Regency 2400 Freestanding Woodstove
|
17
17
|
installation
MOBILE HOME INSTALLATION
Once you have properly marked the position of
your unit and the floor protection as outlined in
the Residential Installation items #1 through #8,
a supply of fresh air has to be supplied to your
unit. Cut a minimum 4" (102mm) diameter hole
through your floor protector and the floor directly
under your pedestal base to the outside. Use 4"
(102mm) duct pipe with a mesh grill to pipe fresh
air into the pedestal area. Block off the hole in
the back of the pedestal with the square plate
and the two 1/2" screws provided.
Place your unit in position and secure it to the
floor using two lag bolts 3/8" (10mm) x 3-1/2"
(89mm) through the two holes inside the pedestal
base. It is important to maintain the structural
integrity of the Mobile Home floor, walls and roof
when installing your unit.
For Mobile Home units installed in the U.S. the
unit must be grounded using a #8 ground wire
with approved termination and star washer.
In addition to standard installation instructions the
following requirements are mandatory for installa-
tion in a mobile home.
1)
The stove must be permanently bolted to
the floor of the Mobile Home using the floor
screws provided.
2)
The stove must have a permanent outside air
source for combustion.
3)
The stove must be electrically grounded to the
steel chassis of the Mobile Home.
4)
A listed double-wall connector chimney system,
roof thimble, spark arrestor and roof flashing kit
suitable for use in Mobile Homes must be used.
5)
If the chimney exits the Mobile Home at a loca-
tion other than through the roof, and exits at a
point 7ft. (2130mm) or less above the ground
level on which the Mobile Home is positioned
a guard or method of enclosing the chimney
shall be fitted at the point of exit for a height up
to 7ft. (2130mm).
6)
The chimney shall be attached directly to the
room heater and shall extend at least 3 ft.
(914mm) above the part of the roof through
which it passes. The top of the chimney should
project at least 2ft. (610mm) above the highest
elevation of any part of the Mobile Home within
10 ft. (3048mm) of the chimney.
7)
The chimney system shall comply with Local
Requirements.
8)
Any openings in a chimney guard where required
must not permit the entrance of 3/4" (19mm)
diameter rod.
9) CAUTION: THE STRUCTURAL INTEGRITY OF
THE MOBILE HOME ROOF, FLOOR, WALLS
AND CEILING MUST BE MAINTAINED.
10)
Check any other local building code as other
local codes may apply.
11)
WARNING: DO NOT INSTALL IN A SLEEPING
ROOM OF A MOBILE HOME.
12)
Use silicone to create an effective vapour
barrier at the location where the chimney or
other component penetrates to the exterior of
the structure.
CAUTION: At no time use unlabelled parts,
or substitute parts made for another chim-
ney system.
Install as per chimney manufacturer's
installation instructions.
WARNING: Operate only with door fully
closed - open feed door to feed fire only.