background image

 

F1103S  / F3103L 

  |    

19

installation

Side View

Front View

Front View

4) 

Install the third air tube into the holes on the 

side channels. The notch goes on the right 

hand side with the air holes facing forward 

toward the door opening.  If the tube will 

not slide in easily, simply use a pair of vise 

grips or pliers and tap it into place with a 

hammer.  A tighter fit will ensure the tube 

will not move when the unit is burning. 

Note:  When cleaning the chimney reverse 

the above procedures, removing 

the  air  tube  and  baffle  bricks  and 

then replace them when cleaning is 

completed. 

Large Stove F3103L

 

The unit arrives with the third air tube (from the 

front) and the 2 baffle bricks on the floor of the 

firebox. The baffle bricks are positioned first and 

then the air tubes are installed. 

1)

  Slide the left baffle brick over the  two rear 

air tubes and then push it all the way to the 

left side of the firebox. 

Front View

2) 

Tilt the first Baffle Brick down and then slide 

the 2nd Baffle Brick up and back.  Reposition 

both baffle bricks flat on the air tubes. 

3)  Important:  push  both  baffle  bricks  so 

they are tight against the side walls. 

Side View

BRICK FLUE BAFFLE & 

SECONDARY AIR TUBE 

INSTALLATION

The flue baffle system located in the upper area 

of the firebox is removable to make cleaning 

your chimney system easier.  The brick baffles 

must be installed prior to your first  fire. 

 Smoke 

spillage and draft problems may occur if  the 

baffles are improperly positioned. 

 Check the 

position of the brick baffles on a regular basis as 

they can be dislodged if too much fuel is forced 

into the firebox. 

The Large Stoves F3103L  and S3100L are 

shipped with one of the secondary air tubes 

loose inside the firebox. It needs to be installed 

after the brick baffle are installed. Follow the 

directions below.

Small Stove F1103S

1)

  If the two air tubes are installed continue on 

to Step 2), if not, follow the instructions below. 

Install the air tube into the holes in the side 

channels. The notch goes on the right hand 

side with the air holes facing toward the door. 

Slide the tube into the left hand side, as far 

as possible and then bring it back into the 

hole on the right hand side until it locks into 

position. If the tube will not slide in easily 

simply use a pair of vise grips or pliers and 

tap it into place with a hammer. A tighter fit 

will ensure the tube will not move when the 

unit is burning. Refer to the Mobile Home 

Installation section, though there are only 

two air tubes in the small units.

2)

  Slide the left baffle brick over the front air 

tube and then slide it back over the rear air 

tube.

3) 

Tilt the left baffle brick up on top of the side 

channel and it will leave enough room to 

position the right baffle brick in the same 

manner as Step 1 above. Then reposition 

the left baffle brick flat on the air tube. 

4)  Important:  push  both  baffle  bricks  so 

they are tight against the side walls.

Note:  When getting the chimney cleaned, 

remove the baffle bricks for access 

to the flue, then replace them when 

cleaning is completed.

Summary of Contents for F1103S

Page 1: ...4 919 045d MODELS F1103S F3103L Freestanding Woodstoves 11 08 18 Owners Installation Manual Tested by Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference www regency fire com ...

Page 2: ... this heater has been shown to deliver heat at rates ranging from 11 900 BTU hr to 42 900 BTU hr This unit has been tested using 5G series and generates the best efficiency when operated using well seasoned wood and installed in the main living areas where the majority of the chimney is within the building envelope and fully lined It is against federal regulation to operate this wood heater in a m...

Page 3: ...F1103S F3103L 3 ...

Page 4: ...6 Mobile Home Installation 16 Listed Components For Mobile Home Installation 17 Stainless steel smoke deflector adjustment replacement 18 Brick Flue Baffle Secondary Air Tube Installation 19 Brick Installation 20 Door Handle 20 Glass Installation 20 Optional Accessories 20 Screen Door 20 Operating Instructions 22 First Fire 22 Draft Control 22 Ash Disposal 23 Safety Guidelines And Warnings 23 Fan ...

Page 5: ...ENT 2100 AUX ÉTATS UNIS CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI SECURITY MODÈLE DP SELKIRK MODEL DS OLIVER MACLEOD PRO VENT PV SIMPSON DURA VENT MODÈLE DVL GSW SUPER PIPE 6 METAL FAB À DOUBLE PAROI CONNECTÉ À L UN DES SYSTÈMES DE CHEMINÉE COMPATIBLES SUIVANTS SECURITY MODÈLE S2100 OU MODÈLE ASHT SELKIRK MODÈLE SSII OLIVER MACLEOD PRO JET 3103 SIMPSON DURA PLUS GSW MODÈLE SC OU METAL FAB ...

Page 6: ...PAROI SECURITYMODÈLEDP OUOLIVERMACLEODPRO VENTPV AVECSYSTÈMEDECHEMINÉE HOMOLOGUÉ SECURITY MODÈLE S2100 ICC EXCEL 2100 SUPER VENT 2100 AUX ÉTATS UNIS CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI SECURITY MODÈLE DP SELKIRK MODEL DS OLIVER MACLEOD PRO VENT PV SIMPSON DURA VENT MODÈLE DVL GSW SUPER PIPE 6 METAL FAB À DOUBLE PAROI CONNECTÉ À L UN DES SYSTÈMES DE CHEMINÉE COMPATIBLES SUIVANTS SECUR...

Page 7: ...F1103S F3103L 7 dimensions UNIT DIMENSIONS F1103S Dimensions F3103L Dimensions 20 508mm 20 508mm 25 1 4 641mm 25 1 4 641mm 25 1 4 641mm ...

Page 8: ...3L dimensions WOOD STOVE OUTSIDE AIR DIMENSIONS With pedestal from base of unit to centerline 4 1 2 114mm With bottom heat shield from rear heat shield to centerline F1103S 5 127mm F3103L 7 7 8 198mm Rear Front Rear ...

Page 9: ...ct this unit to a chimney serving another appliance unless approved by your local building authority 12 A chimney connector cannot pass through an attic or roof space closet or similar concealed space or a floor ceiling wall or partition of combustible construction In Canada if pas sage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B36...

Page 10: ...5 with Rear Deflector 20 12 10 34 18 5 23 5 NOTE Be aware that local Codes and Regulations may override some clearances listed in this manual Check with your local inspector Residential Installation C Vent Single Wall Unit From Unit From Corner From Flue Center line A B C D E F Small F1103S with Airmate 13 11 8 25 17 5 20 with Rear Deflector 15 10 5 11 27 17 23 Large F3103L with Airmate 18 12 8 5 ...

Page 11: ...y local codes extend ing beneath the heater and a minimum of 6 from each side and minimum 16 from the front face of the stove and minimum 6 or the rear clearance to combustibles whichever is smaller from the rear of the stove NOTE In Canada floor protection must extend 18 to the front and 8 to each side of the stove From From Flue Min Min Hearth Unit Unit Center line Width to Rear Wall G H I J K L...

Page 12: ...15 556 Therearheatdeflectorissuppliedwiththestove andmustbeinstalledunlesstheoptionalairmate hasbeenselected Itstopstheheatradiatedfrom thefluecollarfromoverheatingtherearwall The rear heat deflector is installed on top of the rear heat shield as shown in Diagram 4 Pedestal Assembly Small 850 115 Large 850 315 1 For easier assembly tip the stove on its back onto a soft surface to prevent scratch i...

Page 13: ...can decrease problems such as difficult start ups back smokingwhendoorisopen and dirty glass It might be sufficient to initiallytrywiththeminimumrequired height and then if problems do arise add additional height at a later date 4 Slide the roof flashing over your chimney and seal the flashing to the roof with roofing compound Secure the flashing to your roof with nails or screws 5 Place the storm...

Page 14: ...re are no cracks loose mortar or other signs of deterioration and blockage Have the chimney cleaned before the stove is installed and operated When connecting the stove through a combustible wall to a masonry chimney special methods are needed Ensure that an effective vapour barrier at the location where the chimney or other component penetrates to the exterior of the structure MASONRY FIREPLACE T...

Page 15: ... to brick and combustibles 2 in 50 8mm Minimum clearance 12 in 304 8mm of brick Chimney connector Fire clay liner Method C 6 152 4 mm Clearance to Combustible Wall Member Starting with a minimum 24 gage 024 61 mm 6 152 4 mm metal chimney connector and a minimum 24 gage ventilated wall thimble which has two air channels of 1 25 4 mm each construct a wall pass through Thereshallbeaminimum6 152 4 mms...

Page 16: ...6 ft Example b One 90 deg elbow 2 ft 2 ft of horizontal run 4 ft one T 3 ft Total Addition at sea level 9 ft Recommended Flue Height Elevation Example a Example b 0 18 21 1000 18 72 21 84 2000 19 44 22 68 5000 21 60 25 20 8000 23 76 27 72 Once you have properly marked the position of your unit and the floor protection as outlined in the Residential Installation items 1 through 8 a supply of fresh ...

Page 17: ...y Small and Large Freestanding pedestal units are approved for installation in a Mobile Home if one of the following pipe systems is used U S Installation METALBESTOS SSII Qty Part Description 1 6DS VK Connector Kit 1 6TMH Shield Support 1 6TAF 6 Flashing 1 6T 36 Chimney Length 1 6T 18 Chimney Length 1 6T CT Rain Cap PRO JET 3103 Qty Part Description 1 PV06 TK Connector 1 CSB Shield Support 1 RRS ...

Page 18: ...tightened bolts To replace the deflector loosen off both bolts and slide defector upward and out Install new defector and hand tighten bolts Ensure positive location of the defector prior to hand tightening WARNING Operation of the unit with out proper installation of smoke deflector will void warranty Smoke deflector is installed through the door opening in location shown in diagram Smoke deflect...

Page 19: ... may occur if the bafflesare improperly positioned Checkthe position of the brick baffles on a regular basis as they can be dislodged if too much fuel is forced into the firebox The Large Stoves F3103L and S3100L are shipped with one of the secondary air tubes loose inside the firebox It needs to be installed after the brick baffle are installed Follow the directions below Small Stove F1103S 1 If ...

Page 20: ...he firebox and replace all the bricks except for the brick over the ash plug See brick diagrams 5 Place the ash plug tool beside the lid then slide the ash drawer inside Refer to the Ash Drawer Operating section Freestanding Small F1103 Pedestal Ash Drawer Kit 850 100 1 Remove the bricks from the floor of the firebox 2 If using ashdrawer discard cover plate 3 Remove the ash dump cover plates one i...

Page 21: ... 00 updated Aug 09 05 capitalized the word Nut Lockwasher Ground wire from power cord Ground wire from fan 8 Groun Lug d Star washer Nut Nut Star washer Grounding Lug Detail CAUTION Labelallwirespriortodisconnection whenservicingcontrols Wiringerrorscancause improper and dangerous operation WARNING Electrical Grounding Instructions This appliance is equipped with a three pronged grounding plug for...

Page 22: ...age to the unit and void your warranty FIRST FIRE When your installation is completed and in spected you are ready for your first fire 1 Open control fully 2 Open firebox door and build a small fire using paper and dry kindling Secure door on the firebox and wait a few minutes for a 13 Allfuelburningappliancesconsumeoxygen during operation It is important that you supply a source of fresh air to y...

Page 23: ...door closed during operation and maintain all seals in good condition 3 Do not burn any quantities of paper gar bage and never burn flammable fluids such as gasoline naptha or engine oil in your stove 4 Ifyouhavesmokedetectors preventsmoke spillage as this may set off a false alarm 5 Do not overfire heater If the chimney con nector flue baffle or the stove top begin to glow youareoverfiring Stopad...

Page 24: ...edoorframe causingatighter seal Removeandreplacethenuts washerand spacer as shown GLASS MAINTENANCE Your Regency stove is supplied with 5 mm Neoceram ceramic glass that will withstand the highest heat that your unit will produce In the event that you break your glass by impact purchase your replacement from an authorized Regencydealeronly andfollowourstep by step instructions for replacement Allow...

Page 25: ... Test the seal on the loading door with a paper bill Place a paper bill in the gasketed area of the door of a cold stove Close the door Try to remove the paper by pulling The paper should not pull out easily if it does try adjusting the door latch if that doesn t solve the problem replace the door gasket Check and lubricate door hinge latch Use only high temperature anti seize lube ie never seize ...

Page 26: ...ate 13 Bolt 1 4 20 x 1 2 Hex Head 14 820 376 Retainer Plate Ash Dump Top 15 Nut 1 4 20 Hex 16 846 570 7 8 Door Gasket Repair Kit 17 846 918 Hinge Cap Gold 2 set 948 079 Hinge Cap Nickel each 19 948 101 Spring Handle Large Gold 948 135 Spring Handle Large Nickel F1103 F3103 STOVE MAIN ASSEMBLY Part Description Part Description 20 948 102 Spring Handle Small Gold 948 136 Spring Handle Small Nickel 8...

Page 27: ...sh Plug Tool Handle 56 850 121 Bottom Shield Small 850 321 Bottom Shield Large 57 Blanking Plate Btm Shield 850 101 Ashdrawer Kit Btm Shield 55 Ashdrawer Bottom Shield 58 942 110 Ash Plug 59 820 249 Ash Plug Tool Handle 140 850 126 Legs Cast Black 850 127 Legs Cast Gold 850 128 Legs Cast Brush Nickel 948 216 Regency Logo Gold 948 223 Regency Logo Nickel Not available as a replacement part PEDESTAL...

Page 28: ...k Partial 1 1 4 x 4 1 2 x 3 1 2 76 Brick Partial 1 1 4 x 2 x 9 77 Brick Partial 1 1 4 x 3 1 4 x 9 78 Brick Partial 1 1 4 x 4 1 2 x 3 1 4 79 Brick Partial 1 1 4 x 4 1 2 x 2 1 4 80 Brick Partial 1 1 4 x 6 1 2 x 2 1 4 81 Brick Partial 1 1 4 x 1 1 4 x 9 82 Brick Partial 1 1 4 x 3 1 8 x 4 1 2 83 Brick Partial 1 1 4 x 3 3 8 x 9 84 Brick Partial 1 1 4 x 4 1 2 x 8 85 Brick Partial 1 1 4 x 4 1 4 x 8 Not av...

Page 29: ...F1103S F3103L 29 notes ...

Page 30: ...g switches etc 2 Glass Crazing 1 Catalyst Assembly 6 Years Prorated Venting Chimney 1 Screens 1 Conditions Warranty protects against defect in manufacture or FPI factory assembled components only unless herein specified otherwise Any part s found to be defective during the warranty period as outlined above will be repaired or replaced at FPI s option through an accredited distributor dealer or pre...

Page 31: ...ype operator error abuse misuse use of improper fuels such as unseasoned cordwood mill ends construction lumber or debris off cuts treated or painted lumber metal or foil plastics garbage solvents cardboard coal or coal products oil based products waxed cartons compressed pre manufactured logs lack of regular maintenance and upkeep acts of God weather related problems from hurricanes tornados eart...

Page 32: ... additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the authorized selling dealer to obtain warranty service In the event the authorized selling dealer is unable to provide warranty service please contact FPI by mail at the address listed below Please include a brief description of the problem and your address email and telephone conta...

Page 33: ... us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Product Model required Dealer Details Dealer Name required Dealer Address Dealer Phone Installer Date Installed mm dd yyyy Your Contact Details required Name Address Phone Email For purchases made in CANADA...

Page 34: ......

Page 35: ......

Page 36: ..._______________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial No ___________________________________________________________ Printed in Canada Regency and Classic are trademarks of FPI Fireplace Products International Ltd Copyright 2018 FPI Fireplace Products International Ltd...

Reviews: