10
|
Regency Excalibur
®
P90-10 Zero Clearance Direct Vent Gas Fireplace
|
10
installation
Side Wall Clearance
6-1/2" (165mm)
Horizontal Vent Clearances
Top
2-1/2" (64mm)
Side
1-1/2" (38mm)
Bottom
1-1/2" (38mm)
Vertical Vent Clearances
1-1/4" (32mm)
Alcove Clearances**:
Max. Depth
36" (914mm)
Min. Width
72" (1829mm)
Min. Height
72" (1829mm)
* see mantle clearance instructions
(Refer to the "Combustible Mantels" section).
CLEARANCES
The clearances listed below are Minimum
distances unless otherwise stated:
A major cause of chimney related fires is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fireplace and
vent system be installed only in accordance
with these instructions.
LOCATING YOUR
GAS FIREPLACE
1.
When selecting a location for your fireplace,
ensure that the clearances outlined on this
page are met.
2.
Provide adequate clearances for servicing.
3.
The appliance must be installed on a flat,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the floor, or raised up
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
flooring, the appliance must be installed on
a metal or wood panel extending the full
width and depth of the appliance.
4.
The P90 Direct Vent Gas Fireplace can
be installed in a recessed position or
framed out into the room as in A, B, C, D.
See Diagram 1.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1.
Ensure that structural members are not cut
or weakened during installation.
2.
Ensure proper grounding using the #8 ground
lug provided. See the "Wiring Diagram"
section.
5.
This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6.
The P90 Direct Vent Gas Fireplace is approved
for alcove installations, which meet the
clearances listed on this page.
7.
We recommend that you plan your installa-
tion on paper using exact measurements for
clearances and floor protection before actu-
ally installing this appliance. Have a qualified
inspector, dealer, or installer review your plans
before installation.
Note: For vent terminations see the "Exterior
Vent Termination
Locations" section.
Diagram 1
A)
Flat on Wall
B)
Flat on Wall Corner
C)
Recessed into
Wall/Alcove
D)
Corner
HEATWAVE
DUCT SYSTEM
OPTIONAL KIT
#946-556
The
HeatWave
Air Duct Kit increases the
effectiveness of your fireplace by dispersing
warm air from the fireplace to remote locations in
the same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
Please Note:
Only 1 HeatWave kit may be
operated at one time. This includes the internal
blower option as well.
OPTIONAL
HEAT RELEASE KIT
#946-570
The Heat Release Kit expels warm air from
the fireplace to the outside of the building,
allowing the fireplace to be operated with less
heat entering the room. The kit may be used
on either the left or right side.
WARNING:
Fire hazard is an extreme risk
if these clearances are not
adhered to.
Clearances for HeatWave and
Heat Release Kit
Heat Release Kit
The
HeatWave
Duct Kit and the Heat Release
Kit have different clearance and framing
requirements, check the
HeatWave
and Heat
Release manual for details.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
NOTE: The minimum floor clearance must be
maintained from the top surface of the carpeting,
tile, etc.
See Hearth Requirements in this manual.