Regency I31-2 Gas Fireplace Inbuilt

TEST FOR FLUE

SPILLAGE

A " spillage" test must be made before
the installed unit is left with the custom-
er. Follow the procedure below:

1) Start all exhaust fans in the home and then

close all external doors and windows in the
house.

2) Light the unit and set controls to maximum.

Turn fan off.

3) After five minutes, test that there is a “pull”

on the flue by placing a smoke match,
cigarette or similar device which gives off
smoke, in front of the spill tube. To ensure
a valid test, place a scrap piece of sheet
metal (or other noncombustible material)
between the spill tube and the upper louvre,
this will prevent the natural convection of
the unit from interfering with the test. See
diagram 1.

Diagram 1

GAS INSERT

AERATION SYSTEM

The aeration adjustment rod is attached to the
air shutter which is located just above the
orifice bracket. The rod is used to adjust the
aeration on the main burner without having to
take the appliance apart.

The burner aeration is factory set but may need
adjusting due to either the local gas supply, air
supply or altitude. This adjustment is performed
by the installer.  (Pull the rod for a more yellow
flame, or push the rod to make the flame bluer.)

Natural Gas:

8 mm open

Propane:

full open

Note: Any damage due to carboning re-

sulting from improperly setting
the aeration controls is NOT cov-
ered under warranty.

INSTALLATION

DRAFT DIVERTER

CONNECTION

1) Attach the flue to the flue collar on the

detachable draft diverter. The flue collar of
the appliance will fit inside a standard flue
and may be fastened directly to the flue by
sheet metal screw. Diagram 1.

NOTE: Final gas connection should be af-

ter unit is in place to avoid damage
to line when pushing the unit into
position.

Diagram 1

Diagram 2

FLUEING

THE APPLIANCE MUST NOT BE CONNECTED
TO A CHIMNEY FLUE SERVING A SEPARATE
SOLID FUEL BURNING APPLIANCE.

This appliance is designed to attach to a 100 mm
diameter twin skin or listed gas fuel type flue
liner running the full length of the chimney. A
minimum flue height of 3.6 m. is recommended.
The Regency Inbuilt Fireplace incorporates its
own internal draft diverter, so no additional
external draftdiverter is required.

Periodically check that the flue is unrestricted
and an adequate draft is present when the unit
is in operation. (See page 7 for spillage test.)

Before installing flue system ensure that the
damper plate is open and secure to prevent the
damper plate from falling down and crushing
the liner.

Install to AG 601,(Australia) NZS 5261 (New
Zealand).

Combustion and Ventilation Air

WARNING:  This appliance needs
fresh air for safe operation and must
be installed with provisions for ade-
quate combustion and ventilation
air available to the room in which it
is to be operating.

Air for combustion is drawn in through the front
of the unit, therefore, the front of the unit must
be kept clear of any obstructions.

GAS PRESSURE TEST

The unit is preset to give the correct gas input
at the specified manifold pressures shown on
the label. The maximum gas manifold pressure
is:

Natural Gas

0.9 kPa

Propane

2.65 kPa

The manifold pressure is controlled by a regu-
lator built into the gas control, and should be
checked at the pressure test point. The pres-
sure check should be carried out with the unit
burning and the setting should be within the
limits specified.

2) Before pushing the appliance into position

inside the fireplace, align the draft diverter
with the guides on the insert top and push
forward. While pushing the unit back into
place keep pulling the draft diverter forward
until the screw hole in the spill tube aligns
with the screw hole in the top of the firebox.
The screw is secured through the inside top
of the firebox into the bottom of the spill tube.
(If screw holes do not line up then draft
diverter is not positioned correctly.)
 Diagram 2.

Summary of Contents for I31-2

Page 1: ...ry to light any appli ance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplierfromaneighbour s phone Follow the gas sup plier sinstructions If y...

Page 2: ...s been designed to provide you with all the warmth and charm of a fireplace at the flick of a switch The model I31 2 of this series has been approved by Australian Gas Association for both safety and...

Page 3: ...Fan Maintenance 15 TroubleShooting 17 Parts List 18 Warranty Warranty 23 Page UnitDimensions 2 SafetyLabel 4 Installation For Your Safety 5 Specifications 5 Installation Checklist 5 MaterialsRequired...

