07.03.02, Version 1.2 

User manual MR004DL/FA 

 

GmbH, Stettiner Str. 38, D-33106 Paderborn

LED signals

:  

Power

 (green): Power supply is O.K. 

Slave

 (yellow): M-Bus slave is transmitting 

Max

 (yellow): Maximum current exceeded

 

Short

 (red):  Over current (short circuit) 

 

RS232 interface: 

The M-Bus can be accessed via an RS232C interface. The signals TXD, RXD and GND 
(PC notations) are wired to terminals and to both DB9 connectors at the housing. The 
upper DB9 socket (female) is designed for a PC and the lower DB9 plug (male) for a 
modem. Only one of these three connectors can be used simultaneously. You can 
attach a 1:1 serial cable to PC or the modem cable to modem. The modem must be 
configured before it is connected (see addendum: “Modem configuration”).

 

 

Pinning of DB9 connectors: 

Pin 

Socket 

Plug 

Usage socket 

Usage plug 

RXD 

TXD 

Transmit to PC  

Receive from modem 

TXD 

RXD 

Receive from PC 

Transmit to modem 

DTR 

Unused 

Always active 

GND 

GND 

Ground potential 

Ground potential 

RTS 

CTS 

Handshake unused  Always active 

CTS 

RTS 

Always active 

Handshake unused 

Pin 1, 6 and 9 are not connected 
 

RS485 interface: 

The PW60 normally activates the receive mode on the RS485. On reception of data 
from the M-Bus slaves it switches to transmit mode (RS485 transmitter active). About 
37ms after the last received data bit (0) the receive mode is re-entered. The RS485 
interface of the PW60 is not addressable. There is an internal line termination of 1k

 

inside the PW60. A stronger line termination of 120

 can be obtained by connecting a 

resistor of  130

 between the terminals S+ and S-. 

 

Simultaneous use of interfaces: 

In case of a local readout using the keyboard of the remote display or during an 
automatical readout the RS485 and RS232 interfaces do not have access to the M-Bus. 
These functions and the contemporary use of the RS485 and RS232 interfaces can 
produce temporary disturbances in communication. 
 

Exchange of the fuse: 

Over voltages on the power supply input may cause the fuse to blow. Please switch off 
or disconnect the mains power (danger of life) before inserting a new fuse   (type 

5x20 

250V 0,16A slow blow / 5x20 110V 0,25A slow blow for –US version

). The fuse is 

removed by pulling the fuse holder. You can use a screw driver to open the fuse holder. 
 

Summary of Contents for MR004C

Page 1: ...es Article no MR004C Level converter for 60 unit loads in housing for DIN rail MR04W Level converter for 60 unit loads in wall mountable housing MR004FA Remote display and level converter for 60 unit...

Page 2: ...Datalogger MR004DL Both devices can be operated as a transparent level converter and as a remote display with keyboard or by remote control The datalogger adds the possibility to automatically read a...

Page 3: ...ceive of PC RS485 S S Terminals for RS 485 interface observe polarity M Bus M M M Bus terminals 3 pairs M Bus devices are wired polarity independent in parallel to the same line The signs mark only th...

Page 4: ...s active Handshake unused Pin 1 6 and 9 are not connected RS485 interface The PW60 normally activates the receive mode on the RS485 On reception of data from the M Bus slaves it switches to transmit m...

Page 5: ...he number of connected meters You can connect 60 meters specified with 1 unit load 1 5mA but only 30 meters specified with 2 unit loads 3mA Are there defective slaves or open cable ends lying in the e...

Page 6: ...loads with power Technical data Supply Voltage 230VAC 50Hz 25W respective 110VAC 50Hz 25W US version Environment Operating temperature 0 45 C Storage temperature 10 60 C Humidity 10 70 non condensing...

Page 7: ...he cable diameter The maximum allowed resistance of the cable RL between the MR004DL FA can be estimated with the following formulas N no of unit load each 1 5mA N slaves at end of cable RL 9467 15 x...

Page 8: ...ith LEDs under the terminal lid compartment and also on the LCD If there are problems with interpretation of the M Bus data the display shows Status Error The list of errors is shown on the LCD after...

Page 9: ...ng Fservice the device includes 4 keys and a backlighted display for comfortable local access to all functions The buttons give a very precise mechanical feedback and each input is acknowledged by an...

Page 10: ...activated temporary or permanent error bist in the Status byte an E will be shown The first character follows one digit for the device 0 main device Filtering data To make the readout of data easy th...

Page 11: ...ed to these functions Shows the list of slaves Allows editing of Primary address ID and baudrate The meter data of all devices are read and displayed on the LCD based on the list of slaves After selec...

Page 12: ...YY Shows the ID of location description Change of passcode B global access Selects passcode mode Standard requests passcode on startup Access by ID Adr requests ID address for single read Manually sta...

Page 13: ...tected meters You should check the entries of the list of slaves from the menu List of slaves Show edit list Editing the list of slaves The entries in the list of slaves can also be edited by the user...

Page 14: ...upport this format Therefore we offer a special solution called M Bus modem for use with any level converter and also with MR004DL FA in level converter mode In spite of this the command mode makes us...

Page 15: ...ll with data In this example there is enough memory to store minimum 7 x 65536 5462 83 readouts The practice shows that usualy there are often installations with less meters and shorter M Bus telegram...