![Regada SO 2-Ex Installation, Service And Maintenance Instructions Download Page 4](http://html1.mh-extra.com/html/regada/so-2-ex/so-2-ex_installation-service-and-maintenance-instructions_1433054004.webp)
2
SO 2-Ex
The Installation, Service and Maintenance Instructions are drawn up according to requirements of EC Executive
Nr. 2006/42/EC "Uniform requirements for machines and devices from the point of view of safety and health
care", to save life and health of users and to avoid material damages and exposure environment to danger.
1. General Information
1.1 Purpose and Application
Explosion-proof electric multi-turn actuators
(hereafter referred to as
EA
), types
SO 2-EX respectively SO
with controller
are
high performance electro-mechanical products, designed for direct assembly on
controlled devices . EA of SO 2-Ex types are provided for remote control of closing bodies, and EA of SO
2-Ex with controller for automotive control of regulating bodies. They are equipped by measuring and
technological processes controlling means; the information carrier on their
input
and/
or
output is unified
analogue direct current, or voltage signal. They can be used in heating, energy, gas, air-conditioning and
other technological equipments, for which are suitable due to their manufacturing qualities. They are
assembled by means of flange and connecting component in accordance with ISO 5210 , resp. DIN 3338,
resp. GOST R 55510.
1. It is forbidden to use the EA as a lifting mechanism!
2. Switching of actuator by a semiconductor components/switches have to be consulted with
producer.
1.2
Safety Instructions
Product characteristics from risk point of view
EA are reserved technical devices with higher rate of danger (group A), with possibility of
installation in areas specially danger regarding casualties caused by electric current. EA are according to
directive LVD 2014/35/EU and standard EN/IEC 61010-1 within valid edition assigned for installation
category II (overvoltage category).
Product influence to environment
Electromagnetic compatibility (EMC
): the product complies with the requirements of the Directive 2014/30/EU
of the European Parliament and of the Council on the approximation of the laws the Member States relating to
the electromagnetic compatibility and with the requirements of EN standards as well EN/IEC 61000-6-4+A1,
EN/IEC 61000-6-2, EN/IEC 61000-3-2 and EN/IEC 61000-3-3 within valid edition.
Vibrations caused by the product:
product influence is negligible.
Noise produced by the product:
The maximum allowable noice level (A) of the product measured in a place of
operation is 80dB (A).
Electric actuators are made in explosion-proof version Ex db eb h II B T5 Gb and
Ex h tb IIIC T100
°
C Db, pursuant to:
EN/IEC 60079-0: Explosive atmospheres – Part 0 : Equipment general requirements – General requirements
EN/IEC 60079-1: Explosive atmospheres – Part 1 : Equipment protection by flameproof enclosures “d”
EN/IEC 60079-7: Explosive atmospheres - Part 7: Equipment protection by increased safety "e".
EN/IEC 60079-31: Explosive atmospheres – Part 31: Equipment dust inition protection by enclosure „t“, within
valid edition.
Electric parts EA are proposed:
- as devices of the group
II resp. III
for others threatened areas (excluding mines)
- of the category
2
with demanding requirements for safety
- for use max. in zone
1, 2, 21 a 22.
-
for atmospheres
G
(gases, vapors or mists )
or
D
(combustible conductive dusts)
- topressure range from 0.8 to 1.1 bar.
Design version is :
- flameproof enclosures “
db
“,
increased safety
“eb”
or level dust ignition protection by enclosure
“tb”
- with explosion protection group
IIB
or
IIIC
- and temperature class
T5
(max. permissible surface tempe100°C.
Zones for installation of explosion-proof electric actuators and conditions for equipment installation are defined in
the following standards:
EN/IEC 60079-10: Electrical apparatus for explosive gas atmospheres
Part 10: Classification of hazardous areas
EN/IEC 60079-14: Electrical apparatus for explosive gas atmospheres
Part 14: Electrical installations in hazardous areas
II 2 G
II 2 D
Summary of Contents for SO 2-Ex
Page 31: ...SO 2 Ex 29 7 Enclosures 7 1 Wiring diagrams SO 2 Ex...
Page 32: ...30 SO 2 Ex 7 2 Wiring diagrams SO 2 Ex with controller...
Page 33: ...SO 2 Ex 31...
Page 35: ...SO 2 Ex 33 7 3 Dimensional drawings...
Page 36: ...34 SO 2 Ex...
Page 37: ...SO 2 Ex 35...
Page 38: ...36 SO 2 Ex...
Page 39: ...SO 2 Ex 37...
Page 40: ...38 SO 2 Ex...
Page 41: ...SO 2 Ex 39...