4.1 Check Valve

The non-return valve prevents the tank from cooling down due to gravity circulation when the sun is 

not shining. It is located between the ball valves and can therefore be removed and cleaned without 

having to drain the solar fluid from the entire circuit.

Správná poloha při provozu.

If the mark is on the left, the check valve is set to the position for normal 

operation.  If  you  need  to  open  the  valve  (e.g.  to  drain  fluid  from  the 

system), turn the check valve control with the red dot to the right.

This will deactivate the check valve function.

For correct operation of the pump station during normal use it is important 

to have the check valve control always in the right position, i.e. the mark 

on the left (see pic.).

!

4.2 Ball Valves

Ball valves are used to separate the pump station from the solar circuit. During servicing (including 

cleaning of the check valve) there is no need to drain the fluid from the solar system. For greater rigi-

dity of the hydraulic part of the pump station, the upper ball valve is attached to the fixing back plate.
The upper ball valve is operated by a lever which is not located on the valve during operation.  

A wrench or pliers must be used to operate the lower ball valve, which is part of the flow indicator. 

Turning the lever or the key or pliers a quarter turn to the right closes the ball valve. It opens when 

the lever is turned to the left. Before closing / opening the ball valve, it is necessary to remove the 

front part of the insulation. As a result, closing the system is reserved for installation or service 

technicians only. Thus, the user cannot simply close the solar circuit and cause stagnation and sub-

sequent degradation of the solar fluid.
The ball valves are equipped with apacking with two O-rings with dimensions of 8.7 x 1.8 mm that can 

be easily replaced by removing the control element with stop ends and loosening the packing nut with 

a # 21 wrench.

The safety valve, expansion vessel and upper filling ball valve always remain connected to the 

solar thermal system, even if the ball valves are closed! For this reason, never try to separate them 

from the filled solar system, as there is a risk of serious injury and damage to the solar system!

Never close the drain line of the safety valve, it must always be free for any liquid leaking from the 

safety valve!

5. Accessories

Accessories (not included in supply)

Code

ETT-N heating element w. connector, 2 kW

16942

ETT-N heating element w. connector, 3 kW

16943

Connector for CSE SOL SRS1 T-E

16940

Straight compression fitting, Cu 22 x Cu 22 

7629

Straight Compression Fitting Adaptor, Cu 22 x 

G 3/4“ M

13695

These accessories are not included in supply. An ETT-N heating element with connector (16942 or 16943) 

is needed when the pump station is to be used following the hydraulic variant 1 (chapter 7.1). The pipe 

fittings (7629 and 13695) are intended for connecting a waste pipe to the safety valve. 

Right position during operation.

Summary of Contents for CSE SOL G SRS1 T-E

Page 1: ...www regulus eu CSE SOL G SRS1 T E CSE SOL G SRS1T E EN Installation and Operation Manual CSE SOL G SRS1 T E SOLAR PUMP STATION...

Page 2: ...essary to connect only the collector temperature sensor An electric heating element of up to 3 kW output can be connected to the pump station The pump station is equipped with a special socket for thi...

Page 3: ...at 50 C 1 2 bar at 90 C 1 8 bar at 110 C this condition is met for current installations when the initial system pressure is set following the formula see the Instructions for solar collectors p 1 3...

Page 4: ...N THE UPPER PART OF INSULATION 7 PRESSURE GAUGE 8 EXPANSION VESSEL CONNECTION POINT 3 4 M 9 6 BAR SAFETY VALVE 10 FILLING BALL VALVE 11 SPANNER FOR CONTROL OF BALL VALVE W SIDE OUTLET 12 DRAIN BALL VA...

Page 5: ...r is turned to the left Before closing opening the ball valve it is necessary to remove the front part of the insulation As a result closing the system is reserved for installation or service technici...

Page 6: ...STATION SRS1 T CONTROLLER KEY 1 hot water storage tank 2 ETT N electric heating element 3 solar collectors 4 solar pump station 5 pump station for DHW recirculation CSE TVMIX ZV 6 safety kit for HW st...

Page 7: ...7 1 Overview of Hydraulic Variants 1 3 5...

Page 8: ...controlled internally without PWM signal by selecting a proper mode and pump curve externally by PWM C control signal profile for solar systems WARNING IMPORTANT The pump permits to be controlled als...

Page 9: ...n the current system pressure drop CONTROL MODE DESCRIPTION Constant pressure I The lowest curve of constant pressure II The middle curve of constant pressure III The highest curve of constant pressur...

Page 10: ...DE green LED FLASHING INTERNAL 1 Proportional pressure AUTOADAPT 2 Constant pressure AUTOADAPT 3 Proportional pressure I 4 II 5 III 6 Constant pressure I 7 II 8 III 9 Constant speed I 10 II 11 III DIS...

Page 11: ...mance Setting selection To select your desired setting press the button repeatedly until you find the setting you need see the table above If you pass the desired setting you have to go one more round...

Page 12: ...o the fill and drain ball valves using hoses see Chap 4 and open these valves After filling the solar thermal system close the fill and drain ball valves disconnect the hoses and re open the ball valv...

Reviews: