Regency Horizon™ HZ42STE-10 Gas Fireplace
|
37
37
|
installation
HIGH ELEVATION
This unit is approved for altitude 0 to 4500 ft.
(CAN1 2.17-M91).
GAS LINE
INSTALLATION
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the CAN/CGA B149 installation
code.
For USA installations follow local codes and/or the
current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only
approved fittings. Always provide a union so that
gas lines can be easily disconnected for servicing.
Flare nuts for copper lines and flex connectors
are usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be sup-
plied in or near the unit (or as per local codes)
for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with
a soap and water solution or gas leak detector.
Do not use open flame for leak testing.
HZ42STE-NG10 SYSTEM DATA
Min. Supply Pressure 5" WC (1.25 kpa)
Low Setting Man.
Pressure
1.6" WC (0.40kpa)
Max. Manifold
Pressure
3.5" WC (0.87 kpa)
Orifice Size
#40 DMS
Minimum Input
17,500 Btu/h
(5.13 kW)
Maximum Input
26,000 Btu/h
(7.62 kW)
HZ42STE LP10 SYSTEM DATA
Min. Supply Pressure 12" WC (2.98 kpa)
Low Setting Man.
Pressure
6.4" WC (1.59kpa)
Max. Manifold
Pressure
10" WC (2.49 kpa)
Orifice Size
#53 DMS
Minimum Input
19,500 Btu/h
(5.71 kW)
Maximum Input
24,500 Btu/h
(7.18 kW)
AERATION ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude. Open the air shutter for a blue flame or
close for a more yellow flame.
Minimum Air Shutter Opening:
NG Fully Closed
LP 3/16"
With Logs:
NG 1/4"
LP Full open
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1)
Make sure the valve is in the "OFF" position.
2)
Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a
1/8" wide flat screwdriver.
3)
Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" ID hose.
4)
Light the pilot and turn the valve to "ON" position.
5)
The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6)
When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Note: Screw should be snug, but do not over
tighten.
Periodically check the pilot flames. Correct
flame pattern has three strong blue flames: 1
flowing around the thermopile, 1 around the
thermocouple and 1 flowing across the burner.
Note: If you have an incorrect flame pattern,
contact your Regency
®
dealer for further
instructions.
Incorrect flame pattern will have small,
probably yellow flames, not coming into
proper contact with the burner or thermopile
or thermocouple.
PILOT ADJUSTMENT
Burner
Flame Sensor
Pilot
Ignitor
885 S.I.T. VALVE
DESCRIPTION
1)
6 Stage flame adjustment
2)
Pilot adjustment
3)
Outlet Pressure Tap
4)
Inlet Pressure Tap
5)
Pilot Outlet
6)
Main Gas Outlet
7)
Main Gas Inlet
1
2
3
4
6
5
7