Object name

 

Object ID

 

Description

 

Unit

 

Adjustable

 

Cor_EAF 

Analog Input, 23 

Current output EAF 

No 

Cor_Humidity 

Analog Input, 24 

Current output 
dehumidification/humidification 

No 

Cor_Split 

Analog Input, 25 

Current output split 

No 

Cor_ExtraSeqCV1 

Analog Input, 26 

Current output Y4-extra sequence 

No 

Cor_Efficiency 

Analog Input, 27 

Heat exchanger efficiency 

No 

Cor_SAFRunTime 

Analog Input, 28 

Running time SAF 

No 

Cor_EAFRunTime 

Analog Input, 29 

Running time EAF 

No 

Cor_SupplyPID_SetP 

Analog Input, 30 

Calculated supply air setpoint at 
outdoor compensated setpoint 

°C 

No 

Cor_SupplyPID_Output 

Analog Input, 31 

Supply air controller output signal 

No 

Cor_ExhaustPID_Output 

Analog Input, 32 

Extract air controller output signal 

No 

Cor_SAFPID_Output 

Analog Input, 33 

Output signal SAF 

No 

Cor_EAFPID_Output 

Analog Input, 34 

Output signal EAF 

No 

Cor_FrostPID_Output 

Analog Input, 35 

Warming controller output signal 

No 

Cor_CO2PID_Output 

Analog Input, 36 

CO

2

 controller output signal 

No 

Cor_RoomPID_Output 

Analog Input, 37 

Room controller output signal 

No 

Cor_DeIcePID_Output 

Analog Input, 38 

De-icing controller output signal 

No 

Cor_HumidityPID_Output 

Analog Input, 39 

Humidity controller output signal 

No 

Analog Values

 

Object name

 

Object ID

 

Description

 

Unit

 

Adjustable

 

Cor_SupplySetpoint 

Analog Value, 0 

Supply air setpoint if supply air 
control is selected 

°C 

Yes 

Cor_ExtractSetpoint 

Analog Value, 1 

Extract air setpoint if extract air 
control is selected 

°C 

Yes 

Cor_SAFFullspeedPressure 

Analog Value, 2 

Setpoint normal speed supply air 
fan, frequency control pressure 

Pa 

Yes 

Cor_SAFHalfspeedPressure 

Analog Value, 3 

Setpoint reduced speed supply air 
fan, frequency control pressure 

Pa 

Yes 

Cor_EAFFullspeedPressure 

Analog Value, 4 

Setpoint normal speed extract air 
fan, frequency control pressure 

Pa 

Yes 

Cor_EAFHalfspeedPressure 

Analog Value, 5 

Setpoint reduced speed extract air 
fan, frequency control pressure 

Pa 

Yes 

Cor_CO2Setpoint 

Analog Value, 6 

Setpoint CO

2

 

ppm 

Yes 

Cor_SAFFullspeedAirFlow 

Analog Value, 7 

Setpoint normal speed supply air 
fan flow 

m

3

/h 

Yes 

Cor_SAFHalfspeedAirFlow 

Analog Value, 8 

Setpoint reduced speed supply air 
fan flow 

m

3

/h 

Yes 

Cor_EAFFullspeedAirFlow 

Analog Value, 9 

Setpoint normal speed extract air 
fan flow 

m

3

/h 

Yes 

Cor_EAFHalfspeedAirFlow 

Analog Value, 10 

Setpoint reduced speed extract air 
fan flow 

m

3

/h 

Yes 

Cor_NeedHeatStart 

Analog Value, 11 

Room temperature for start of 
support control heating 

°C 

Yes 

Summary of Contents for E-BACNET2-V

Page 1: ...E BACNET2 V manual Copyright AB Regin Sweden 2012 Copyright AB Regin Sweden 2012...

Page 2: ...software described in this document is supplied under licence by Regin and may be used or copied only in accordance with the terms of the licence No part of this document may be reproduced or transmit...

Page 3: ...HAPTER 3 CONFIGURATION 6 Refresh 6 Wink 6 Edit Change settings 6 Upgrading the software version of the unit 8 APPENDIX 1 LIST OF VARIABLES FOR E BACNET2 V 10 Analog Inputs 10 Analog Values 11 Binary I...

Page 4: ...ace via the PLA ELA address 254 254 To change these settings see chapter 3 The Corrigo E controller is connected to the converter with the supplied cable and communicates with the SCADA system via the...

Page 5: ...LAN1 port of the converter and a network port The converter may also be connected directly to a computer but this requires a crossover RJ45 cable not included Connect the power supply to the converter...

Page 6: ...able converters connected to the network are displayed Refresh Pressing the Refresh button will update the list of converters Wink Wink is a function that can be used to ensure that the correct physic...

Page 7: ...atically added after it UDP Port BACnet IP standard is 47808 The checkbox Foreign device is used when E BACNET2 V is to be connected to another IP network It is then neccessary to state the BBMD addre...

Page 8: ...r is turned on the unit will beep once The upgrade procedure has now started 7 Wait between 30 and 60 seconds and the unit will beep again The procedure is now finished and the E BACNET2 V unit has be...

Page 9: ...Appendix I...

Page 10: ...a No Cor_EAFPressure Analog Input 7 Current pressure extract air Pa No Cor_DeIcingTemp Analog Input 8 De icing temperature C No Cor_FrostprotectionTemp Analog Input 9 Frost protection temperature C No...

Page 11: ...t signal No Cor_HumidityPID_Output Analog Input 39 Humidity controller output signal No Analog Values Object name Object ID Description Unit Adjustable Cor_SupplySetpoint Analog Value 0 Supply air set...

Page 12: ...igh supply air temperature C Yes Cor_EfficiencyLowLimit Analog Value 26 Alarm low efficiency Yes Cor_FrostLimit Analog Value 27 Alarm limit frost protection C Yes Cor_RoomHighLimit Analog Value 28 Ala...

Page 13: ...ormal active No Cor_ExtendedRunActiveHalf Binary Input 16 Extended running reduced active No Cor_DeIcingActive Binary Input 17 De icing function active No Cor_RecycleRunActive Binary Input 18 Recircul...

Page 14: ...in manual mode No Cor_AlaPt_39 Binary Input 57 EAF in manual mode No Cor_AlaPt_40 Binary Input 58 Frequency converter EAF in manual mode No Cor_AlaPt_41 Binary Input 59 Heating battery in manual mode...

Page 15: ...converter SAF No Cor_AlaPt_80 Binary Input 88 Communication error frequency converter EAF No Cor_AlaPt_81 Binary Input 89 Communication error expansion unit 1 No Cor_AlaPt_82 Binary Input 90 Communica...

Page 16: ...ort control cooling 9 CO2 control 10 Free cooling 11 Full speed stop 12 Fan stop No Multistate Values Object name Object ID Description Unit Adjustable Cor_AirUnitAutoMode Multistate Value 0 Manual se...