22
Menus X.9 I/O
After the last configuration menu there is a menu where you can look at the actual values of
all the inputs and outputs. This menu can also be accessed directly from the Base Display by
twisting the encoder knob counter clockwise and then pressing. See chapter 6.
Menu OK
Last of the configuration level menus is the OK-menu. To leave the configuration level, go to
this menu and press the encoder knob.
On exit from the configuration level you will be returned to the Basic level.
There is also a time-out function that will automatically exit the configuration level after 5
minutes of inaction.
Storage of settings
All configuration settings become valid as soon as they are entered by klicking the encoder
knob. They are however not written to the flash memory until you exit the configuration
level either via the OK menu or via the time-out function.
To exit the configuration level without saving the changes to flash memory, cut the supply
voltage when still in the configuration level. All values will be kept as they were before you
entered the configuration level.
Reset to factory setting
The OP5 can be reset to factory settings by configuring Humidity control (mode 3) and
setting the P-band to 99. Then cut the power supply. When power is reapplied all
configuration settings will be reset to factory setting.