Framing and Finishing

1)

 

Determine the total thickness of facing material (e.g. drywall plus 
ceramic tiles) to allow the fi nished surface to be fl ush with the front 
of the unit. Total facing thickness can vary from 1/2” (13mm) to 
1-1/4” (32mm) thick. 

 

2)

 

Frame in the enclosure for the unit with framing material. 

 

Note:

 Header for the P36 

must

 be installed vertically to maintain 

clearances to combustible materials.  Non combustible header may 
be installed horizontally.  

3)

 

For exterior walls, insulate the enclosure to the same degree as 
the rest of the house, apply vapor barrier and drywall, as per local 
installation codes. 

(Do not insulate the fi replace itself.)

4)

 

The top of the unit must not be closer than 32” (813mm) to the 
ceiling.

5)

 

Combustible material may be brought up to the top and sides of 
the unit and be covered with ceramic tiles, bricks, rock or other 
suitable combustible fi nishing materials.

 

If using the Barcelona Surround, Kensington, Balmoral, or 
Tripoli Screen Door please note that framing and facing must 
be non combustible (12” on top and 6” on both sides) and  that 
the Barcelona is only approved  for installation with a single 
sidewall.

 

Note: The unit does not have to be completely enclosed in a 
chase. The clearance on top of the unit is 0” to the standoffs 
so combustible building materials can be laid directly on top 
of the standoffs. You must maintain proper clearances from 
the vent to combustible materials (See Below).

6)

 

Use metal studs for framing where the minimum clearance from 
the vent to combustible material cannot be maintained.

Drywall

Mantel Clearances

2

0

12

6

4

8

10

0

Side View

Top of

Unit

12" (305mm)

3-1/2" (89mm)

7-1/2"(191mm)

A

To base

of Unit

Standof

f

B

C

D

6" Side Wall

5"

2"

Mantel

leg

Mantel

leg

P36 - P36D

Allowable mantel leg

projection.

3"

1-1/2"

8" Single Sidewall when using the Barcelona Surrround

Mantel Clearances

A

B

C

D

with Flush Glass or 

Hampton Cast

30-1/2” 

(778mm)

14” (356mm)

10” (254mm)

7” (178mm)

with Bay Option

30-1/2” 

(778mm)

13” (330mm)

10” (254mm)

7” (178mm)

with Flush Glass and 

Barcelona Surround

30-1/2” 

(778mm)

17” (432mm)

12” (305mm)

8” (203mm)

with Tripoli Screen Door, 

Kensington, or Balmoral 

Front

30-1/2” 

(778mm)

20” (508mm)

N/A

12” (305mm)

P36 - P36D Gas Fireplace

Combustible Mantels

Because of the extreme heat this fi replace emits, the mantel 
clearances are critical.

 Combustible mantel clearances from top of 

the louvers are shown in the diagram below. Mantel may be installed 
anywhere in the shaded area or higher.

Note:  If desired a non-combustible mantel may be installed at a 

lower height.

Note:  Ensure the paint that is used on the mantel and the facing 

is “heat resistant” or the paint may discolour.

Mantel Leg Clearances

Combustible mantel leg clearances as per diagram below:
Clearances are from the fi nished edge of the unit or an installed front. 

Maximum 
1-1/2” projection at 2” 
minimum clearance.

WARNING

Failure to maintain required clearances is a major cause of 
chimney related fi res.  Installation of this fi replace must comply 
with these clearances.

Clearance:

Dimension

Measured From:

A: Mantel Height

7” (178mm)

Minimum (Additional on this page)

B: Sidewall

6” (152mm)

Side of installed front

Sidewall: Barcelona Only

8” (203mm)

Approved for single sidewall only

C: Ceiling

32” (813mm)

Top of installed unit

D: Mantel Depth

12” (305mm)

Maximum (Additional on this page)

E: Alcove Width

48” (1219mm)

Sidewall to Sidewall (Minimum)

F: Alcove Depth

36” (914mm)

Front to back wall (Maximum)

Top of Hearth must not be higher than the base of the fi rebox. 

Vent Clearances

Clearance Dimension

Horizontal - Top

2” (51mm)

Horizontal - Side

1-1/2” (38mm)

Horizontal - Bottom

1-1/2” (38mm)

Vertical 

(Flex or Rigid)

1-1/4” (32mm)

E

B

B

A

C

D

F

Clearance Requirements

36

June 2007 Regency Product Specifi cations Book

Gas Fir

eplaces

Gas Fireplaces

Summary of Contents for P36-NG4

Page 1: ... 4 921mm 36 1 4 921mm H Framing Height 36 1 4 921mm 37 1 4 946mm I Framing Depth 12 3 4 324mm 17 1 8 435mm J Corner Wall Length 42 7 16 1078mm 48 1219mm K Corner Facing Wall Width 60 1524mm 68 1727mm L Framed Chase Ceiling 46 1168mm 46 1 2 1181mm M Vent Centerline Height 40 1 2 1029mm 40 1 2 1029mm N Gas Connection Height 2 51mm 2 51mm O Gas Connection Inset 3 1 2 89mm 3 1 2 89mm P Gas Connection ...

Page 2: ...projection 3 1 1 2 8 Single Sidewall when using the Barcelona Surrround Mantel Clearances A B C D with Flush Glass or Hampton Cast 30 1 2 778mm 14 356mm 10 254mm 7 178mm with Bay Option 30 1 2 778mm 13 330mm 10 254mm 7 178mm with Flush Glass and Barcelona Surround 30 1 2 778mm 17 432mm 12 305mm 8 203mm with Tripoli Screen Door Kensington or Balmoral Front 30 1 2 778mm 20 508mm N A 12 305mm P36 P36...

Page 3: ...pe purchased from Regency may be used for Flex installations 3 Horizontal sections must be supported every 3 feet Alternate Horizontal Termination Caps Alternate Horizontal Riser Vent Terminal Part 640 530 P Snorkel Terminations Snorkel Terminations For installations requiring a vertical rise on the exterior of the building 14 inch and 36 inch tall Snorkel Terminations and the Riser Vent are avail...

Page 4: ...ible materials Minimum of 1 pipe section between elbows Note Must use optional flue adapter when using Rigid Pipe Part 510 994 Maximum 40 ft 12 2m Minimum 10 6 3 2m Minimum 8 6 2 6m Max 10 3m centerline to centerline Minimum 12 305mm Maximum 27 ft 8 2m 0 2 4 6 40 8 10 12 14 16 18 20 22 24 26 28 30 Vertical Height Feet 32 34 36 38 6 8 2 0 4 10 12 12 16 18 14 Rigid Pipe Adapter Part 510 994 Pipe Leng...

Page 5: ...x 6 Min F 5 Min 8 Max 7 Min Vertical Venting with Three 3 90 Elbows Two 45 elbows One 90 elbow Option V H H1 V V1 Maximum total pipe length of all sections must not exceed 30 feet Total horizontal sections must not exceed 8 feet Minimum of 1 foot between 90 elbows is required A 0 Min 2 Max 2 Min B 1 Min 2 Max 3 Min C 2 Min 3 Max 4 Min D 3 Min 4 Max 6 Min E 4 Min 5 Max 7 Min F 5 Min 6 Max 8 Min G 6...

Page 6: ... 10 12 14 16 18 20 22 24 26 28 30 in the diagram shows allowable combinations when installing a P36 The darker shaded area in the diagram shows additional allowable combinations when installing a P36D Note Must use optional flue adapter Part 510 994 when using Rigid Pipe Maintain clearances to combustibles Horizontal vent must be supported every 3 feet Firestops are required at each floor level and ...

Page 7: ... Venting with Three 3 90 Elbows Two 45 elbows One 90 elbow Option V H V V1 H H1 Maximum total pipe length of all sections must not exceed 30 feet Total horizontal sections must not exceed 8 feet Minimum of 1 foot between 90 elbows is required A 0 Min 1 Max 1 Min 2 Max B 1 Min 2 Max 3 Min 3 Max C 2 Min 2 Max 5 Min 4 Max D 3 Min 2 Max 7 Min 5 Max E 4 Min 3 Max 9 Min 6 Max F 5 Min 4 Max 10 Min 7 Max ...

Page 8: ...ear Adapter Kit which contains the following Co linear Flex Adapter Outer Pipe Inner Pipe Adapter 510 994 Flue Adapter 945 45º Elbow Alternate Approved Caps 980 Vertical Termination Cap 991 High Wind Cap 923GK 3 Co linear Adapter with flashing The shaded area in the diagrams show the allowable vertical terminations Please refer to Page 11 Exterior Vent Terminations for additional guidelines on vent...

Reviews: