SO 2-Ex
11
Electric control:
•
remote control (the output element of the EA is controlled with supply voltage) (SO 2-Ex), resp. SO
2-Ex with built-in controller - by feeding of unified signal
•
Adjustment of the limit positions
Precision of limit position switches .........................adjustment working stroke ± 5% of max. set stroke
Additional position relays adjustment ................................ ..cca 1 revolution beneath the limit switches
Hysteresis of position switches ................................................... max. 5% of the max. stroke of the
chosen range
Failure of the customer to specify the particular operating speed parameter in more details the speed
are set to the value according to the 3
rd
degree of the selected range – see Table 2.
Adjustment of the torque switches:
If other adjustment not specified the switching torque is set to the maximum value with tolerance of
±10 %.
Switches – standard version D38:
supply voltage ...................... 250 V(AC); 50/60 Hz; 6(4) A; cos
ϕ
=0,6, resp.: 24 V (DC); T=L/R=3ms
min. current 100mA
Switches – gold-plated contacts – special version D41:
supply voltage 0,1(0,05) A, max. 250 V AC;
0,1 – 24 V DC; T=L/R=3ms
min. current 5mA
Space heaters
(
E1
)
The space heater – supply voltage: .... according to the supply voltage of the motor (max. 250 V AC);
Heating power: .......................................................................................................... cca 20 W/55°C
Thermal switches of the space heaters (F2)
Supply voltage: ............................ according to the supply voltage of the motor (max. 250 V AC, 5 A)
Temperature of switching on: +20
°
C
±
3 K
Temperature of switching off: +30
°
C
±
4 K
Manual control:
- with a handwheel after pressing the detent button. Rotate the handwheel clockwisely to move the
output shaft in the direction „Z“.
Position transmitter
Resistive – potentiometer:
Resistance (single
B1
):............................................................................................... 100
Ω
, 2000
Ω
Resistance (double
B2
): ...................................................................................... 2x100
Ω
, 2x2000
Ω
Operating life of transmitter .................................................................................................
10
6
cycles
Load capacity:..................................................................................... 0,5 W up to 40°C (0 W/125°C)
Maximum current of sliding contact ................................................................................ max. 35 mA
Maximum supply voltage:.......................................................................................... PxR V DC/AC
Potentiometer linearity error:...............................................................................................
±
2.5 [%]
1)
Potentiometer hysteresis:............................................................................................... max.2,5 [%]
1)
for
SO 2-Ex
"O" (open) .....
≥
93%, "Z" (closed) ..............................................
≤
5%
for
SO 2-Ex with controller
"O" (open) ...
≥
85 % and
≤
95%; "Z" (closed)
≥
3 % and
≤
7%
Summary of Contents for SO 2-Ex
Page 31: ...SO 2 Ex 29 7 Enclosures 7 1 Wiring diagrams SO 2 Ex...
Page 32: ...30 SO 2 Ex 7 2 Wiring diagrams SO 2 Ex with controller...
Page 33: ...SO 2 Ex 31...
Page 35: ...SO 2 Ex 33 7 3 Dimensional drawings...
Page 36: ...34 SO 2 Ex...
Page 37: ...SO 2 Ex 35...
Page 38: ...36 SO 2 Ex...
Page 39: ...SO 2 Ex 37...
Page 40: ...38 SO 2 Ex...
Page 41: ...SO 2 Ex 39...