Regency F2400M Owners & Installation Manual Download Page 15

 

Regency 2400 Freestanding Woodstove

  |     

15

15

installation

Method A

:  12" (304.8 mm) Clearance to Combustible Wall 

Member:
Using a minimum thickness 3.5" (89 mm) brick and a 5/8" (15.9 mm) 

minimum wall thickness clay liner, construct a wall pass-through.  

The clay liner must conform to ASTM C315 (Standard Specification 

for Clay Fire Linings) or its equivalent. Keep a minimum of 12" (304.8 

mm) of brick masonry between the clay liner and wall combustibles.  

The clay liner shall run from the brick masonry outer surface to the 

inner surface of the chimney flue liner but not past the inner surface.  
Firmly grout or cement the clay liner in place to the chimney flue liner.  

 

Method B

: 9" (228.6 mm) Clearance to Combustible Wall Member:

Using a 6" (152.4 mm) inside diameter, listed, factory-built Solid-Pak 

chimney section with insulation of 1" (25.4 mm) or more, build a wall 

pass-through with a minimum 9" (228.6 mm) air space between the 

outer wall of the chimney length and wall combustibles. Use sheet 

metal supports fastened securely to wall surfaces on all sides, to 

maintain the 9" (228.6 mm) air space. When fastening supports to 

chimney length, do not penetrate the chimney liner (the inside wall 

of the Solid-Pak chimney).  The inner end of the Solid-Pak chimney 

section shall be flush with the inside of the masonry chimney flue, and 

sealed with a non-water soluble refractory cement.  Use this cement 

to also seal to the brick masonry penetration.

Minimum

12 in. (304.8mm)

to combustibles

Masonry chimney

Chimney

Flue

Minimum chimney clearance to brick

and combustibles 2 in. (50.8mm)

Minimum clearance

12 in. (304.8mm)

of brick

Chimney

connector

Fire clay

liner

Method C

: 6" (152.4 mm) Clearance to Combustible Wall Member:

Starting with a minimum 24 gage (.024" [.61 mm]) 6" (152.4 mm) metal 

chimney connector, and a minimum 24 gage ventilated wall thimble 

which has two air channels of 1" (25.4 mm) each, construct a wall 

pass-through. There shall be a minimum 6" (152.4) mm separation area 

containing fiberglass insulation, from the outer surface of the wall thimble 

to wall combustibles.  Support the wall thimble, and cover its opening 

with a 24-gage minimum sheet metal support. Maintain the 6" (152.4 

mm) space.  There should also be a support sized to fit and hold the 

metal chimney connector. See that the supports are fastened securely 

to wall surfaces on all sides.  Make sure fasteners used to secure the 

metal chimney connector do not penetrate chimney flue liner.  

Method D

: 2" (50.8 mm) Clearance to Combustible Wall Member:

Start with a solid-pak listed factory built chimney section at least 

12" (304 mm) long, with insulation of 1" (25.4 mm) or more, and an 

inside diameter of 8" (2 inches [51 mm] larger than the 6" [152.4 

mm] chimney connector). Use this as a pass-through for a minimum 

24-gage single wall steel chimney connector. Keep solid-pak section 

concentric with and spaced 1" (25.4 mm) off the chimney connector 

by way of sheet metal support plates at both ends of chimney section.  

Cover opening with and support chimney section on both sides with 

24 gage minimum sheet metal supports. See that the supports are 

fastened securely to wall surfaces on all sides. Make sure fasteners 

used to secure chimney flue liner.

COMBUSTIBLE WALL CHIMNEY 

CONNECTOR PASS-THROUGHS

Summary of Contents for F2400M

Page 1: ...Freestanding Woodstove 02 26 16 Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference Owners Installation Manual Tested by F2400 Video www regency fire com French Manual http bit ly 1myB2FA Manuel en Français http bit ly 1myB2FA ...

Page 2: ...ere the majority of the chimney is within the building envelope and fully lined It is against federal regulation to operate this wood heater in a manner inconsistent with operating instructions in this manual or if any parts are removed It is against federal regulation to operate this wood heater in a manner inconsistent with operating instructions in this manual CAUTION BURN UNTREATED WOOD ONLY O...

Page 3: ...Regency 2400 Freestanding Woodstove 3 3 Modular Parts F2400 Video ...

Page 4: ...ion 18 Flue Baffle Secondary Air Tube Installation 18 Stainless steel smoke deflector adjustment replacement 19 Brick Installation 20 Classic Door Handle 20 Contemporary Door Handle 20 Glass Installation 20 Step by step Optional Accessories Installation 20 Screen Door 21 Seasoned wood 22 Operating Instructions 23 Draft Control 23 First Fire 23 Fan Operation 24 Ash Disposal 24 Safety Guidelines and...

Page 5: ...URS DE CHEMINÉE À DOUBLE PAROI SUIVANTS AU CANADA CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI SECURITYMODÈLE DP OU OLIVER MACLEOD PRO VENT PV AVEC SYSTÈME DE CHEMINÉE HOMOLOGUÉ SECURITY MODÈLE S2100 ICC EXCEL 2100 SUPER VENT 2100 SUPERPRO 2100 CF SENTINAL AUX ÉTATS UNIS CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI SECURITY MODÈLE DP SELKIRK MODEL DS OLIVER MACLEOD PRO VENT PV SIMPSON DU...

Page 6: ...MODÈLE S2100 ICC EXCEL 2100 SUPER VENT 2100 SUPERPRO 2100 CF SENTINAL AUX ÉTATS UNIS CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI SECURITY MODÈLE DP SELKIRK MODEL DS OLIVER MACLEOD PRO VENT PV SIMPSON DURA VENT MODÈLE DVL GSW SUPER PIPE 6 METAL FAB À DOUBLE PAROI CONNECTÉ À L UN DES SYSTÈMES DE CHEMINÉE COMPATIBLES SUIVANTS SECURITY MODÈLE S2100 OU MODÈLE ASHT SELKIRK MODÈLE SSII OLIVER MACLE...

Page 7: ...Regency 2400 Freestanding Woodstove 7 7 dimensions F2400M UNIT DIMENSIONS Classic Door Contemporary Door ...

Page 8: ...8 Regency 2400 Freestanding Woodstove 8 dimensions S2400M UNIT DIMENSIONS Classic Door Contemporary Door ...

Page 9: ...osi tion the stove with the flue collar centered under the installed chimney 10 In areas of seismic activity Regency rec ommends that your unit is secured to the floor by using the bolt down holes inside the pedestal the same ones used in Mobile Home installations 11 For residential installations using 6 C Vent single wall the chimney connector must be at least 24 gauge steel Do not use galvanized...

Page 10: ... also required for air space between the apliance and wall ceiling Residential Installation C Vent Single Wall Unit From Unit From Corner From Flue Center Line A B C D E F Medium F2400M with Airmate 15 381 mm 5 5 139 mm 4 101 mm 27 685 mm 12 304 mm 15 5 393 mm with Rear Deflector 15 381 mm 6 5 165 mm 6 152 mm 27 685 mm 13 330 mm 17 5 444 mm Medium S2400M Step Stove 16 406 mm 11 279 mm 6 152 mm 28 ...

Page 11: ...t be installed with a listed double wall connector to the ceiling level Note Minimum alcove ceiling height 84 Maximum depth of alcove 36 NOTE This clearance is also required for air space between the appliance and wall ceiling Unit From Unit From Corner From Flue Center Line G H I J K L Medium F2400M with Airmate 15 381 mm 5 5 139 mm 27 685 mm 12 304 mm 54 1371 mm 48 1219 mm with Rear Deflector 15...

Page 12: ... shown in Diagram 4 Side Shield Adjustment The left and right side shields are lowered for shipping and handling It allows for a handhold on the top of the stove Before placing in the Step Stove in its final position the side shields must be raised Loosen the screws on the rear on the stove 3 per side slide the side panel up as far as pos sible and then secure by tightening the screws Pedestal Ass...

Page 13: ... to initiallytrywiththeminimumrequired height and then if problems do arise add additional height at a later date 4 Slide the roof flashing over your chimney and seal the flashing to the roof with roofing compound Secure the flashing to your roof with nails or screws 5 Place the storm collar over the flashing sealing the joints with a silicone caulking 6 Fasten the raincap with spark screens if re...

Page 14: ...inspected by a professional Make sure there are no cracks loose mortar or other signs of deterioration and blockage Have the chimney cleaned before the stove is installed and operated When connect ing the stove through a combustible wall to a masonrychimney specialmethodsareneeded MASONRY FIREPLACE There are listed kits available to connect a stove to a masonry fireplace The kit is an adapter that...

Page 15: ...chimney clearance to brick and combustibles 2 in 50 8mm Minimum clearance 12 in 304 8mm of brick Chimney connector Fire clay liner Method C 6 152 4 mm Clearance to Combustible Wall Member Starting with a minimum 24 gage 024 61 mm 6 152 4 mm metal chimney connector and a minimum 24 gage ventilated wall thimble which has two air channels of 1 25 4 mm each construct a wall pass through Thereshallbeam...

Page 16: ... and may cause damage An uncontrol lable burn or excessive temperature indicates excessive draft Inadequate draft may cause back puffing into the room and plugging of the chimney Inadequate draft will cause the appliance to leak smoke into the room through appliance and chimney connector joints Ensure the heater is installed in areas that are not too close to neighbors or in valleys that would cau...

Page 17: ... chassis of the Mobile Home 4 A listed double wall connector chimney system roof thimble spark arrestor and roof flashing kit suitable for use in Mobile Homes must be used 5 If the chimney exits the Mobile Home at a loca tion other than through the roof and exits at a point 7ft 2130mm or less above the ground level on which the Mobile Home is positioned a guard or method of enclosing the chimney s...

Page 18: ...the firebox 1 If all 4 air tubes are installed continue on to Step 2 if not follow the instructions below Install the air tube into the holes in the side channels The notch goes on the right hand sidewiththeairholesfacingtowardthedoor LISTED COMPONENTS FOR MOBILE HOME INSTALLATION TheRegencyF2400MandS2400M Freestand ing pedestal units are approved for installation in a Mobile Home if one of the fo...

Page 19: ... bolts To replace the deflector loosen off both bolts and slide defector upward and out Install new defector and hand tighten bolts Ensure positive location of the deflector prior to hand tightening WARNING Operation of the unit with out proper installation of smoke deflector will void warranty Smoke deflector installed with 2 bolts Note This is a view from the back of the unit through the top Ens...

Page 20: ... bricks from the floor of the firebox 2 If using ashdrawer discard cover plate 3 Remove the ash dump cover plates one inside the firebox and one on the underside of the firebox by removing the two nuts and bolts holding the 2 plates together from inside the firebox 4 Pushtheashplugintotheholeinsidethefirebox and replace all the bricks except for the brick over the ash plug refer to the brick diagr...

Page 21: ...ngerous operation WARNING Electrical Grounding Instructions This appliance is equipped with a three pronged grounding plug for your protection against shock hazard and should be plugged directly into a prop erly grounded three prong receptacle Do not cut or remove the grounding prong from this plug SCREEN DOOR Hook screen to the inside on the right side of the firebox door opening Lock in place by...

Page 22: ...sides Softer woods like pine spruce and poplar aspen that is cut split and stacked properly in the early spring maybe be ready for burning in the fall Extremely hard woods like oak and maple and large pieces of firewood may take a minimum of a full year to dry enough Drying may also take longer in damp climates There are a few ways to tell if wood is dry enough to burn efficiently Use as many indi...

Page 23: ...to be expected as the high temperature paint becomes sea soned Windows and or doors should be left open to provide adequate ventilation while this temporary condition exists Burning the stove at a very high temperature the first few times may damage the paint Burn fires at a moderate level the first few days 8 Do not place anything on the stove top during the curing process This may result in dama...

Page 24: ... exhaust fans Ensure adequate ventilation and correct chimney location CAUTION Certain fuels such as charcoal and wet wood can crate the possibility of generating carbon monoxide CO CO is a dangerous by product hat is odourless and can cause seri ous injury ASH DISPOSAL During constant use ashes should be removed every few days The Ash Drawer option features a convenient ash dump for easy removal ...

Page 25: ...orrect operation and longevity of your RegencyWoodheater Theyshouldbeinspected on a regular basis and replaced if they show any signs of undue wear or damage Failure of any of these components can damage the heater and void warranty 5 Thechimneyandchimneyconnectorshould beinspectedatleastonceeverytwomonths during the heating season to determine is a creosote buildup has occurred 6 Have chimney sys...

