
24
10 DIP Switches
Table 5: DIP Switch Functions
Figure 8: DIP Switches
Switch # Function
1
Power output on/off
2
Not Used
3
Not Used
4
Not Used
5
Not Used
Figure 7: System Level Control Wiring Diagram
Relay 1
Relay 2
Relay 3
Relay 4
Load
Load
Load
Load
Line
Line
Line
Line
System Level Control
Access to these terminals is in close proximity to the mains connectors which carry line
voltage capable of causing personal injury or damaging the equipment if contact is made.
Power should be turned off when accessing this area.
The DIP switches can be used to confi gure diff erent settings for the
VGreen 165. Each DIP switch and their corresponding function is de-
fi ned in Table 5.
Access to these terminals is in close proximity to the mains connectors which carry line
voltage capable of causing personal injury or damaging the equipment if contact is made.
Power should be turned off when accessing this area.
NOTE:
If no digital input is detected, the VGreen 165 will automatically
start the 24 hour schedule if the START key was pressed prior to the
application of a digital input.
10019878-001-001 _V-Green165 UM_7-30-19.indd 26
8/5/2019 4:26:59 PM