REGISTER ERRORS AND WARNINGS
Code
Name
Warning
1
Error
1
Reason
Reparation
1 ESD
X
Input ESD activated
1.
Deactivate input ESD.
2.
Check the wiring.
2
Analog control
signal
X
Analog control signal
is < 3,5 mA
1.
Connect the control signal correctly to the
conIN -IN
2.
Check the regulation parameter. If the
analog control signal is disabled regulation
parameter must be set to the 2P mode.
3.
Check the control signal using some
multimeter.
4.
Check the parameter
analog control signal
.
If the signal is 0 – 20mA then parameter
must be set respectively.
5.
Recalibrate input of control signal. It means
parameter 1mA and 20mA.
3 Calibration
-
-
Calibration starts when
torque is activated
1.
Move the actuator to the position when
torque is not activated.
4 Torque
X
X
Torque was activated
outside the end positions
1.
Check the end limit position
O
and
C
. End limit
position must be set between torque values.
2.
Check if there is some mechanical obstacle.
6 Thermo fuse
X
Overheating is activated
1.
Wait until motor is cooled down.
2.
Check the wiring.
7 Direction
X
Sense of rotation is
reversed
1.
Check the sense of rotation of position sensor.
2.
Check the right wiring of the motor.
3.
Check the right connection of phases
when three-phase motor is used.
8 EEPROM
X
CRC of EEPROM does not
match
1.
Record any parameter without changing
its value.
9 RAM
X
CRC of RAM does not
match
1.
Reloading parameters will automatically repair
this error.
2.
If the error occurred repetitively send the
control unit to manufacturer.
11 Menu mode
X
System is in menu
1.
Exit the LCD or LED MENU.
2.
Exit the setting mode in EHL explorer, e.g.
after manual control of motor.
3.
Turn off and on the power line.
12 Torque sensor
X
Error of torque sensor
1.
Change the broken gearbox of the torque
sensor. Magnet must be in specified distance
from the sensor and must have specified
strength of magnetic field.
2.
Replace the broken torque sensor.
13 Sensor of
position 1
X
Error of position sensor 1
1.
Check the mounting of position sensor.
2.
Replace the position sensor module.
3.
Replace the gearbox of position sensor
module.
14 Sensor of
position 2
X
Error of position sensor 2
See code nr.13
15 Sensor of
position 3
X
Error of position sensor 3
See code nr.13
16 Sensor of
position 4
X
Error of position sensor 4
See code nr.13
17 Regulator
calibration
X
Unexecuted calibration
1.
Start regulator calibration.
18 Torque
calibration
X
Wrong settings of torque
values
1.
Backup the parameters from system backup or
from file.
2.
Torque calibration.
19 Stroke
X
Wrong settings of stroke
value
1.
Reset the parameters
Position C
and
Position
O
. New values must meet the required range.
21 Temperature <
X
Temperature is too low
1.
Check the parameter
Temperature min
.
2.
Check the value of current temperature.
3.
Check the function of heating.
22 Temperature >
X
Temperature is too high
1.
Check the parameter
Temperature max
.
2.
Check the value of current temperature.