Page 4: ...label that accompanies each Regency I31 2 Gas Inbuilt fireplace We have printed a copy of the contents here for your review DATA BADGE NOTE Regency units are con stantly being improved Check the labe...

Page 5: ...ustible fire place The appliance and flue should be enclosed when installed or passing through a living area where children may come in contact with it 5 Always connect this space heater to a chimney...

Page 6: ...TIONS INSTALLATION NOTE Mantel clearances for Installation into a Zero Clearance Kit are differ ent Please refer to the Zero Clear ance Kit Manual for details Mantel Clearances with Bay and Flush Louv...

Page 7: ...ED TOACHIMNEYFLUESERVINGASEPARATE SOLIDFUELBURNINGAPPLIANCE Thisapplianceisdesignedtoattachtoa100mm diameter twin skin or listed gas fuel type flue liner running the full length of the chimney A minim...

Page 8: ...cts as a safety shut off to prevent a build up of carbon monoxide If the flue is blocked or has no draw the switch will automati cally shut off the supply of gas within 5 10 minutes Tampering with the...

Page 9: ...ne end of burner to the other If there is any flame hesitation check that area for any blockage of the burner port 12 Install flush glass and optional bay glass as per instructions in this manual D 02...

Page 10: ...ace the trim on the assembled faceplate panels aligning the wire connections from the switches with the notch on the left side panel 5 Hookup the 3 Fan Switch wires to the fan switch on the left side...

Page 11: ...ion fit if the louvre needs to be adjusted bend the bracket out as shown in the diagram 3 Place the bottom of the flush glass behind the bottom glass trim 4 Secure the glass with the two glass clips a...

Page 12: ...14 GA 16 GA 18 GA 20 GA 22 GA 15 24 m 9 75 m 6 10 m 3 66 m 2 71 m WIRING CAUTION Label all wires prior to disconnectionwhen servicingcontrols Wiring errors can cause improper and dangerous operation W...

Page 13: ...the unit cooled to below a useful heat output range the fan will shut off automatically NORMAL OPERATING SOUNDS OF GAS APPLIANCES It is possible that you will hear some sounds from your gas appliance...

Page 14: ...label 1 Push in gas control knob slightly and turn clockwise to OFF Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 2 Wait five 5 minutes to clear out any gas If...

Page 15: ...arranty Clean any fingerprints off before turn ing the unit on If the top louvres start to discolour check the door gasket seal and replace if necessary LOG REPLACEMENT The unit should never be used w...

Page 16: ...of dish soap on the grommet so it will slide more easily onto the pin Check to make sure the fan is seated properly on the pins this is very important try to move the fan back and forth there should...

Page 17: ...oting continues open aeration shutter on burner Note To clean glass remove and wipe with cloth or paper towel Check gas pressure Clean out carbon spider webs lint etc from burner area Check and replac...

Page 18: ...1 Spill Switch Bracket 12 910 220 Spill Switch 13 Levelling Bolts 5 16 x 3 Hex Head 948 216 Logo Plate 918 044 Manual Masport 400 945 Brick Panel Set 33 902 255 Brick Panel Back 34 902 176 Brick Panel...

Page 19: ...Gasket Valve Heat Shield 56 Pilot Bracket 57 904 240 Burner Orifice Nat Gas 37 904 390 Burner Orifice Propane 52 58 910 424 Pilot ON OFF Extension Knob 59 910 426 Flame HI LOW Extension Knob 60 402 0...

Page 20: ...plate Trim Left Assy Regular 401 913 Faceplate Trim Compelte Oversize 141 Faceplate Side Right Oversize 142 Faceplate Top Oversize 143 Faceplate Side Left Oversize 401 524 Trims Packaged Oversize 144...

Page 21: ...0 314 P Center Glass 110 902 183 Bay Brick Panel 400 935 Bay Door Trim Set Gold 400 989 Bay Door Trim Set Steel 111 Bay Door Trim Top 112 904 196 1 Round Ceramic Magnet 113 Bay Door Trim Bottom Flush...

Page 22: ..._______________________________________________ ______________________________________________________ _______________________________________________________________ _________________________________...

Page 23: ...y Assur anceTeamcarefullyinspectseachunitthoroughlybeforeit leaves our door Regency Industries Ltd is pleased to extendthislimitedlifetimewarrantytotheoriginalpurchaser of a Regency Product The Warran...

Page 24: ...Printed in Canada...

Reviews: