CONTROL UNIT SERIES AUS X
28
8540643 - 26/08/2016 Rev.13
The override condition can last a maximum of
(repeatable).
The function can only be re-started by pressing the pushbutton again
:
1. Maximum total OVERRIDE time (after consecutive requests) =
2. Maximum number of consecutive requests for OVERRIDE =
The override condition ends when the barrier and sensors are
cleared (entrance clear) and the GUARD condition is re-enabled
(barrier fully operational) without sending any further commands.
The timer (point 1) and counter (point 2) are reset when one of the
following conditions occurs:
- A correct muting sequence.
- A system reset (switched off and then turned on).
SIGNALS DESCRIPTION
1
Input
Muting Sensor n°1
2
Input
Muting Sensor n°2
3
Input
Power supply 24Vdc
4
Input
Timeout selection n°1 *
5
Input
Timeout selection n°2 *
6
Input
Manual/Automatic configuration
7
Input
Override selection n°1 **
8
Input
Override selection n°2 **
9
Output
Safety photocell number 1 TEST
10
Output
Muting lamp output
11
Input
External muting enable input
12
Output
Safety relay B, contact 1 (N.O.)
13
Input
Power supply 0Vdc
14
-
Ground connection
15
Input
Restart command Input
16
Input
Test of the system external request
17
Input
Safety photocell number 1 status
18
Input
Safety photocell number 2 status
19
Output
Safety photocell number 2 TEST
20
Input
K1K2 external contactors feedback
21
Output
Output safety relays status
22
Output
Safety relay B, contact 2 (N.O.)
23
Output
Safety relay A, contact 1 (N.O.)
24
Output
Safety relay A, contact 2 (N.O.)
Table 9
* REFER TO THE Table 10 FOR THE SELECTION OF THE MUTING TIMEOUT