E-BACNET2-V manual, revision B
Chapter 3
Configuration
7
This will display the following window, containing the settings that can be made:
IP
It is possible either to let the network’s DHCP server assign the converter an IP address or to assign
it a fixed IP address.
BACnet
Permits setting of:
Device ID
: The device ID number of the object.
Location
: Place, e.g. ”room23”.
Description
: Description, e.g. ”AHU01” (air handling unit 01).
Name
: The desired name of the converter. If adding a dollar sign ($) after the name, device
ID will be automatically added after it.
UDP Port
. BACnet IP standard is 47808.
The checkbox “Foreign device” is used when E-BACNET2-V is to be connected to another IP
network. It is then neccessary to state the BBMD address. An example of this is when E-
BACNET2-V is stand-alone and connecting to a SCADA system over the Internet. The BBMD
address is handled by the network administrator.
Station
Used to state the PLA:ELA address for Corrigo E on the RS485 side. The Corrigo E standard
address is 254:254.
The “Debug” checkbox is used to set the converter to debug mode. This function requires a special
version of the converter, and is not normally used.
Once all settings has been made, press ”Save” in order to upload the settings to the converter.