Page 26: ...75 Ash Hole Cover Plate 13 Bolt 1 4 20 x 1 2 Hex Head 14 820 376 Retainer Plate Ash Dump Top 15 Nut 1 4 20 Hex 16 846 570 7 8 Door Gasket Repair Kit 17 948 079 bn Spring Hinge Cap Nickel each 19 948 135 Spring Handle Large Nickel 20 948 136 Spring Handle Small Nickel F2400M STOVE MAIN ASSEMBLY W CLASSIC DOOR Part Description 846 515 Complete Fan Blower Assy 120 V 25 910 684 Power Cord 120 V 27 910...

Page 27: ... Top 15 Nut 1 4 20 Hex 16 846 570 7 8 Door Gasket Repair Kit 17 948 082 Hinge Cap Black each 19 156 241 Cast Handle 20 948 144 Small Spring Handle Black F2400M STOVE MAIN ASSEMBLY W CONTEMPORARY DOOR Part Description 846 515 Complete Fan Blower Assy 120 V 25 910 684 Power Cord 120 V 27 910 142 Thermodisc Fan Auto ON OFF 28 910 138 Manual Auto Switch 2 way 29 910 140 Fan Speed Switch HI OFF LOW 3 w...

Page 28: ...Assembly 16 846 570 7 8 Door Gasket Repair Kit 17 948 079 BN Hinge Cap Nickel each 19 948 135 Spring Handle Large Nickel 20 948 136 Spring Handle Small Nickel Part Description 846 515 Complete Fan Blower Assy 120 V 25 910 684 Power Cord 120 V 27 910 142 Thermodisc Fan Auto ON OFF 28 910 138 Manual Auto Switch 2 way 29 910 140 Fan Speed Switch HI OFF LOW 3 way 30 910 157 P Fan Blower Motor 120 V 36...

Page 29: ... 570 7 8 Door Gasket Repair Kit 17 846 918 Hinge Caps Gold 2 set 948 082 Hinge Cap Black each 19 156 241 Cast Handle 20 948 144 Small Spring Handle Black Part Description 846 515 Complete Fan Blower Assy 120 V 25 910 684 Power Cord 120 V 27 910 142 Thermodisc Fan Auto ON OFF 28 910 138 Manual Auto Switch 2 way 29 910 140 Fan Speed Switch HI OFF LOW 3 way 30 910 157 P Fan Blower Motor 120 V 36 033 ...

Page 30: ...awer Lid Assy 58 942 110 Ash Plug 59 820 249 Ash Plug Tool Handle 56 020 911 Bottom Shield Medium 57 Blanking Plate Btm Shield 850 101 Ashdrawer Kit Btm Shield 55 Ashdrawer Bottom Shield 58 942 110 Ash Plug 59 820 249 Ash Plug Tool Handle 140 850 126 Legs Cast Black 850 128 Legs Cast Brush Nickel 948 223 Regency Logo Nickel 919 542 Manual Not available as a replacement part PEDESTAL BOTTOM SHIELD ...

Page 31: ...FREESTANDING WOOD STOVES F2400 S2400 Firebrick Replacement NOTE This kit contains one spare brick in case of breakage Description 70 Brick Regular Full Size 1 1 4 x 4 1 2 x 9 72 Brick Partial 1 1 4 x 2 x 4 1 2 74 Brick Partial 1 1 4 x 4 1 2 x 3 1 2 76 Brick Partial 1 1 4 x 2 x 9 2 ...

Page 32: ...32 Regency 2400 Freestanding Woodstove 32 notes ...

Page 33: ...Regency 2400 Freestanding Woodstove 33 33 notes ...

Page 34: ...34 Regency 2400 Freestanding Woodstove 34 notes ...

Page 35: ... the warranty will be invalid Exclusions This limited Lifetime Warranty does not extend to or include paint door or glass gasketing firebrick back sides bottom or trim It does not cover installation and operational related problems such as over firing use of corrosive driftwood wood preservatives metal foils coal plastic garbage sulphur mill ends oils solvents petroleum products railroad ties paper ...

Page 36: ...____________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No ___________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of all your...

Reviews: