DMS3
DMS3 MO_a_74107602_19.7.2012
version 1.3
74 1076 02
51
Code
Name
Warning
1
Error
1
Reason
Reparation
26 Bus error
X
Bus error
1.
Check the wiring between all modules.
2.
Disconnect the bus cabel from control unit. If
the error is still active replace the control unit.
3.
Connect only the bus cabel and disconnect
from it all modules. If the error occurred,
replace the bus cabel.
4.
Consecutively connect particular modules.
After each one check if the error occurred.
28 Phase
X
Missing phase or wrong
sequence of phases
1.
Check the voltage of each phase and also
the voltage between all phases.
2.
Switch any two phases.
29 Relay
X
Operating life of relay
overflow
1.
Replace the relay and clear the counter
Sum
engine O contacts
and
Sum engine C contacts
.
31 ROM
X
Wrong CRC of ROM
1.
Turn off and on the power line. If the error
appears again send the control unit to the
manufacturer.
33 Wrong command
X
Inputs O and C are active
simultaneously.
1.
Check the function of superior system.
34 Inertia
-
-
Calibration measured the
inertia of actuator wrongly
1.
Start calibration.
35 Stop time
-
-
Calibration measured the
drifting wrongly
1.
Start calibration
36 Manual control
X
Input SW3 for manual
control is activated.
1.
Deactivation of input SW3 for manual control.
2.
Check the parameter
Manual control
. If the
manual control is not active the value
of parameter must be OFF.
37 Position module
X
Error of communication of
position module
1.
Check the wiring between module and control
unit
38 Torque module
X
Error of communication of
torque module
1.
Check the wiring between module and control
unit
2.
Check the parameter of torque configuration.
When the module torque is enabled then the
parameter must be set to the
switch-off min -
100% or
switch-off 100%.
39 Module LED
X
Error of communication of
LED module
1.
Check the wiring between module and control
unit
2.
Check the parameter
LED module.
When the
module is used the value of parameter must
be set to the X.
41 Wrong position
X
Position of an actuator is
out of set stroke
1.
Using hand control set the position back into
operation range.
2.
Check the parameter
Position O
and
Position C
.
42 Power
Supply/Relay
module
X
Error of communication of
Power Supply/Relay
module
1.
Check the wiring between module and control
unit
2.
Check the parameter
Power Supply/Relay
module
.
When the module is used the value of
parameter must beset to the X.
43 Parameters
X
Different or out of bounds
parameters in EEPROM
1.
Only using EHL explorer app. Parameters
which are reported as wrong write the new
value from allowed range.
44 Rotation
X
Actuator is not rotating
1.
check if the motor is rotating. If not remove
the cause.
2.
Check if the value
Position absolute
in window
monitoring is changing. If the value is not
changing during rotation then check the
rotation of shaft with magnet of position
sensor.
3.
Check the parameter
Rotation checking time.
.
Increase the value until it is ok.
45 Reset
X
Processor was incorrectly
reset
1.
This error is counted in counter of errors and it
is automaticaly resolved. If the error is
generated often then contact the