Regency Hume Freestanding Wood Fire

7

MINIMUM CLEARANCE TO 

COMBUSTIBLE MATERIALS

INSTALLATION

 

A

400mm

400mm

450mm

B

210mm

180mm

300mm

C

200mm

200mm

200mm

D

181mm

181mm

181mm

E

123mm

123mm

123mm

F

400mm

400mm

400mm

G

1015mm

1015mm

1015mm

H

1120mm

1120mm

1120mm

Floor Protection

A combustible fl oor must be protected by non-combustible material (like 
tile, concrete board, or as defi ned by local codes) extending beneath 
the heater as follows;

From Sides: 

123mm

From Front:  

400mm

From Back:  

181mm

The  fl oor protector should consist of 6mm thick cement fi bre  sheet 
which has a thermal resistance of 0.8m

2

 k/w for 4mm sheets of cement 

fi bre sheet.

The fl ue pipe shall extend not less than 4.6m above the top of the fl oor protector.

NOTE:  Installation must be carried out by a licensed installer in accordance
 

  with 

AS/NZS 

2918:2001.

Flo-Met

Super Single 

*(1)

Hawkwind

Standard

AHD Special

Insulated 

*(2)

IMPORTANT

* (1) The 

Flomet Super Single fl ue kit

 must be installed with a 130

o

 x 

900mm stainless refl ective shield between decromesh.

* (2) The 

AHD Special Insulated fl ue kit

 must be installed with a 

40mm air gap around the fl ue to any combustible surfaces and the 
ceiling ring must be spaced as such to provide an air gap of 20mm to 
the ceiling. The AHD Special Insulated fl ue kit must be installed with 
a perforated ceiling plate and 250mm dia. x 195mm high heatshield 
positioned directly above the ceiling plate.

NOTE:

 A minimum clearance of 180mm (fl at wall) or 200mm (corner wall) must be retained for all wall surfaces to allow for fan access and maintenance.

Summary of Contents for Albany F200B-1

Page 1: ...or property damage Refer to this manual For assistance or additional information consult an authorised installer service agency or the distributor FOR YOUR SAFETY Do not store or use petrol or other flammable vapours and liquids in the vicinity of this or any other appliance Installation and service must be performed by an authorised installer service agency or the gas supplier HUME FREESTANDING W...

Page 2: ...manual please contact the REGENCY DEALER in your area Keep those REGENCY FIRES burning SAFETY NOTE If this wood fire is not properly installed a house fire may result For your safety follow the installation instructions contact local building fire officials or authority having jurisdiction about restrictions and installation inspection requirements in your area The authority having jurisdiction sh...

Page 3: ...ance 9 Door Latch Adjustment 9 Wood Storage 9 PARTS LIST Stove Assembly 10 WARRANTY Warranty 11 Data Badge 4 Unit Dimensions 5 INSTALLATION Residential Installation 6 Safety Guidelines and Warnings 6 Brick Cast Installation 6 Clearance to Combustibles 7 Floor Protection 7 OPERATING INSTRUCTIONS Operating Instructions 8 Air Slide Control 8 First Fire 8 ...

Page 4: ...is the correct one Regency Freestanding Wood Fire Model Hume F250B TESTED TO AS NZS 4013 1999 TEST REPORT NUMBER HCMG 07 003 13kW 57 WHEN TESTED IN ACCORDANCE WITH AS NZS 4012 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 2012 2013 2014 Fireplace Products Australia Pty Ltd 21 23 South Link Dandenong VIC 3175 TESTED BY HRL TECHNOLOGY PTY LTD TRAMWAY ROAD MORWELL VICTORIA 3840 2007 MAXIMUM AVERAGE...

Page 5: ...Regency Hume Freestanding Wood Fire 5 UNIT DIMENSIONS ...

Page 6: ...s preventsmoke spillage as this may set off a false alarm 5 Do not overfire heater If the chimney con nector flue baffle or the stove top begin to glow youareoverfiring Stopaddingfueland close the draft control Overfiring can cause extensive damage to your stove including warpage and premature steel corrosion Overfiring will void your warranty 6 Do not permit creosote or soot build up in the chimn...

Page 7: ...ot less than 4 6m above the top of the floor protector NOTE Installation must be carried out by a licensed installer in accordance with AS NZS 2918 2001 Flo Met Super Single 1 Hawkwind Standard AHD Special Insulated 2 IMPORTANT 1 The Flomet Super Single flue kit must be installed with a 130o x 900mm stainless reflective shield between decromesh 2 The AHD Special Insulated flue kit must be installe...

Page 8: ... ports at the top of the firebox just below the flue baffle OPERATING INSTRUCTIONS With your unit now correctly installed and safety inspected by your local authority you are now ready to start a fire Before establishing your first fire it is important that you fully understand the operation of your draft control CAUTION THIS APPLIANCE MUST BE MAINTAINEDANDOPERATEDATALLTIMES IN ACCORDANCE WITH THE...

Page 9: ... an extremely hot fire WARNING Thingstorememberincase of a chimney fire 1 Close all draft and damper controls 2 CALL THE FIRE DEPARTMENT Ways to Prevent and Keep Unit Free of Creosote 1 Burn stove with the draft control wide open for about 10 15 minutes every morning during burning season 2 Burn stove with draft control wide open for about 10 15 minutes every time you apply freshwood Thisallowsthe...

Page 10: ...1 Top Plate Panel 6 1172004 Rear Panel 7 8010301 Bricks Set Set 9 8 8010302 Liner Cast Iron Set 9 8010303 Liner Cast Iron Sides L R 10 8010305 Liner Cast Iron Back 11 8010306 Air Bar Stainless Steel 12 8010307 Glass Neoceram With Gasket 13 8010313 Door Assembly without handle 14 8010309 Air Slide 15 8010310 Ash Lip Panel 16 8010114 Door Handle Set 17 F250 917 Fan Assembly 18 1172003 Pedestal Assem...

Page 11: ...cy Fireplace Products will not be liable for results or costs of workmanship from unauthorised service persons or dealers At all times Regency Fireplace Products reserves the right to inspect product in the field which is claimed to be defective All claims must be submitted to Regency Fireplace Products by authorized selling dealers It is essential that all submitted claims provide all of the nece...

Page 12: ...PLACE PRODUCTS AUSTRALIA PTY LTD 21 23 SOUTH LINK DANDENONG SOUTH VICTORIA 3175 AUSTRALIA NOTE PLEASE RETAIN YOUR INVOICE AS PROOF OF PURCHASE FOR WARRANTY VERIFICATION INCORRECT INSTALLATION IS NOT COVERED BY WARRANTY A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES ...

Reviews: