19
Chapter 8 Configuration
All the configuration menus lie in the 10-seconds level. This level is accessed from the Base
Display by pressing and holding the encoder button for 10 seconds.
There are numerous configuration menus covering all available options and combinations.
In some cases, making a certain choice in one menu will mean that you will only see certain
other menus. For example, the menu for setting the damper minimum limit is only shown if
you have configured AO2 to be a damper control output.
Menus 1.0 – 5.0
In the first set of configuration menus you choose which of the five control modes you wish
to run. The upper text row, the lower text row number and the first digit in the menu-number
show which control mode is at hand.
1. Temperature control
2. CO2-control
3. Humidity control
4. Pressure control
5. Pressure control with outdoor compensation
Menu X.1 Output signals (Control mode 1 only), Transmitter range
(Control modes 2, 3, 4 and 5)
Control mode 1.
For temperature control there is a choice of 8 different output signal combinations. Select
one fitting the application on hand.
Output
Graphic
AO1
/
AO2
symbol
symbol
1. Heating
/
-
\
2. Cooling
/
-
/
3. Heating
/
Cooling
\ /
4. Heating
/
Heating
\ \
5. Cooling
/
Cooling
/ /
6. Heating
/
Damper
\ /
7. Cooling
/
Damper
\ /
8. Change-over
/
-