B41XTCE Gas Fireplace
MANTEL CLEARANCES
Note: Ensure the paint that is used on the mantel
and the facing is "heat resistant" or the
paint may discolour.
MANTEL LEG CLEARANCES
Due to the extreme heat this fireplace emits, the
mantel clearances are critical.
Combustible mantel
clearances from top of front facing are shown in the
diagram on the right.
Note: A non-combustible mantel may be
installed at a lower height if the framing
is made of metal studs covered with a
non-combustible board.
Combustible
Mantel Clearances
2
0
12
6
4
8
10
0
Top of
Fireplace
Opening
12
1"
7
A
B
C
Non-combustible
Header
(steel stud)
on edge
14
To Floor
12
24
Inches
D
6
Non-combustible
Standoff
Mantel Clearances
B41XTCE
A
B
C
D
From Top of
Fireplace Opening
32-11/16"
(830mm)
25-13/16"
(656mm)
22-1/16"
(560mm)
17-9/16"
(446mm)
9 Side Wall
(Measured from side of
Fireplace Opening)
7
4
Mantel
le
g
Mantel
le
g
Allowable mantel leg
projection.
3"
1-1/2"