28
|
Regency Excalibur
®
P90-10 Zero Clearance Direct Vent Gas Fireplace
|
28
installation
Vertical Venting with Two (2. 90
o
Elbows
Vertical Venting with Three (3. 90
o
Elbows
Must Use: 5" x 8" Simpson Direct Vent Piping with FPI Increaser
Starter Collar (Part #946-605., unless V1 is greater than or equal
to 4'-6" then use 4" x 6-5/8" piping.
Option V
H
V + V1
A)
0' Min. 2' Max. 1' Min.
B)
1' Min. 4' Max. 2' Min.
C) 2' Min. 5' Max. 3' Min.
D) 3' Min. 6' Max. 4' Min.
E)
4' Min. 7' Max. 5' Min.
F)
5' Min. 8' Max. 6' Min.
One 90
o
elbow = Two 45
o
elbows.
With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and max.
8 feet total horizontal.
Please note min. 1 foot
between 90
o
elbows is
required.
For additional vertical venting with 2 x 90
o
elbows, refer to the
"Rigid Pipe Venting Arrangements - Horizontal Termination"
section.
Must Use: 5" x 8" Simpson Direct Vent Piping with FPI Increaser
Starter Collar (Part #946-605..
Option V
H + H1 V + V1
A)
6" Min. 2' Max. 3' Min.
B)
1' Min. 2' Max. 3' Min.
C) 2' Min. 3' Max. 4' Min.
D) 3' Min. 4' Max. 6' Min.
E)
4' Min. 5' Max. 7' Min.
F)
5' Min. 6' Max. 8' Min.
G) 6' Min. 7' Max. 9' Min.
H) 7' Min. 8' Max. 10' Min.
One 90
o
elbow = Two 45
o
elbows.
With these options, max.
total pipe length is 30 feet
with min. of 10 feet total
vertical and max. 8 feet
total horizontal.
Please note min. 1 foot
between 90
o
elbows is
required.