background image

PAGE 11

Reimers Electra Steam, Inc.  01/10/2022

HLR 120‐180 Manual ‐ English

REV 1

Frequency:  Under  normal  operating 

conditions  test  valve  every  two  (2) 

months.  Under  severe  service 

conditions  or  if  corrosion  and/or 

deposits are noticed within the valve 

body,  testing  must  be  performed 

more  often.  A  test  must  also  be 

performed  at  the  end  of  any  non­

service period.

Test 

the 

safety 

relief 

valve 

(preferably  near  its  maximum 

pressure  setting  by  holding  the  test 

lever  fully  open  for  at  least  5 

seconds  to  flush  the  valve  seat  free  of  sediment  and 

debris. Then release and permit the valve to snap shut.

­ Close the water inlet and outlet stop valves (FIGURE 10)

­ Turn off and lock out all boiler power supplies

­ Ensure  that  the  boiler  drain  valve  (FIGURE  10)  is  piped 

to a safe point of discharge

­ Open  the  boiler  drain  valve  carefully  and  drain  the 

pressure vessel. As soon as there is no pressure present 

in the vessel, open the bleeder valve (FIGURE 7) slightly 

to break the vacuum

* Water Inlet and Outlet Stop Valves are not provided with 

the boiler

­ Remove  the  left  pressure  vessel  jacket  end  cap  to 

access the heating elements

­ Label the wires of heating elements and disconnect from 

the terminals

­ Remove  the  four  (4)  nuts  from  each  heating  element 

flange  and  pull  the  elements  slowly  out  of  the  pressure 

vessel

­ Inspect  and  if  necessary  remove  with  a  stiff  wire  brush 

rust, calcium or other deposits from the element rods

­ Insert a flash light through one heating element opening 

and  inspect  through  the  second  opening  the  inner  walls 

of the pressure vessel. It is normal that the inner walls of 

the  vessel  be  covered  by  a  layer  of  red,  brown  or  black 

layer  of  rust.  However, 

rough  pressure  vessel 

surface  and  layers  of  rust 

peeling off the surface are 

an  indication  for  severe 

corrosion.  In  such  case, 

contact  a  water  treatment 

company.

­ Install the heating elements back into the boiler pressure 

vessel, following the above procedure in reverse order. 

­ After  installing  the  pressure  vessel  jacket  end  cap,  turn 

on all power supplies of the boiler. 

­ Flip the red POWER switch of the boiler controller to the 

ON­position  and  leave  the  operating  mode  selector 

switch in the middle (OFF­position)

­ Observe  the  LOW  WATER  alarm  light  in  the  boiler 

controller front panel. If it turns ON, the low water cut­off 

device works properly.

­ Close  the  boiler  drain  valve,  open  the  inlet  and  outlet 

valves  and  with  the  bleeder  valve  open,  refill  the  boiler 

pressure  vessel.  Close  the  bleeder  valve  as  soon  as  it 

discharges water.

­ Press  the  LOW  WATER  RESET  switch.  The  LOW 

WATER alarm light should turn OFF.

­ The hot water boiler should be ready for operation.

3.5.1 Testing the Electronic Low Water Cut­Off Device Only

Frequency: Any time.

­ Press and hold the LOW WATER CUT­OFF TEST switch 

on the boiler controller panel

­ After  3  seconds,  the  HEATING  indicator  light  –  if  it  was 

ON  –  will  turn  OFF;  the  LOW  WATER  alarm  indicator 

light will turn ON

­ Press the LOW WATER RESET switch to de­activate the 

LOW WATER alarm 

3.5.2  Testing  the  Entire  Low  Water  Cut­Off  System 

(Electronic Low water Cut­Off  Low Water probe)

Frequency: 

90 days after installation, then once every year

­ Flip  the  boiler  operating  mode  selector 

switch to the middle (OFF­position)

­ Close  the  water  inlet  and  outlet  stop 

valves (FIGURE 10)

­ Turn  off  and  lock  out  all  boiler  power 

supplies

­ Ensure  that  the  boiler  drain  valve 

(FIGURE 10) is piped to a safe point of 

discharge

­ Open  the  boiler  drain  valve  carefully 

and  drain  the  pressure  vessel. As  soon 

as  there  is  no  pressure  present  in  the 

vessel,  open  the  bleeder  valve 

(FIGURE  7)  slightly  to  break  the 

vacuum.

­ Flip the red POWER switch of the boiler controller to the 

ON­position  and  leave  the  operating  mode  selector 

switch in the middle (OFF­position)

­ Observe  the  LOW  WATER  alarm  light  in  the  boiler 

controller front panel. If it turns ON, the low water cut­off 

device works properly.

­ Close  the  boiler  drain  valve,  open  the  inlet  and  outlet 

3.4 Element Inspection, Replacement, and Element 

Cleaning

WARNING

Element Rods

3.5 Testing the Low Water Cut­Off Device

3.3 Testing the Safety Relief Valve

CAUTION

Before testing, make certain that 

the discharge pipe is properly 

connected to the valve outlet and 

arranged to contain and safely 

dispose of boiler discharge.

Maintenance work must be 

performed by experienced 

personnel only. Ensure boiler is 

cold and drained and has no 

pressure or electricity.

Water Inlet 

Stop Valve*

Water Outlet 

Stop Valve*

FIGURE 9

FIGURE 10

Boiler Drain 

Valve*

Selector 

Switch

FIGURE 12

FIGURE 11

Summary of Contents for HLR120

Page 1: ...120 180 Manual English REV 1 4407 Martinsburg Pike Phone 540 662 3811 Clear Brook VA 22624 Fax 540 665 8101 USA email sales reimersinc com web www reimersinc com _______ MODEL ________ SERIAL HLR 120...

Page 2: ...Boiler Startup 9 Honeywell Controller T775P2003 Setup 9 Honeywell Controller T775P2003 Setting Operating Parameters 9 Boiler Startup 9 Boiler Maintenance 10 Tightening the Electrical Terminal Connect...

Page 3: ...c contactors Internal branch circuit fusing Main supply power distribu on block Indicator lights for POWER HEATING CIRCULATOR PUMP and ALARMS Pressure and temperature gauges Applications Space Hea ng...

Page 4: ...t are normally expendable in usual course of operation Claims against carriers for damage in transit must be filed by the buyer Reimers liability if any will not exceed the price of Reimers products c...

Page 5: ...es Located on electrical enclosure door Located on end caps of cylindrical boiler pressure vessel jacket Located on end caps of cylindrical boiler pressure vessel jacket This manual contains safety me...

Page 6: ...he internal pressure of the boiler It can fail Periodically have your boiler inspector compare the gauge with a known gauge utilizing the test valve arrangement provided 6 REGISTRATION Most states and...

Page 7: ...he working space or exposed live parts on both sides of the working space that are effectively guarded by insulating materials Condition 2 Exposed live parts on one side of the working space and groun...

Page 8: ...recognized water treatment company located in your area Recommended levels for boiler feed water Recommended levels for boiler water water inside pressure vessel when boiler is operating The safety va...

Page 9: ...D LAG FOFO 1 3 3 9 DI OPTIONS DISABLE 1 3 3 10 SHOW RT NO EXIT 1 3 4 Setting up the Stages Not set EXIT 1 4 Setup Alarms Not set EXIT PROGRAMMING OUTPUT STAGES WITH NO RESET 3 1 Entering Program Mode...

Page 10: ...E alarm light will turn on and all heating stages turn off immediately Frequency During boiler installation 90days after boiler installation and then annual Re tighten the terminals of the contactors...

Page 11: ...ch in the middle OFF position Observe the LOW WATER alarm light in the boiler controller front panel If it turns ON the low water cut off device works properly Close the boiler drain valve open the in...

Page 12: ...s the LOW WATER RESET switch The LOW WATER alarm light should turn OFF The hot water boiler should be ready for operation 4 Troubleshooting WARNING Ensure that the boiler is cold and has no pressure E...

Page 13: ...s list for HLR 120 180 WARNING Use Reimers replacement parts All components are designed and approved to be used in this Underwriters Laboratories listed and ASME National Board Stamped boiler Failure...

Page 14: ...PAGE 14 Reimers Electra Steam Inc 01 10 2022 HLR 120 180 Manual English REV 1 NOTE When ordering parts please give boiler Model and Serial Number and detail shipping instructions...

Reviews: