CSE2 MIX F G60 1F twin-line pump station is designed for mixed heating circuits. It provides
flow through the heating system, mixes to the outlet temperature using a motorized mixing
valve (controlled by an external controller). The pump station includes a filter with magnet,
so it is also suitable for older steel pipe systems. It can be easily mounted on a wall or on
a manifold for multiple heating circuits.
2. PUMP STATION DESCRIPTION AND DATA
Main Features
Description
The twin-line pump station consists of:
● Grundfos UPM3 AUTO pump
● 2 ball valves w. sensor sheath
● check valve
● filter with strainer&magnet
● LK 840 mixing valve w. actuator
● thermometers, insulation
Working fluid
water, antifreeze heat-transfer fluid for heating systems
Installation
vertically on a wall or manifold (125 mm pitch)
Connections
4 x G 1“ F
Code
19103
Data for CSE2 MIX F G60 1F Pump Station
Fluid working temperature
5 - 95 °C
Max. working pressure
10 bar
Min. working pressure
0.5 bar
Ambient temperature
5 - 40 °C
Max. relative humidity
80%, non condensing
Pump power supply
1 ~ 230 V, 50 - 60 Hz
Pump station max. power input 42 W
Mixing valve Kvs
6.3 m
3
/h
Max. pressure difference
5 m H
2
O (at mixing valve inlets)
Leak rate
< 1% Kvs at 5 mH
2
O pressure difference (at mixing valve inlets)
Mixing valve power supply
230 V, 50 Hz; from external controller w. 3-point control
Valve shift time
120 s
Insulation material
EPP RG 60 g/l
Overall dimensions
360 x 181 x 245 mm
Total weight
6.7 kg
Connections
4 x G 1“ F
Pump Station Pressure Drop Graph