Controller
Fillcontrol Auto Compact — 20.10.2020 - Rev. D
English — 13
ER
Code
Alarm
Floating
contact
Causes
Remedy
Alarm reset
01
Min. pressure
–
Only with Magcontrol
JA
The set value for the "P
0
" minimum working
pressure has been exceeded.
•
Water loss in the system.
•
Expansion vessel defective.
•
Fault at the "PU" pump.
•
Check the system for leaks.
•
Replace the expansion vessel.
•
Check the function in manual mode.
–
"PU" pump
"Quit"
02.1
Insufficient water
No water in the mains separator tank.
•
Ball valve in make-up line closed.
•
Dirt trap clogged.
•
Float valve defective.
•
Open the ball valve in the make-up
line.
•
Clean the dirt trap.
•
Replace the float valve.
04.1
Pump
JA
Pump does not start.
•
"PU" pump is stuck.
•
Pump motor defective.
•
10 A fuse defective.
•
Contactor (Klixon) tripped.
•
Manually turn the pump to start.
•
Replace the pump motor.
•
Replace the fuse.
•
Check the mechanical and electrical
functions of the pump motor.
"Quit"
06
Make-up time
Set value for the make-up time has been
exceeded.
•
Severe water loss in the system.
•
Make-up line not connected.
•
Make-up rate insufficient.
•
Make-up hysteresis too high.
•
Check the system for leaks.
•
Connect the make-up system.
•
Check the make-up rate.
•
Check the make-up hysteresis.
"Quit"
07
Make-up cycles
Set value for the make-up cycles has been
exceeded.
•
Leakage in the system.
•
Check the system for leaks.
"Quit"
08
Pressure measurement
–
Only with Magcontrol
JA
Controller receives incorrect signal.
•
Pressure transducer plug not plugged in.
•
Broken wire from "PIS" pressure
transducer.
•
"PIS" pressure transducer defective.
•
Plug in the plug.
•
Replace the wire.
•
Replace the "PIS" pressure
transducer.
"Quit"
10
Maximum pressure
–
Only with Magcontrol
Set value for the maximum pressure has been
exceeded.
•
Safety valve defective.
•
Pipe to system has insufficient diameter.
•
Check the actuating pressure of the
safety valve.
•
Replace the safety valve.
•
Install new pipe to the system with
sufficient diameter.
"Quit"
11
Make-up volume
–
Only if "With water
meter" is activated in the
Customer menu.
Set value of the water meter has been
exceeded.
•
Leakage in the system.
•
Water volume per contact incorrectly set
in the Service menu.
•
Check the system for leaks.
•
Check the set value.
"Quit"
16
Power failure
No power.
Check power supply.
–
19
Stop > 4 h
The device is in Stop mode for more than 4
hours.
Select Automatic mode.
–
20
Max. make-up volume
Set value for the make-up quantity has been
exceeded.
Reset the "Make-up volume" meter in the
Customer menu.
"Quit"
21
Maintenance recommended
Set value exceeded.
Carry out maintenance.
"Quit"
24
Softening
•
Set value for the water capacity has been
reached.
•
Time interval for replacement of the
softening cartridge has been reached.
Replace the softening cartridge.
"Quit"
30
I/O module fault
•
I/O module defective.
•
Connection between option card and
controller faulty.
•
Option card defective.
Inform Reflex Customer Service.
31
EEPROM defective
JA
•
EEPROM defective.
•
Internal calculation error.
Inform Reflex Customer Service.
"Quit"
32
Undervoltage
JA
Supply voltage too low.
Check power supply.
33
Adjustment parameter faulty
EEPROM parameter memory defective.
Inform Reflex Customer Service.
34
Main board communication
faulty
•
Connecting cable defective.
•
Main board defective.
Inform Reflex Customer Service.
35
Digital input voltage faulty
Short-circuit of input voltage.
Check the wiring at the digital inputs
(water meter, for example).
36
Analogue input voltage faulty
Short-circuit of input voltage.
Check the wiring at the analogue inputs
(pressure/level).