Object name
Object ID
Description
Unit
Adjustable
Cor_EAF
Analog Input, 23
Current output EAF
V
No
Cor_Humidity
Analog Input, 24
Current output
dehumidification/humidification
V
No
Cor_Split
Analog Input, 25
Current output split
V
No
Cor_ExtraSeqCV1
Analog Input, 26
Current output Y4-extra sequence
V
No
Cor_Efficiency
Analog Input, 27
Heat exchanger efficiency
%
No
Cor_SAFRunTime
Analog Input, 28
Running time SAF
h
No
Cor_EAFRunTime
Analog Input, 29
Running time EAF
h
No
Cor_SupplyPID_SetP
Analog Input, 30
Calculated supply air setpoint at
outdoor compensated setpoint
°C
No
Cor_SupplyPID_Output
Analog Input, 31
Supply air controller output signal
%
No
Cor_ExhaustPID_Output
Analog Input, 32
Extract air controller output signal
%
No
Cor_SAFPID_Output
Analog Input, 33
Output signal SAF
%
No
Cor_EAFPID_Output
Analog Input, 34
Output signal EAF
%
No
Cor_FrostPID_Output
Analog Input, 35
Warming controller output signal
%
No
Cor_CO2PID_Output
Analog Input, 36
CO
2
controller output signal
%
No
Cor_RoomPID_Output
Analog Input, 37
Room controller output signal
%
No
Cor_DeIcePID_Output
Analog Input, 38
De-icing controller output signal
%
No
Cor_HumidityPID_Output
Analog Input, 39
Humidity controller output signal
%
No
Analog Values
Object name
Object ID
Description
Unit
Adjustable
Cor_SupplySetpoint
Analog Value, 0
Supply air setpoint if supply air
control is selected
°C
Yes
Cor_ExtractSetpoint
Analog Value, 1
Extract air setpoint if extract air
control is selected
°C
Yes
Cor_SAFFullspeedPressure
Analog Value, 2
Setpoint normal speed supply air
fan, frequency control pressure
Pa
Yes
Cor_SAFHalfspeedPressure
Analog Value, 3
Setpoint reduced speed supply air
fan, frequency control pressure
Pa
Yes
Cor_EAFFullspeedPressure
Analog Value, 4
Setpoint normal speed extract air
fan, frequency control pressure
Pa
Yes
Cor_EAFHalfspeedPressure
Analog Value, 5
Setpoint reduced speed extract air
fan, frequency control pressure
Pa
Yes
Cor_CO2Setpoint
Analog Value, 6
Setpoint CO
2
ppm
Yes
Cor_SAFFullspeedAirFlow
Analog Value, 7
Setpoint normal speed supply air
fan flow
m
3
/h
Yes
Cor_SAFHalfspeedAirFlow
Analog Value, 8
Setpoint reduced speed supply air
fan flow
m
3
/h
Yes
Cor_EAFFullspeedAirFlow
Analog Value, 9
Setpoint normal speed extract air
fan flow
m
3
/h
Yes
Cor_EAFHalfspeedAirFlow
Analog Value, 10
Setpoint reduced speed extract air
fan flow
m
3
/h
Yes
Cor_NeedHeatStart
Analog Value, 11
Room temperature for start of
support control heating
°C
Yes