Appendix 1
List of variables for
E-BACNET2-V
E-BACNET2-V contains a total of 184 objects. These are distributed over different categories in
accordance with the following list:
Analog Input = 40
Analog Value = 41
Binary Input = 98
Binary Value = 1
Multistate Input = 1
Multistate Value = 2
Device = 1
Analog Inputs
Object name
Object ID
Description
Unit
Adjustable
Cor_SupplyAirTemp
Analog Input, 0
Supply air temperature
°C
No
Cor_ExtractAirTemp
Analog Input, 1
Extract air temperature
°C
No
Cor_RoomTemp1
Analog Input, 2
Room temperature 1
°C
No
Cor_RoomTemp2
Analog Input, 3
Room temperature 2
°C
No
Cor_ExhaustAirTemp
Analog Input, 4
Exhaust air temperature
°C
No
Cor_ExtraSensor
Analog Input, 5
External sensor/setpoint device,
depending on the configuration.
°C
No
Cor_SAFPressure
Analog Input, 6
Current pressure, supply air
Pa
No
Cor_EAFPressure
Analog Input, 7
Current pressure, extract air
Pa
No
Cor_DeIcingTemp
Analog Input, 8
De-icing temperature
°C
No
Cor_FrostprotectionTemp
Analog Input, 9
Frost protection temperature
°C
No
Cor_CO2Sensor
Analog Input, 10
CO
2
sensor
ppm
No
Cor_HumidityRoom
Analog Input, 11
Humidity, room
RH
No
Cor_HumidityDuct
Analog Input, 12
Humidity, duct
RH
No
Cor_ExtraUnitTemp
Analog Input, 13
Extra controller, temperature
°C
No
Cor_ExtSAFControl
Analog Input, 14
Frequency control, manual SAF
%
No
Cor_ExtEAFControl
Analog Input, 15
Frequency control, manual EAF
%
No
Cor_HumidityOutDoor
Analog Input, 16
Humidity outdoor
RH
No
Cor_SAFAirFlow
Analog Input, 17
Frequency control, air flow SAF
m
3
/h
No
Cor_EAFAirFlow
Analog Input, 18
Frequency control, air flow EAF
m
3
/h
No
Cor_HeatCV1
Analog Input, 19
Current output Y1-heating
V
No
Cor_ExchCV1
Analog Input, 20
Current output Y2-exchanger
V
No
Cor_CoolCV1
Analog Input, 21
Current output Y3-cooling
V
No
Cor_SAF
Analog Input, 22
Current output frequency converter
SAF
V
No