2.2 TURNING PG 600 S ON WITH NO GRID POWER

Press and hold ON push button for 2 sec. to turn on PG 600 S. The display indicates operation from a 

battery (the battery shall be connected). As soon as grid power supply is restored, the display will show 

the input voltage and PG 600 S will work normally, charging the battery. 

2.3 TURNING PG 600 S OFF 

PG 600 S can be turned off by pressing and holding the OFF push button for at least 3 sec. The display 

will go off. WARNING! The battery is not being charged. It will not backup anything in case of a power 

supply failure, however as soon as the power supply is restored, it will switch on. In order to prevent the 

UPS from automatic switching on, it shall be disconnected from the mains. Pay attention to the fact that 

the earth protection of devices connected to PG 600 S will be interrupted.

Warning

• 

For safety reasons, it is recommended not to modify the cables supplied.

• 

Make sure the power supply to PG 600 S is safely earthed.

• 

A mains socket or circuit breaker shall be located close to the appliance and shall be easily 

accessible. 

• 

Never disconnect the 230 V power supply to PG 600 S when it is running - the earth protection 

of both PG 600 S and the connected load would be interrupted.

• 

Check that when all the loads are connected, the total earth leakage current does not exceed  

2.7 mA (EN 62040-1-1).

• 

When PG 600 S gets plugged to power supply, the battery starts being charged. At the same 

time, the internal cooling fan starts up. After the battery is fully charged, the fan will remain off 

unless the inner temperature of PG 600 S starts rising. 

• 

In case of a power supply breakdown, the fan turns on, cooling the inverter if needed.

• 

When power supply is restored, the timer turns on and the cycle is repeated. 

3 OPERATION MODES

Power grid operation

 

The input voltage is shown on the display, the battery is being charged or is already charged. 

Battery operation 

No input voltage is shown on the display. PG 600 S shall supply backup power until the grid power 

supply is restored or the battery discharged. When the battery voltage becomes too low, intermittent 

audio alarm will sound. From that moment, PG 600 S may turn off any time depending on the load. As 

soon as grid power supply is restored, charging the battery will require at least 12 hours (preferably 24). 

Alarm 

When overloaded, PG 600 S disconnects the output and sounds an uninterrupted audio signal. It will 
not function as a power backup until the load gets disconnected and PG 600 S turned off and on again. 

Operation mode description

Operation mode

Description

Display 

Fault

If a fault occurs, the UPS will go to a Fault mode. The 

fault code will be shown on the display.

Charging

In this mode, the battery will be charged from the grid. 

Should the input power supply show abnormal values, 

the device will either turn off or go to the Fault mode.

Power grid

The load is power suppled directly from the grid. At the 

same time, the battery is also being charged from the 

mains.

If the input voltage is outside the range (200-240V), the 

automatic voltage regulator will intervene. Should the 

input power supply show abnormal values, the device will 

go to the Battery mode.

Battery

The UPS will draw el. energy from the battery and supply 

it to the load. 

15

Summary of Contents for PG 600 S

Page 1: ...www regulus eu PG 600 S PG 600 S EN Installation and Operation Manual PG 600 S BACKUP POWER SUPPLY...

Page 2: ...TURES DESCRIPTION 5 1 1 GENERAL DESCRIPTION 5 1 2 FRONT PANEL 6 1 3 REAR PANEL 9 2 INSTALLATION 9 2 1 RECOMMENDED WIRING 9 2 2 TURNING PG 600 S ON WITH NO GRID POWER 15 2 3 TURNING PG 600 S OFF 15 3 O...

Page 3: ...a sufficiently spacious and ventilated room enabling good access It shall never be exposed to weather Whenever handling a battery and PG 600 S the PG 600 S shall be turned off and disconnected from th...

Page 4: ...se gases escape into the air In batteries with pressure valves most of these gases recombine inside the battery and just a very small portion escapes into the air Always ensure good ventilation for ba...

Page 5: ...signed for manual control do not use sharp or pointed items PG 600 S is not designed for operation in explosive environment Both PG 600 S and the battery shall be placed in a sufficiently ventilated s...

Page 6: ...and the red LED flashes At the same time the symbol Overload warning The audio alarm sounds every 2 s and the red LED flashes At the same time the symbol Adjustment warning The audio alarm sounds eve...

Page 7: ...presented in the table below Optional info Display Imput Input voltage 230 V input frequency 50 Hz Battery Battery voltage 24 8 V battery current 1 A Output Output voltage 230 V output frequency 50 Hz...

Page 8: ...blink 75 100 The bottom three bars are lit and the top one blinks Float mode Batteries are fully charged All bars are lit Battery mode Info will contain data on the battery capacity Battery voltage D...

Page 9: ...the internal cooling fan also starts running 5 Connect your pump or another load by plugging its cable into the socket of PG 600 S It is inevitable to stick to a TN S wiring system 6 Press and hold O...

Page 10: ...V 50 Hz CIRCUIT WITHOUT BACKUP IR 12 SMART CONTROLLER PUMP WITHOUT BACKUP DETAILED PIC SHOWING TERMINAL BOARDS MARKING AND WIRING PUMP WITH BACKUP CIRCUIT WITH BACKUP Do respect the separation betwee...

Page 11: ...HOUT BACKUP IR 12 SMART CONTROLLER PUMP WITHOUT BACKUP DETAILED PIC SHOWING TERMINAL BOARDS MARKING AND WIRING PUMP WITH BACKUP CIRCUIT WITH BACKUP Do respect the separation between the circuits with...

Page 12: ...230 V 50 Hz CIRCUIT WITHOUT BACKUP IR 12 SMART CONTROLLER PUMP WITHOUT BACKUP DETAILED PIC SHOWING TERMINAL BOARDS MARKING AND WIRING PUMP WITH BACKUP CIRCUIT WITH BACKUP Do respect the separation be...

Page 13: ...13 Fireplace Backup of a fireplace circulation pump with flue thermostat MAINS 230 V 50 Hz PUMP WITH BACKUP FLUE THERMOSTAT BATTERY PG 600 S BACKUP POWER SUPPLY...

Page 14: ...r Pump backup STDC TRS etc controller Backup of a PWM controlled pump PG 600 S BACKUP POWER SUPPLY BATTERY PG 600 S BACKUP POWER SUPPLY BATTERY MAINS 230 V 50 Hz STDC TRS etc controller MAINS 230 V 50...

Page 15: ...remain off unless the inner temperature of PG 600 S starts rising In case of a power supply breakdown the fan turns on cooling the inverter if needed When power supply is restored the timer turns on...

Page 16: ...V default value is 10 5 V 23 Backlight OFF default ON 24 Sound alarm ON default OFF 29 Charging from the mains Charging from the mains enabled default Charging from the mains disabled 30 UPS function...

Page 17: ...ted output 06 Too high output voltage from the UPS 07 Overload 11 Main relay faulty 41 Too low input voltage 42 Too high input voltage 43 Too low input frequency 44 Too high input frequency 45 Automat...

Page 18: ...age Check battery technical data Fault code 04 Too low battery voltage Check battery technical data Fault code 05 Short circuited output Disconnect the load and restart Fault code 06 UPS output voltag...

Page 19: ...utput waveform backup mode 16 4 kg 39 4 kg dimensions d x w x h weight ambient working temperature ambient relative humidity noise level Battery Type nominal voltage number capacity 18 Ah 12 V 44 Ah 1...