GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1)
Make sure the valve is in the "OFF"
position.
2)
Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a
1/8"
wide
fl
at screwdriver.
3)
Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4)
Light the pilot and turn the valve to "ON"
position.
5)
The pressure check should be carried out
with the unit burning and the setting should
be within the limits speci
fi
ed on the safety
label.
6)
When
fi
nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8"
fl
at
screwdriver.
Note: Screw should be snug,
but do not over tighten.
BACK-UP BATTERY
INSTALLATION
(within Power Module)
1)
Unplug the power source.
2)
Remove the Power Module by lifting it up
off of the velcro and pull out.
Power Module
3)
Remove the Power Module cover by
removing the 2 screws, one on each side
of the box.
4)
Install the 9V and AA battery.
SIT VALVE DESCRIPTION
1)
Gas on/off knob
2)
Electronically Operated Hi/Lo
3)
Pilot
Adjustment
4)
Thermocouple Connection -
option
5)
Outlet Pressure Tap
6)
Inlet Pressure Tap
7)
Pilot Outlet
8)
Main Gas Outlet
9)
Alternative TC Connection Point
IN
OUT
1
3
5
6
4
2
NOTE: The 9V battery operates the
rear burner under power outage
conditions.
The AA battery operates the DC
Sparker for lighting the pilot.