Reliable Trim Sets 1 Reliable s Type D Double Interlock Preaction Syste...

Page 3: ...RT ALARM PORT OUTLET EXTERNAL RESET HINGE RESTRICTION PUSH ROD CHAMBER INLET PUSH ROD CHAMBER OUTLET PUSH ROD CLAPPER IN LATCHED POSITION CLAPPER IN OPEN POSITION LEVER CLAPPER IN CLOSED POSITION INLET WEEP HOLE TO RESET CLAPPER NOTE PUSH ROD CHAMBER MUST BE VENTED TO DRAIN MODEL DDX VALVE SECTION VIEW MODEL DDX VALVE REAR VIEW Fig 1 3 ...

Page 4: ... Manual Emergency Pull Box see Reliable Bulletin 506 is also available and can be provided as an option Whenever ambient temperature conditions are high the water temperature in the Model DDX Deluge Valve push rod chamber could possibly increase thereby increasing the pressure in the chamber to values exceeding the rated pressure of the system In an indoor installation where stan dard room tempera...

Page 5: ...ed from improper fire pump settings un derground construction work or an improper venting of trapped air in the water supply piping System Design Considerations The automatic sprinklers releasing devices electric re leasing control equipment fire detection devices manual pull stations and signaling devices which are utilized with the Type D Double Interlock Preaction System must be UL or ULC Liste...

Page 6: ...ve seat Del uge valve shall have an external reset knob for resetting the clapper without requiring the removal of the valve face plate Pushrod chamber design shall consist of a stainless steel piston pushrod and spring assembly with diaphragm seal secured to the casting through a pushrod guide con structed of a synthetic engineering plastic to resist corro sion Casting shall have a bleeder hole l...

Page 7: ...erlock preaction system piping and be capable of restoring normal air pressure in the system within the time limits specified by NFPA 13 Unit shall include a mo tor mounted oil less piston compressor pressure gauge pressure switch check valve drain valve and safety relief valve Single phase motor shall have internal thermal pro tection Nitrogen Nitrogen cylinders provided by an approved source sha...

Page 8: ... 80 mm 3 500 89 mm 3 344 85 mm 11 32 9 0 mm 5 8 16 mm 4 100 mm 4 500 114 mm 4 334 110 mm 3 8 9 5 mm 5 8 16 mm 165 mm 6 500 165 mm 6 330 161 mm 3 8 9 5 mm 5 8 16 mm 6 150 mm 6 625 168 mm 6 455 164 mm 3 8 9 5 mm 5 8 16 mm 8 200 mm 8 625 219 mm 8 441 214 mm 7 16 11 mm 3 4 19 mm Threaded openings Per ANSI B 2 1 Flange Dimensions Flange T ype Nominal Pipe Size Bolt Circle Diameter Bolt Hole Diameter Fl...

Page 9: ... M M 1 6 5 M M 6 I N C H 1 5 0 M M 1 6 5 M M 4 I N C H 1 0 0 M M 4 I N C H 1 0 0 M M 3 I N C H 8 0 M M 3 I N C H 8 0 M M 2 1 2 I N C H 6 5 M M 7 6 M M 2 1 2 I N C H 6 5 M M 7 6 M M 2 I N C H 5 0 M M 2 I N C H 5 0 M M 1 5 10 50 100 500 0 1 0 5 PRESSURE LOSS BAR 0 1 1 10 10 100 1000 10000 FLOW RATE GPM PRESSURE LOSS PSI Fig 3 ...

Page 10: ...ion of the detection system and or sprinkler system subjected to fire conditions 8 Open the pushrod chamber supply valve and allow wa ter to fill the pushrod chamber Close the Model B Manual Emergency Station 9 Bleed all air from the actuation piping Open the so lenoid valve by operating a detector or an electric manual emergency station While water is flowing through the sole noid valve cause it ...

Page 11: ...then tighten se curely Ref Bulletin 613 2 Water leaking from Ball Drip This can be caused by either a water column on top of the clapper or a supply water leakage a Leakage due to water column This condition is caused by leakage past the clapper seal assembly Be sure the clapper seal and seat are free of any type of de bris or damage If nec essary follow steps below to replace the seal assembly an...

Page 12: ...em b Shut down the valve controlling water supply to the Del ugeValve Relievetheinletpressurebyopeningthemaindrain valve Close the pushrod chamber supply valve and open the Model B Manual Emergency Station c Remove the trim at the unions nearest to the pushrod chamber cover d Take the pushrod chamber cover off by removing the six retaining screws e Visually inspect the pushrod chamber cover and pi...

Page 13: ...13 750EXP_A Fig 4 ...

Page 14: ...1 10 37 8 30 33 20 31 5 16 36 2 42 5 6 34 38 9 IMPORTANT NOTE Early generation 4 and 6 DDX valves may incorporate a brass drop in seat Prior to ordering replacement parts confirm the presence of a stainless steel screw in seat or brass drop in seat For replacement parts for valves with brass drop in seat please contact Reliable Sprinkler Company Technical Services techserv reliablesprinkler com 29...

Page 15: ...1 Stainless Steel CF8M 18 95276006 Diaphragm 1 EPDM Polyester 19 95306267 N A N A N A RetainingRing 3 8 Shaft LeverPin 2 Stainless Steel 15 7 or 17 7 N A 95306267 N A N A RetainingRing Shaft LeverPin N A N A 95306269 N A Retaining Ring 5 8 Shaft Lever Pin N A N A N A 95316408 Retaining Ring Shaft Lever Pin 20 95306268 N A N A N A RetainingRing 3 8 Shaft HingePin 2 Stainless Steel 15 7 or 17 7 N A ...

Page 16: ... Size End Configuration Trim Assembly Loose Trim Segmentally Assembled Fully Assembled no Control Valve Fully Assembled with Control Valve Optional 300 psi 20 7 bar solenoid valve Note This trim assembly will include a spool piece with 1 4 outlet to accommodate push rod chamber supply piping Not available for 76mm or 165mm systems or systems using a flanged inlet Model DDX valve Service Kits Servi...

Page 17: ...t 2 End to end take out of Model DDX valve with flanged inlet where available see page 8 also reference Bulletin 519 3 Not applicable to 76mm or 165mm systems or systems using a flanged inlet Model DDX valve 4 2 systems include spool piece with outlet below valve dimension provided is total length of both components Reliable Automatic Sprinkler Co Inc 800 431 1588 Sales Offices 800 848 6051 Sales ...

Reviews: