Appendix 1  

List of variables for  

E-BACNET2-V 

E-BACNET2-V  contains  a  total  of  184  objects.  These  are  distributed  over  different  categories  in 
accordance with the following list: 

 

Analog Input = 40 

 

Analog Value = 41 

 

Binary Input = 98 

 

Binary Value = 1 

 

Multistate Input = 1 

 

Multistate Value = 2 

 

Device = 1 

Analog Inputs

 

Object name

 

Object ID

 

Description

 

Unit

 

Adjustable

 

Cor_SupplyAirTemp 

Analog Input, 0 

Supply air temperature 

°C 

No 

Cor_ExtractAirTemp 

Analog Input, 1 

Extract air temperature 

°C 

No 

Cor_RoomTemp1 

Analog Input, 2 

Room temperature 1 

°C 

No 

Cor_RoomTemp2 

Analog Input, 3 

Room temperature 2 

°C 

No 

Cor_ExhaustAirTemp 

Analog Input, 4 

Exhaust air temperature 

°C 

No 

Cor_ExtraSensor 

Analog Input, 5 

External sensor/setpoint device, 
depending on the configuration. 

°C 

No 

Cor_SAFPressure 

Analog Input, 6 

Current pressure, supply air 

Pa 

No 

Cor_EAFPressure 

Analog Input, 7 

Current pressure, extract air 

Pa 

No 

Cor_DeIcingTemp 

Analog Input, 8 

De-icing temperature 

°C 

No 

Cor_FrostprotectionTemp 

Analog Input, 9 

Frost protection temperature 

°C 

No 

Cor_CO2Sensor 

Analog Input, 10 

CO

2

 sensor 

ppm 

No 

Cor_HumidityRoom 

Analog Input, 11 

Humidity, room 

RH 

No 

Cor_HumidityDuct 

Analog Input, 12 

Humidity, duct 

RH 

No 

Cor_ExtraUnitTemp 

Analog Input, 13 

Extra controller, temperature 

°C 

No 

Cor_ExtSAFControl 

Analog Input, 14 

Frequency control, manual SAF 

No 

Cor_ExtEAFControl 

Analog Input, 15 

Frequency control, manual EAF 

No 

Cor_HumidityOutDoor 

Analog Input, 16 

Humidity outdoor 

RH 

No 

Cor_SAFAirFlow 

Analog Input, 17 

Frequency control, air flow SAF 

m

3

/h 

No 

Cor_EAFAirFlow 

Analog Input, 18 

Frequency control, air flow EAF 

m

3

/h 

No 

Cor_HeatCV1 

Analog Input, 19 

Current output Y1-heating 

No 

Cor_ExchCV1 

Analog Input, 20 

Current output Y2-exchanger 

No 

Cor_CoolCV1 

Analog Input, 21 

Current output Y3-cooling 

No 

Cor_SAF 

Analog Input, 22 

Current output frequency converter 
SAF 

No 

Summary of Contents for E-BACNET2-V

Page 1: ...E BACNET2 V manual Copyright AB Regin Sweden 2012 Copyright AB Regin Sweden 2012...

Page 2: ...software described in this document is supplied under licence by Regin and may be used or copied only in accordance with the terms of the licence No part of this document may be reproduced or transmit...

Page 3: ...HAPTER 3 CONFIGURATION 6 Refresh 6 Wink 6 Edit Change settings 6 Upgrading the software version of the unit 8 APPENDIX 1 LIST OF VARIABLES FOR E BACNET2 V 10 Analog Inputs 10 Analog Values 11 Binary I...

Page 4: ...ace via the PLA ELA address 254 254 To change these settings see chapter 3 The Corrigo E controller is connected to the converter with the supplied cable and communicates with the SCADA system via the...

Page 5: ...LAN1 port of the converter and a network port The converter may also be connected directly to a computer but this requires a crossover RJ45 cable not included Connect the power supply to the converter...

Page 6: ...able converters connected to the network are displayed Refresh Pressing the Refresh button will update the list of converters Wink Wink is a function that can be used to ensure that the correct physic...

Page 7: ...atically added after it UDP Port BACnet IP standard is 47808 The checkbox Foreign device is used when E BACNET2 V is to be connected to another IP network It is then neccessary to state the BBMD addre...

Page 8: ...r is turned on the unit will beep once The upgrade procedure has now started 7 Wait between 30 and 60 seconds and the unit will beep again The procedure is now finished and the E BACNET2 V unit has be...

Page 9: ...Appendix I...

Page 10: ...a No Cor_EAFPressure Analog Input 7 Current pressure extract air Pa No Cor_DeIcingTemp Analog Input 8 De icing temperature C No Cor_FrostprotectionTemp Analog Input 9 Frost protection temperature C No...

Page 11: ...t signal No Cor_HumidityPID_Output Analog Input 39 Humidity controller output signal No Analog Values Object name Object ID Description Unit Adjustable Cor_SupplySetpoint Analog Value 0 Supply air set...

Page 12: ...igh supply air temperature C Yes Cor_EfficiencyLowLimit Analog Value 26 Alarm low efficiency Yes Cor_FrostLimit Analog Value 27 Alarm limit frost protection C Yes Cor_RoomHighLimit Analog Value 28 Ala...

Page 13: ...ormal active No Cor_ExtendedRunActiveHalf Binary Input 16 Extended running reduced active No Cor_DeIcingActive Binary Input 17 De icing function active No Cor_RecycleRunActive Binary Input 18 Recircul...

Page 14: ...in manual mode No Cor_AlaPt_39 Binary Input 57 EAF in manual mode No Cor_AlaPt_40 Binary Input 58 Frequency converter EAF in manual mode No Cor_AlaPt_41 Binary Input 59 Heating battery in manual mode...

Page 15: ...converter SAF No Cor_AlaPt_80 Binary Input 88 Communication error frequency converter EAF No Cor_AlaPt_81 Binary Input 89 Communication error expansion unit 1 No Cor_AlaPt_82 Binary Input 90 Communica...

Page 16: ...ort control cooling 9 CO2 control 10 Free cooling 11 Full speed stop 12 Fan stop No Multistate Values Object name Object ID Description Unit Adjustable Cor_AirUnitAutoMode Multistate Value 0 Manual se...

Page 17: ...Box 116 S 428 22 K llered Sweden AB Regin Head office Phone 46 31 720 02 00 Fax 46 31 720 02 50 info regin se www regin se R E G I N T H E C H A L L E N G E R I N B U I L D I N G A U T O M A T I O N...

Reviews: