installation
Grandview
®
G800C-1 Gas Fireplace | 21
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
If these clearances (air space) to combustible materials are not adhered to. It is of
greatest importance that this fireplace and vent system be installed only in accordance
with these instructions.
Cool Wall Clearances
The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Minimum Vent Clearances
to Combustibles
Clearance Requirements—Cool Wall Installations
Clearance:
Cool Wall - Clean Front
Measured From:
A: Mantel Height (min.)
**0"
Top of Fireplace Opening
B: Sidewall
6" (152 mm)
Side of Fireplace Opening
C: Ceiling
47-1/2" (1207 mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
14" (356 mm)
Front of Fireplace Opening
E: Alcove Width
84" (2134 mm)
Wall to Wall (Minimum)
F: Alcove Depth
36" (914 mm)
Front to Back Wall (Maximum)
G: Convection Air Outlet
66"sq (426 cm
2
)
Top/Front of Enclosure
H: Convection Air Outlet Opening Offset
0-2" (51 mm)
*Top of Chase Enclosure
K:
Chase Enclosure (Min.)
80" (2032 mm)
From Base of Appliance Floor
L: Clearance to Sprinkler Head (Min.)
36" (914 mm)
Perpendicular From Chase Grill
Notes:
0"
No Hearth Required
IMPORTANT - *A minimum of 66 square inches of open area, not lower than 0"-2" from top of enclosure, required
for all cool wall installations — this can be achieved by having an open area in front. See manual for details.
** An extra 3/4" (19mm)of mantel height is required when using a faceplate.
Horizontal Top
2" (51 mm)
Horizontal Side
1-1/2 " (38 mm)
Horizontal Bottom
1-1/2" (38 mm)
Vertical Vent
1-1/2" (38 mm)
Alcove
E
F
D
A
E
F
H
G
K
C
Side view
L
Chase grill
Sprinkler
The
HeatWave
Duct Kit has different
clearance and framing requirements, check
the
HeatWave
manual for details.