B41XTCE Gas Fireplace

Caution Requirements

The top, back and sides of the fireplace are defined by 

standoffs. The metal ends of the standoff may 

NOT

 

be recessed into combustible construction.

WARNING

Fire hazard is an extreme risk 

if these clearances (air space) to combustible materials are not 

adhered to. It is of greatest importance that this fireplace and vent 

system be installed only in accordance with these instructions.

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest 

importance that this fireplace and vent system be installed only in accordance with these instructions.

Clearance:

Dimension

Measured From:

A: Mantel Height (min.)

17-9/16" (446mm)

Top of Fireplace Opening

B: Sidewall

9" (229mm)

Side of Fireplace Opening

C: Ceiling

36-5/8" (930mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

12" (304mm)

25-13/16" (651mm)

from Top of Fireplace Opening

E: Alcove Width

60" (1524mm)

Wall to Wall (Minimum)

F: Alcove Depth

36" (914mm)

Front to Back Wall (Maximum)

Notes:

0"

No Hearth Required

B41 XTCE Clearance Requirements

C

D

A

E

F

C

Close to Ceiling

F

E

Alcove

E

F

Horizontal Top

3" (76mm)

Horizontal Side

2 " (51mm)

Horizontal Bottom

2" (51mm)

Vertical Vent

2" (51mm)

Minimum Vent Clearances

to Combustibles

Summary of Contents for Bellavista B41XTCE

Page 1: ...aming height requires consideration of the hearth depth Dimension N N the thickness of the installed hearth Approved Venting Systems Flex Vent Systems FPI AstroCap Flex Vent Rigid Pipe Vent Systems Simpson Direct Vent Pro Selkirk Direct Temp Metal Fab Sure Seal ICC Excel Direct Vent Framing Dimensions Description B41XTCE M Framing Width 47 1 4 1200mm N Framing Height 49 1 2 1257mm O Rear Vent Fram...

Page 2: ... required clearances air space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions Clearance Dimension Measured From A Mantel Height min 17 9 16 446mm Top of Fireplace Opening B Sidewall 9 229mm Side of Fireplace Opening C Ceiling 36 5 8 930mm Top of Fireplace Opening D Mantel Depth max 12 304mm 25 13...

Page 3: ...on combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Combustible Mantel Clearances 2 0 12 6 4 8 10 0 Top of Fireplace Opening 12 1 7 A B C Non combustible Header steel stud on edge 14 To Floor 12 24 Inches D 6 Non combustible Standoff Mantel Clearances B41XTCE A B C D From Top of Fireplace Opening 32 11 16 830mm 25 13 1...

Page 4: ...e finishing material tile slate etc the material can be installed directly onto the metal surface clean front of the unit in the area shown below CLEAN FINISH 6 If applying a non combustible facing it may be installed over the metal surface clean front of the unit in the area shown below Combustible and Non combustible Facing and Finishing Materials around unit 38 7 16 976mm 29 737mm Combustible M...

Page 5: ...anel NOTE Non combustible finishing materials may be of any thickness desired Minimum Clearances for Finishing Materials Trim materials Note All non combustible facingmaterialshouldbuttupcleanly to the flanges around the firebox opening Rough edges may be visible from an angle To maintain a clean finished edge facing material edges may be finished with a J style trim or metal cornerbead both mater...

Page 6: ...Height Feet Rigid or Flex 47 1 2 1 2m Horizontal Feet Max 36 0 9m 2 0 6 4 8 2 0 6 4 8 Vertical Height Feet 28 1 2 0 7m Horizontal Feet Max 36 0 9m Vent Restrictor Set 1 Factory Setting No Restrictor Required VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS FLEX VENT OR RIGID PIPE 5 X 8 REAR VENTING DEFLECTOR INSTALLATION FOR REAR VENTED HORIZONTAL TERMINATIONS Rear Venting Deflector The Rear Vent ...

Page 7: ...iagram shows all allowable combinations of straight vertical and offset to vertical terminations using two 90o elbows with Rigid Pipe Venting Systems for Propane and Natural Gas Two 45o elbows equal to one 90o elbow Maximum of four 45o elbows allowed Minimum 8 2 4m Min 47 1 2 1 2m 0 2 4 6 40 8 10 12 14 16 18 20 22 24 26 28 30 Vertical Height Feet 32 34 36 38 6 8 Horizontal Feet 2 0 4 10 12 Restric...

Reviews: