I1200 Regency Wood Insert

9

INSTALLATION

INSTALLING

YOUR INSERT

SAFETY NOTE:

 The insert is very heavy and 

will require two or three people to move it into 
position. The insert can be made a little lighter 
by removing the cast iron door by opening it and 
lifting it off its hinges. Be sure to protect your 
hearth extension with a heavy blanket or carpet 
scrap during the installation.

NOTE: 

You will be required to purchase either 

the standard or offset 6" diameter (152mm) 
fl ue adaptor that is best suited for the specifi c 
installation.

List of Tools needed;

 - Pull Rod (included with insert)
 - 1/2” socket / ratchet
 - 3/8 open face wrench 

1)

  Install fl ex liner into existing chimney as 

per liner manufacturer’s specifi cations. See 
diagram 1.

2)

    Install the required fl ue adaptor onto the end 

of the fl ex liner.  Secure the adaptor using 
3 screws - 1 on the front, left and right side 
as shown in diagram 2.

 

Alignment of the fl ue adaptor can be critical 
during the install, it is recommended that the 
fl ex liner be left as compressed as possible.  
Before inserting the unit the adaptor should 
hang, when level, slightly above the required 
height. 

Secure adaptor using 3 screws - 1 in the 

front and 1 each on the left and right side.

3) 

 Install the unit by fi rst setting the rear of 

the unit into the fi replace. See diagram 
3. Ensure that the unit is centered in the 
existing fi replace and lined up with the fl ue 
adaptor.

 

4)

   Slide the unit back until the fl ue adaptor is 

slightly engaged.  

5

)   At this point it is recommended to level the 

unit and ensure that the leveling bolts rest 
on the surface of the fi replace. This will keep 
the adaptor from binding as the unit is slid 
into position. 

6) 

 Insert the provided pull rod through the 

hole in the top center of the unit. Secure 
the threaded end into the fl ue adaptor as 
shown in diagram 4. While sliding the unit 
into place pull on the rod to ensure that 
the fl ue adaptor is properly engaged. See 
diagram 5. 

Pull Rod

7)

   Ensure that the unit is still level. 

8)

   To complete the installation and to ensure a 

secure fi t and connection of the fl ue adaptor 
to the insert, it is essential that the two bolts, 
fl at washers and lock washers (supplied 
with packaged manual) be installed and 
tightened using a 1/2" socket as shown in 
diagram 6. This prevents the possibility of 
creosote drip and exhaust gas leakage.

9)

   Remove the pull rod from the top center of 

the fi replace. See diagram 7.

10)

 Re-install the door if removed prior to 

installation.

NOTE: The pull rod should not be thrown 

away. It should be kept if the stove 
is ever needed to be removed from 
the fi replace.

Flex Liner

Flue Adaptor

Pull Rod In Place

Pull Rod

Diagram 1

Diagram 2

Diagram 3

Diagram 4

Diagram 5

Diagram 6

Diagram 7

Summary of Contents for I1200S Wood Insert

Page 1: ...Canada V4G 1H4 918 665a I1200S Wood Insert 07 12 07 Owners Installation Manual Tested by Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Plea...

Page 2: ...REGENCY DEALER in your area Keep those REGENCY FIRES burning SAFETY NOTE If this Insert is not properly installed a house re may result For your safety follow the installation instructions contact loc...

Page 3: ...ation into a Masonry Fireplace 10 Installation into a Factory Built Fireplace 10 Faceplate Trim Optional Fan Support Installation 11 Fan Blower 14 Firebrick Assembly 15 Draft Control 15 Door Handle 15...

Page 4: ...FROM INSERT BODY INSTALL ONLY ON A NON COMBUSTIBLE HEARTH RAISED F 1 5IN 38MM ABOVE AN ADJACENT COMBUSTIBLE FLOOR COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON COMBUSTIBLE MATERIAL EXTENDING E 16 IN 405M...

Page 5: ...I1200 Regency Wood Insert 5 UNIT DIMENSIONS WITH STANDARD FLUE ADAPTOR 6 152mm Diameter STANDARD FLUE ADAPTOR 171 932...

Page 6: ...I1200 Regency Wood Insert 6 UNIT DIMENSIONS WITH OFFSET FLUE ADAPTOR 6 152mm Diameter OFFSET FLUE ADAPTOR 171 936...

Page 7: ...your replace insert Install and use only in accordance with manufacturer s installation and operating instructions 2 Check your local building codes Build ing Inspection Department You may require a...

Page 8: ...508mm 14 356mm 7 375 187mm 16 406mm 1 5 38mm 8 203mm HOW TO DETERMINE IF ALTERNATE FLOOR PROTECTION MATERIALS ARE ACCEPTABLE The speci ed oor protector should be 3 8 18mm thick material with a K facto...

Page 9: ...rear of the unit into the replace See diagram 3 Ensure that the unit is centered in the existing replace and lined up with the ue adaptor 4 Slide the unit back until the ue adaptor is slightly engage...

Page 10: ...EPLACE The insert must be installed as per the require ments of your local inspection authority Three methods of ue connection are acceptable in most areas these include 1 Positive ue connection where...

Page 11: ...ded See Diagram 2 Diagram 2 Rear View 4 Position the assembled faceplate side and top to the insert Ensure to align the draft rod into the opening of the faceplate as well as the side faceplate slots...

Page 12: ...mounting brackets and tighten to secure in place Diagram 5 Diagram 6 Shown with Optional Bottom Faceplate Regular Oversize Faceplate Trim Installation Black Trim included with Regular Oversize Facepl...

Page 13: ...on the fan support to the bottom of the fan assembly 17 Drill 4 x 5 32 holes to the underside of the fan assembly using the holes in the fan support as a guide See Diagram 9 Diagram 9 Rear Bottom View...

Page 14: ...placemaybeadjustedby increasing or decreasing the offset spacing of the clips 3 Ensure that the power cord is not in contact with any hot stove surfaces CAUTION Label all wires prior to disconnection...

Page 15: ...If the two air tubes are installed continue on to Step 2 if not follow the instructions below Installtheairtubeintotheholesinthe side channels The notch goes on the right hand side with the air holes...

Page 16: ...he re As you dry out your re brick and your masonry ue if applicable your draft will increase 10 Forthoseunitsinstalledathigherelevations or into sub standard masonry replaces drafting problems may oc...

Page 17: ...lly operate the fan system push the rst switch to Man and second switch to either high or Low This will bypass the sensing deviceandallowfullcontrolofthefan Switching from Auto to Manual or High to Lo...

Page 18: ...acer washer shown in the diagram below will allow the latch to be moved closer to the door frame causing a tighter seal Remove and replace the nuts washer as shown MAINTENANCE GLASS CLEANING Do not at...

Page 19: ...y Door Gasket Kit 17 846 918 Hinge Caps 2 set Gold 19 948 101 Spring Handle Large Gold 20 948 102 Spring Handle Small Gold 170 915 Fan Blower Assembly 24 910 157 P Blower Fan Motor 25 910 678 Power Co...

Page 20: ...aceplate Trim Set Oversize Black 171 926 Trim Set Oversize Brass 171 928 Bottom Piece and Fan Support Regular 171 930 Bottom Piece and Fan Support Oversize 60 Faceplate Right Side Regular Oversize 61...

Page 21: ...Description 170 960 Complete Brick Set 70 Brick Regular Full Size 1 1 4 x 4 1 2 x 9 76 Brick Partial 1 1 4 x 2 x 9 81 Brick Partial 1 1 4 x 1 1 4 x 9 84 Brick Partial 1 1 4 x 4 1 2 x 8 85 Brick Partia...

Page 22: ...I1200 Regency Wood Insert 22 NOTES...

Page 23: ...of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is claimed to be defective All claims must be submitted to FPI by...

Page 24: ...___________________________________________________ Printed in Canada Regency replace products are designed with reliability and simplicity in mind In addition our internal QualityAssurance Teamcarefu...

Reviews: