DMS3
DMS3 MO_a_74107602_19.7.2012
version 1.3
74 1076 02
52
Code
Name
Warning
1
Error
1
Reason
Reparation
manufacturer.
46 Module LCD
X
Error of communication of
LCD module
1.
Check the wiring between module and control
unit
2.
Check the parameter
LCD module.
When the
module is used the value of parameter must
beset to the X.
47 Module type
Position
X
Unknown type of position
module.
48 Module type
Torque
X
Unknown type of torque
module
49 Module type LED
X
Unknown type of LED
module
51 Module type LCD
X
Unknown type of LCD
module
52 Module type
Power
Supply/Relay
X
Unknown type of PWR
module
1.
Use different type of module. This one is not
supported by control unit
2.
Use the newer type of control unit
54 I2C
X
Error of communication of
I2C bus
1.
Turn off and on the power line.
2.
If the error is still active replace the control
unit.
55 Power frequency
X
Indefinable
Power frequency
1.
To test parameters your timing network and
parameter power supply board the system.
As far as power supply board non - support
frequency timing network, replace
her in suitable type.
2.
To test connection power supply
in source power supply board, not allowed
give out toward his disconnecting
e.g . bad contact.
56 V5V
X
Voltage less as 4,5 V
1.
Change power supply board
2.
Change control unit
57 Torque check
X
Parameter
Torque check
=unexecuted
1.
Perform functional
Torque check
and setup
parameter
Torque check =Done
58 End position
-
-
During calibration
regulator has been
achieved end position
1.
Restart calibration regulator the best further
from end positions
1
Codes of errors may vary in different version of firmware or factory settings.
If the errors persist then contact the manufacturer.
§
In case of EA error the error is indicated by the blink of LED ERR.
§
LED is flashed for a longer period, which indicates the beginning of the error.
§
The following number of blinks indicates:
o
The errors of the units 1..9
o For the units 11..99 and after the short pause of the unit
§
When several errors are reported, the individual errors are displayed in sequence. Individual errors are
indicated separately by longer light of LED ERR.
§
After all errors are reported, reports of individual errors are repeatedly shown in cycles, until
individual errors are removed.
Example: Fault 26, 8:
ERR light ON
2x blink = 20
6x blink
26
ERR light OFF
synchronization
ERR light ON
8x blink
8
ERR light OFF
ERR
PAR SEL
MENU