www.
reggiani.net
0
19
SPLYT
|
ENG
|
GENERAL NOTES
Conformity: European standards: EN 60598-1, EN 60598-2-2;
EC Directives: 2006/95/EC (LV), 2004/108/EC (EMC), 2002/96/EC (WEEE), 2011/65/EC (RoHS), 2009/125/CE (Ecodesign)
IP20
Degree of protection
The luminaire must never, under any circumstances, be covered with insulating material or the like.
Class II luminaires.
Class III luminaires. Conformity to requirements is only guaranteed if the protection against electric shock is
based on a Safety Extra Low Voltage (SELV) power supply if no higher voltage is generated. The luminaire must
not be connected to the earth conductor.
Emergency luminaires:
- the preferential line must never be interrupted;
- luminous fl ux in emergency mode: after 60 seconds, about 20% of the luminous fl ux of the lamp in ordinary operation;
- emergency back-up time: 1 hour;
- the green LED indicates correct operation of the inverter-battery circuit;
- the battery is fully recharged in 24 hours;
- the maintenance-free batteries must be replaced every 4 years;
- every six months, check that the system is functioning correctly by fully discharging the battery.
For connection to the mains power supply, use H05V2V2 multi-pole cable with wires of a cross section between 1 mm² and 2.5 mm².
I.M._Splyt_1.95415.indd 19
I.M._Splyt_1.95415.indd 19
01/08/16 08:55
01/08/16 08:55