GF40-2 Pellet Stove | 3
VENT TERMINATION REQUIREMENTS
IT IS HIGHLY RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER.
Use in conjunction with Table 1 for allowable exterior vent termination locations.
Table 1: Use in conjunction with Figure 6 for allowable exterior vent termination locations.
Air Supply Inlet
Gas Meter
Restriction Zone
(Termination not allowed)
Termination Cap
G
G
Opens
Opens
Opens
D
F
B
B
A
I
H
K
G
G
L
C
E
3. Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be installed outside when the appliance
is vented directly through a wall, to create some natural draft to prevent the possibility of smoke or odor during appliance shut down or power
failure. This will keep exhaust from causing a nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and
preferred venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the plants and nature of grade surface.
The exhaust gases are hot enough to ignite grass, plants and shrubs located in the vicinity of termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior of the house might occur. Since these
factors are beyond the control of FPI, we grant no guarantee against such incidents.
NOTE: Venting terminals shall not be recessed into walls or siding.
Letter
Minimum Clearance
Description
A
24 in (61 cm)
Above grass, top of plants, wood, or any other combustible materials.
B
48 in (122 cm)
Beside/below any door or window that may be opened. (18” (46 cm) if outside fresh air
installed.)
C
12 in (30 cm)
Above any door or window that may be opened. (9” (23 cm) if outside fresh air
installed.)
D
24 in (61 cm)
To any adjacent building, fences and protruding parts of the structure.
E
24 in (61 cm)
Below any eave or roof overhang
F
12 in (30 cm)
To outside corner.
G
12 in (30 cm)
To inside corner, combustible wall (vertical and horizontal terminations).
H
3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly
To each side of center line extended above natural gas or propane meter/regulator
assembly or mechanical vent.
I
3 ft (91 cm)
From any forced air intake of other appliance
J
12 in (30 cm)
Clearance to non-mechanical air supply inlet to building, or the combustion air inlet to
any appliance.
K
24 in (61 cm)
Clearance above roof line for vertical terminations.
L
7 ft (2.13 m)
Clearance above paved sidewalk or paved driveway located on public property.
1. Do not terminate the vent in any
enclosed or semi-enclosed areas such
as a carport, garage, attic, crawlspace,
narrow walkway, closely fenced area,
under a sun deck or porch, or any
location that can build up a concentration
of fumes such as stairwells, covered
breezeway, etc.
2. Vent surfaces can become hot enough to
cause burns if touched by children. Non-
combustible shielding or guards may be
required.