- 15 -
Troubleshooting Guidelines
(CONT’D)
3. Connect motor terminals 1, 3, & 5 to either 24VAC or 18VDC and
Common to terminal C.
4. Reconnect the main power to the HVAC system.
5. Energize motor terminals 1, 3, & 5 with either 24VAC or 18VDC and
Common to terminal C continuously for a minimum of 5 minutes.
6. Disconnect the main power to the HVAC system for a minimum of 3
minutes.
7. Disconnect the 24VAC or 18VDC from motor terminals 1, 3, & 5 and
Common from terminal C.
8. Reconnect the Low Voltage Control Input connection(s) to the motor.
9. Reconnect the main power to the HVAC system.
If the motor continues to operate in the wrong direction, repeat this
procedure carefully and confirm all timings. If after several attempts,
changing the rotation has not been successful, please call the
Evergreen
Hotline at 866-503-8566
.
Replacing the Evergreen EM
If the motor does not operate with proper High Voltage Power and low
voltage communication present at the motor, it is failed and will require
replacement. Before replacing the motor, please call the Contractor
Hotline to confirm your diagnostics if possible. The Evergreen EM is a single
component replacement. The control cannot be replaced separately from
the motor. Contact the distributor where the motor was purchased or any
authorized Evergreen distributor for replacement.
If the troubleshooting guidelines provided here do not solve the problem
or you have a problem not listed here, please contact the
Evergreen
Contractor Hotline 1-866-503-8566
. Additional support is available at
www.theDealerToolbox.com.
®
EM