B41XTCE Gas Fireplace

MANTEL CLEARANCES

Note:  Ensure the paint that is used on the mantel 

and the facing is "heat resistant" or the 

paint may discolour.

MANTEL LEG CLEARANCES

Due to the extreme heat this fireplace emits, the 

mantel clearances are critical. 

Combustible mantel 

clearances from top of front facing are shown in the 
diagram on the right.

Note:  A non-combustible mantel may be 

installed at a lower height if the framing 

is made of metal studs covered with a 

non-combustible board.

Combustible

Mantel Clearances

2

0

12

6

4

8

10

0

Top of

Fireplace

Opening

12

1"

7

A

B

C

Non-combustible

Header

(steel stud)

on edge

14

To Floor

12

24

Inches

D

6

Non-combustible

Standoff

Mantel Clearances

B41XTCE

A

B

C

D

From Top of

Fireplace Opening

32-11/16"

(830mm)

25-13/16"

(656mm)

22-1/16"

(560mm)

17-9/16"

(446mm)

9 Side Wall

(Measured from side of

Fireplace Opening)

7

4

Mantel

le

g

Mantel

le

g

Allowable mantel leg

projection.

3"

1-1/2"

Summary of Contents for Bellavista B41XTCE

Page 1: ...aming height requires consideration of the hearth depth Dimension N N the thickness of the installed hearth Approved Venting Systems Flex Vent Systems FPI AstroCap Flex Vent Rigid Pipe Vent Systems Simpson Direct Vent Pro Selkirk Direct Temp Metal Fab Sure Seal ICC Excel Direct Vent Framing Dimensions Description B41XTCE M Framing Width 47 1 4 1200mm N Framing Height 49 1 2 1257mm O Rear Vent Fram...

Page 2: ... required clearances air space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions Clearance Dimension Measured From A Mantel Height min 17 9 16 446mm Top of Fireplace Opening B Sidewall 9 229mm Side of Fireplace Opening C Ceiling 36 5 8 930mm Top of Fireplace Opening D Mantel Depth max 12 304mm 25 13...

Page 3: ...on combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Combustible Mantel Clearances 2 0 12 6 4 8 10 0 Top of Fireplace Opening 12 1 7 A B C Non combustible Header steel stud on edge 14 To Floor 12 24 Inches D 6 Non combustible Standoff Mantel Clearances B41XTCE A B C D From Top of Fireplace Opening 32 11 16 830mm 25 13 1...

Page 4: ...e finishing material tile slate etc the material can be installed directly onto the metal surface clean front of the unit in the area shown below CLEAN FINISH 6 If applying a non combustible facing it may be installed over the metal surface clean front of the unit in the area shown below Combustible and Non combustible Facing and Finishing Materials around unit 38 7 16 976mm 29 737mm Combustible M...

Page 5: ...anel NOTE Non combustible finishing materials may be of any thickness desired Minimum Clearances for Finishing Materials Trim materials Note All non combustible facingmaterialshouldbuttupcleanly to the flanges around the firebox opening Rough edges may be visible from an angle To maintain a clean finished edge facing material edges may be finished with a J style trim or metal cornerbead both mater...

Page 6: ...Height Feet Rigid or Flex 47 1 2 1 2m Horizontal Feet Max 36 0 9m 2 0 6 4 8 2 0 6 4 8 Vertical Height Feet 28 1 2 0 7m Horizontal Feet Max 36 0 9m Vent Restrictor Set 1 Factory Setting No Restrictor Required VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS FLEX VENT OR RIGID PIPE 5 X 8 REAR VENTING DEFLECTOR INSTALLATION FOR REAR VENTED HORIZONTAL TERMINATIONS Rear Venting Deflector The Rear Vent ...

Page 7: ...iagram shows all allowable combinations of straight vertical and offset to vertical terminations using two 90o elbows with Rigid Pipe Venting Systems for Propane and Natural Gas Two 45o elbows equal to one 90o elbow Maximum of four 45o elbows allowed Minimum 8 2 4m Min 47 1 2 1 2m 0 2 4 6 40 8 10 12 14 16 18 20 22 24 26 28 30 Vertical Height Feet 32 34 36 38 6 8 Horizontal Feet 2 0 4 10 12 Restric...

Reviews: