4.

however, eliminate another important facet of good main-
tenance, namely, periodic cleaning and inspection of the 
internal valve parts.

A valve body drain is provided in the event that water 

builds up due to condensate from the air supply system or 
water left inside form system testing.  After closing the main 
supply valve, the condensate drain can be opened slightly 
until the water inside the vale body and main pipe column 
has drained.  See the section titled “Draining Excess/Con-
densate Water from the System” in this bulletin for the de-
tailed procedure.

The Model B Manual Emergency Station is included in 

the Reliable Type D Double Interlock Preaction System trim 
sets. It consists of an aluminum nameplate mechanically at-
tached to a ball valve. The valve handle in its OFF position is 
guarded against accidental turning to the ON position (and 
system discharge) by a nylon cable tie provided with each 
trim kit. The cable tie is inserted after the system has been 
restored for operation. The nylon cable tie is designed to 
allow, in case of an emergency, forceful turning of the valve 
handle to the ON position. As an alternative to the Model B 
Hydraulic Manual Emergency Station, the Model A Hydrau-

lic Manual Emergency Pull Box (see Reliable Bulletin 506) is 
also available and can be provided as an option.

Whenever ambient temperature conditions are high, the 

water temperature in the Model DDX Deluge Valve push-
rod chamber could possibly increase, thereby increasing 
the pressure in the chamber to values exceeding the rated 
pressure of the system. In an indoor installation where stan-
dard room temperatures are exceeded, a pressure relief kit 
may be needed. Pressure relief kit, P/N 6503050001, can 
be installed into the pushrod chamber’s releasing line to limit 
the pressure to 250 psi (17.2 bar).

Reliable Model DDX Deluge Valve with associated Type D 

Double Interlock Preaction Trims sizes 2” (50 mm), 2½” (65 
mm), 76 mm, 3” (80 mm), 4” (100 mm), 165 mm, 6” (150 
mm) and 8” (200 mm) are rated for use at a minimum water 
supply pressure of 20 psi (1.4 bar) and a maximum water 
supply pressure of 250 psi (17.2 bar) for 2” (50mm), 2½” 
(65mm), 3” (80mm), 76mm and 8” (200mm) valve sizes 
and 300 psi (20.7 bar) for 4” (100mm), 6” (150mm) and 
165mm valve sizes. Water supplied to the inlet of the valve 
and to the pushrod chamber must be maintained between 
40

°

F (4

°

C) and 140

°

F(60

°

C).

1A_COMMDDX_EMR

PLASTIC

TO

DRIP CUP

NYLON TIE

TO AUTOMATIC

RELEASING DEVICE(S)

FROM TOP OF PUSH

ROD CHAMBER

PUSH ROD CHAMBER

WATER PRESSURE GAUGE

TUBING

EMERGENCY MANUAL RELEASE STATION

NORMALLY CLOSED AND SECURED. ROTATE HANDLE DOWN

TO VENT PUSH ROD CHAMBER AND RELEASE SYSTEM.

Fig. 2

Summary of Contents for DDX

Page 1: ...m 165 mm 8 200 mm Bulletin 750 October 2022 Bulletin 750 October 2022 Technical Specifications and Instructions for Installation Operation and Maintenance Available with 175 psi 12 1 bar or 300 psi 20 7 bar Rated Solenoid Valve Externally Resettable Clapper One Main Drain 7 to 10 psi 0 5 to 0 7 bar Pneumatic Supervising Pressure Electric Electric Actuation Image subject to change ...

Page 2: ...in on 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes alarm devices air supply and required pressure gauges This trim set is avail able in individual loose parts in time saving segmented assembled kit forms or fully assembled to the Model DDX Deluge Valve with or without a control valve Listings Approvals Only when used with Reliable Trim Sets 1 Reliable s Type D Double Interlock Preaction Syste...

Page 3: ...RT ALARM PORT OUTLET EXTERNAL RESET HINGE RESTRICTION PUSH ROD CHAMBER INLET PUSH ROD CHAMBER OUTLET PUSH ROD CLAPPER IN LATCHED POSITION CLAPPER IN OPEN POSITION LEVER CLAPPER IN CLOSED POSITION INLET WEEP HOLE TO RESET CLAPPER NOTE PUSH ROD CHAMBER MUST BE VENTED TO DRAIN MODEL DDX VALVE SECTION VIEW MODEL DDX VALVE REAR VIEW Fig 1 3 ...

Page 4: ... Manual Emergency Pull Box see Reliable Bulletin 506 is also available and can be provided as an option Whenever ambient temperature conditions are high the water temperature in the Model DDX Deluge Valve push rod chamber could possibly increase thereby increasing the pressure in the chamber to values exceeding the rated pressure of the system In an indoor installation where stan dard room tempera...

Page 5: ...ed from improper fire pump settings un derground construction work or an improper venting of trapped air in the water supply piping System Design Considerations The automatic sprinklers releasing devices electric re leasing control equipment fire detection devices manual pull stations and signaling devices which are utilized with the Type D Double Interlock Preaction System must be UL or ULC Liste...

Page 6: ...ve seat Del uge valve shall have an external reset knob for resetting the clapper without requiring the removal of the valve face plate Pushrod chamber design shall consist of a stainless steel piston pushrod and spring assembly with diaphragm seal secured to the casting through a pushrod guide con structed of a synthetic engineering plastic to resist corro sion Casting shall have a bleeder hole l...

Page 7: ...erlock preaction system piping and be capable of restoring normal air pressure in the system within the time limits specified by NFPA 13 Unit shall include a mo tor mounted oil less piston compressor pressure gauge pressure switch check valve drain valve and safety relief valve Single phase motor shall have internal thermal pro tection Nitrogen Nitrogen cylinders provided by an approved source sha...

Page 8: ... 80 mm 3 500 89 mm 3 344 85 mm 11 32 9 0 mm 5 8 16 mm 4 100 mm 4 500 114 mm 4 334 110 mm 3 8 9 5 mm 5 8 16 mm 165 mm 6 500 165 mm 6 330 161 mm 3 8 9 5 mm 5 8 16 mm 6 150 mm 6 625 168 mm 6 455 164 mm 3 8 9 5 mm 5 8 16 mm 8 200 mm 8 625 219 mm 8 441 214 mm 7 16 11 mm 3 4 19 mm Threaded openings Per ANSI B 2 1 Flange Dimensions Flange T ype Nominal Pipe Size Bolt Circle Diameter Bolt Hole Diameter Fl...

Page 9: ... M M 1 6 5 M M 6 I N C H 1 5 0 M M 1 6 5 M M 4 I N C H 1 0 0 M M 4 I N C H 1 0 0 M M 3 I N C H 8 0 M M 3 I N C H 8 0 M M 2 1 2 I N C H 6 5 M M 7 6 M M 2 1 2 I N C H 6 5 M M 7 6 M M 2 I N C H 5 0 M M 2 I N C H 5 0 M M 1 5 10 50 100 500 0 1 0 5 PRESSURE LOSS BAR 0 1 1 10 10 100 1000 10000 FLOW RATE GPM PRESSURE LOSS PSI Fig 3 ...

Page 10: ...ion of the detection system and or sprinkler system subjected to fire conditions 8 Open the pushrod chamber supply valve and allow wa ter to fill the pushrod chamber Close the Model B Manual Emergency Station 9 Bleed all air from the actuation piping Open the so lenoid valve by operating a detector or an electric manual emergency station While water is flowing through the sole noid valve cause it ...

Page 11: ...then tighten se curely Ref Bulletin 613 2 Water leaking from Ball Drip This can be caused by either a water column on top of the clapper or a supply water leakage a Leakage due to water column This condition is caused by leakage past the clapper seal assembly Be sure the clapper seal and seat are free of any type of de bris or damage If nec essary follow steps below to replace the seal assembly an...

Page 12: ...em b Shut down the valve controlling water supply to the Del ugeValve Relievetheinletpressurebyopeningthemaindrain valve Close the pushrod chamber supply valve and open the Model B Manual Emergency Station c Remove the trim at the unions nearest to the pushrod chamber cover d Take the pushrod chamber cover off by removing the six retaining screws e Visually inspect the pushrod chamber cover and pi...

Page 13: ...13 750EXP_A Fig 4 ...

Page 14: ...1 10 37 8 30 33 20 31 5 16 36 2 42 5 6 34 38 9 IMPORTANT NOTE Early generation 4 and 6 DDX valves may incorporate a brass drop in seat Prior to ordering replacement parts confirm the presence of a stainless steel screw in seat or brass drop in seat For replacement parts for valves with brass drop in seat please contact Reliable Sprinkler Company Technical Services techserv reliablesprinkler com 29...

Page 15: ...1 Stainless Steel CF8M 18 95276006 Diaphragm 1 EPDM Polyester 19 95306267 N A N A N A RetainingRing 3 8 Shaft LeverPin 2 Stainless Steel 15 7 or 17 7 N A 95306267 N A N A RetainingRing Shaft LeverPin N A N A 95306269 N A Retaining Ring 5 8 Shaft Lever Pin N A N A N A 95316408 Retaining Ring Shaft Lever Pin 20 95306268 N A N A N A RetainingRing 3 8 Shaft HingePin 2 Stainless Steel 15 7 or 17 7 N A ...

Page 16: ... Size End Configuration Trim Assembly Loose Trim Segmentally Assembled Fully Assembled no Control Valve Fully Assembled with Control Valve Optional 300 psi 20 7 bar solenoid valve Note This trim assembly will include a spool piece with 1 4 outlet to accommodate push rod chamber supply piping Not available for 76mm or 165mm systems or systems using a flanged inlet Model DDX valve Service Kits Servi...

Page 17: ...t 2 End to end take out of Model DDX valve with flanged inlet where available see page 8 also reference Bulletin 519 3 Not applicable to 76mm or 165mm systems or systems using a flanged inlet Model DDX valve 4 2 systems include spool piece with outlet below valve dimension provided is total length of both components Reliable Automatic Sprinkler Co Inc 800 431 1588 Sales Offices 800 848 6051 Sales ...

Reviews: