E-BACNET2-V manual, revision B 

Chapter 3 

  Configuration 

7  

This will display the following window, containing the settings that can be made: 

 

IP

 

It is possible either to let the network’s DHCP server assign the converter an IP address or to assign 
it a fixed IP address. 

BACnet

 

Permits setting of:  

 

Device ID

: The device ID number of the object. 

 

Location

: Place, e.g. ”room23”. 

 

Description

: Description, e.g. ”AHU01” (air handling unit 01). 

 

Name

: The desired name of the converter. If adding a dollar sign ($) after the name, device 

ID will be automatically added after it. 

 

 

UDP Port

. BACnet IP standard is 47808.  

The  checkbox  “Foreign  device”  is  used  when  E-BACNET2-V  is  to  be  connected  to  another  IP 
network.  It  is  then  neccessary  to  state  the  BBMD  address.  An  example  of  this  is  when  E-
BACNET2-V  is  stand-alone  and  connecting  to  a  SCADA  system  over  the  Internet.  The  BBMD 
address is handled by the network administrator. 

Station

 

Used  to  state  the  PLA:ELA  address  for  Corrigo  E  on  the  RS485  side.  The  Corrigo  E  standard 
address is 254:254. 

The “Debug” checkbox is used to set the converter to debug mode. This function requires a special 
version of the converter, and is not normally used. 

Once all settings has been made, press ”Save” in order to upload the settings to the converter. 

Summary of Contents for E-BACNET2-V

Page 1: ...E BACNET2 V manual Copyright AB Regin Sweden 2012 Copyright AB Regin Sweden 2012...

Page 2: ...software described in this document is supplied under licence by Regin and may be used or copied only in accordance with the terms of the licence No part of this document may be reproduced or transmit...

Page 3: ...HAPTER 3 CONFIGURATION 6 Refresh 6 Wink 6 Edit Change settings 6 Upgrading the software version of the unit 8 APPENDIX 1 LIST OF VARIABLES FOR E BACNET2 V 10 Analog Inputs 10 Analog Values 11 Binary I...

Page 4: ...ace via the PLA ELA address 254 254 To change these settings see chapter 3 The Corrigo E controller is connected to the converter with the supplied cable and communicates with the SCADA system via the...

Page 5: ...LAN1 port of the converter and a network port The converter may also be connected directly to a computer but this requires a crossover RJ45 cable not included Connect the power supply to the converter...

Page 6: ...able converters connected to the network are displayed Refresh Pressing the Refresh button will update the list of converters Wink Wink is a function that can be used to ensure that the correct physic...

Page 7: ...atically added after it UDP Port BACnet IP standard is 47808 The checkbox Foreign device is used when E BACNET2 V is to be connected to another IP network It is then neccessary to state the BBMD addre...

Page 8: ...r is turned on the unit will beep once The upgrade procedure has now started 7 Wait between 30 and 60 seconds and the unit will beep again The procedure is now finished and the E BACNET2 V unit has be...

Page 9: ...Appendix I...

Page 10: ...a No Cor_EAFPressure Analog Input 7 Current pressure extract air Pa No Cor_DeIcingTemp Analog Input 8 De icing temperature C No Cor_FrostprotectionTemp Analog Input 9 Frost protection temperature C No...

Page 11: ...t signal No Cor_HumidityPID_Output Analog Input 39 Humidity controller output signal No Analog Values Object name Object ID Description Unit Adjustable Cor_SupplySetpoint Analog Value 0 Supply air set...

Page 12: ...igh supply air temperature C Yes Cor_EfficiencyLowLimit Analog Value 26 Alarm low efficiency Yes Cor_FrostLimit Analog Value 27 Alarm limit frost protection C Yes Cor_RoomHighLimit Analog Value 28 Ala...

Page 13: ...ormal active No Cor_ExtendedRunActiveHalf Binary Input 16 Extended running reduced active No Cor_DeIcingActive Binary Input 17 De icing function active No Cor_RecycleRunActive Binary Input 18 Recircul...

Page 14: ...in manual mode No Cor_AlaPt_39 Binary Input 57 EAF in manual mode No Cor_AlaPt_40 Binary Input 58 Frequency converter EAF in manual mode No Cor_AlaPt_41 Binary Input 59 Heating battery in manual mode...

Page 15: ...converter SAF No Cor_AlaPt_80 Binary Input 88 Communication error frequency converter EAF No Cor_AlaPt_81 Binary Input 89 Communication error expansion unit 1 No Cor_AlaPt_82 Binary Input 90 Communica...

Page 16: ...ort control cooling 9 CO2 control 10 Free cooling 11 Full speed stop 12 Fan stop No Multistate Values Object name Object ID Description Unit Adjustable Cor_AirUnitAutoMode Multistate Value 0 Manual se...

Page 17: ...Box 116 S 428 22 K llered Sweden AB Regin Head office Phone 46 31 720 02 00 Fax 46 31 720 02 50 info regin se www regin se R E G I N T H E C H A L L E N G E R I N B U I L D I N G A U T O M A T I O N...

Reviews: