background image

 

 

 
 
 

 

1.

 

Water is heated instantaneously as it flows over the 
heating elements in the copper cylinder (diagram 2). 

 

2.

 

The heaters are only switched on when sufficient 

water is flowing.                                                                                                
This is done automatically with a switch which works 
on water pressure and is indicated by the neon light 

illuminating depending on the power selected by 
outer knob “A”. 

 

3.

 

The water is turned on and off by the solenoid valve 
built into the shower.                                                                                         
This is switched on when outer knob “A” is clicked 

clockwise. 

 

4.

 

The flow of water is automatically held at the level 

set by the user even though the supply pressure 
may vary (see “Effect of Other Water Devices on 
Incoming Water Supply”). 

 

5.

 

If the water supply falls below a set limit, the pressure switch will operate and switch off the 
power to the elements. This is indicated by the neon light going out (see “Effect of Other Water 

Devices on Incoming Water Supply”). 

 

6.

 

As a further safeguard

, a thermal cut-out switches the power off if the water temperature 

climbs above the set limit. This cut-out, which gives an audible click, may also operate due to 
residual heat when the shower is switched off.                                                                                                  

It will reset itself if water is run through the shower for 10 to 20 seconds. 

 

7.

 

The pressure relief device is to safeguard against abnormal pressure conditions. 

 

Effect of Seasonal Incoming Water Temperature Changes 

 

The required water temperature is achieved by adjusting the rate of water flow.  

Diagram 3 shows the principle involved in relating temperature rise to flow rate.                                 
The higher the water rate the lower the temperature and vice versa.                                               
The temperature of the water supplied from the mains can vary considerably 

throughout the year from 5 to 20°C.                                                                                                                    
This means that in the winter, flow rate will be less than in the summer to 
achieve the same outlet temperature.                                                                                                                                                                  
In some 

summer

 conditions, the “

 (medium)” power setting may give adequate hot water. 

In some 

winter

 conditions, it may be necessary to select the 

inner or outer spray pattern

 only of 

your shower handset. This will ensure correct operation of the shower with a slightly lower flow rate. 

 

Effect of Other Water Devices on Incoming Water Supply 

 

Your shower is 

designed to stabilise temperature

 changes caused by water pressure 

fluctuations. These can result from toilets being flushed or taps being turned on and off.                                 
When this happens your showering temperature will be held within a controlled band, provided that 

the minimum pressure required by the shower is maintained. 

 

Your shower requires a minimum operating pressure of 69kPa (0.7 bar, 10 psi).                                                                        
At pressures above 69kPa (0.7 bar, 10 psi) it will minimise temperature fluctuations as detailed 
above. If the water pressure falls below 69kPa (0.7 bar, 10 psi) it is likely that the pressure switch 

will turn off the power to the heating elements, resulting in a cold shower.                                                                                                                        
This will be indicated by the neon light going out.  

HOW YOUR 

ACTIVE 350S

 SHOWER WORKS 

Summary of Contents for Active 350S

Page 1: ...IMPORTANT This booklet should be left with the user after installation and demonstration REDRING ACTIVE 350S SMART TECHNOLOGY ELECTRIC SHOWER Installation and User Guide ...

Page 2: ...gy and a unique dual control combining on off power select and flow temperature control Your shower is designed to stabilise temperature changes caused by water pressure fluctuations These can result from toilets being flushed or taps being turned on and off When this happens your showering temperature will be held within a controlled band provided that the minimum pressure required by the shower ...

Page 3: ...nner knob B will rarely need adjusting You must however take into account required adjustments for variations of incoming mains water temperature between summer and winter see Effect of Seasonal Incoming Water Temperature Changes 6 When you have finished showering turn outer knob A anti clockwise to the stop position Water will continue to flow for approximately 7 seconds before switching off This...

Page 4: ...uired water temperature is achieved by adjusting the rate of water flow Diagram 3 shows the principle involved in relating temperature rise to flow rate The higher the water rate the lower the temperature and vice versa The temperature of the water supplied from the mains can vary considerably throughout the year from 5 to 20 C This means that in the winter flow rate will be less than in the summe...

Page 5: ...a comfortable showering temperature has been reached You MUST WAIT approximately 20 seconds for each adjustment to affect the water temperature medium setting may need to be selected Water too HOT Increase water flow by adjusting inner knob B anti clockwise direction of the blue arrows medium setting may need to be selected Increase pressure to water supply e g fully open service valve or stop coc...

Page 6: ...abiliser valve Check stabiliser is in place and remove any debris in valve Water leaks from burst pressure relief valve Check for cause of high pressure and remove it Blockage on outlet e g blocked shower handset Replace the pressure relief disc not covered by guarantee Water does not flow when outer knob A is turned Check circuit through solenoid coil If defective then replace Check circuit throu...

Page 7: ...t arrangement taking the following into account The possible need to use the handset over the sink for hair washing etc The heater must not be mounted in the direct spray from the handset The handset must not be able to come into contact with used water in the cubicle bath or basin If it can even after the hose has been retained by the soap dish see separate accessories fitting instructions sheet ...

Page 8: ...ommended that a WRAS Water Regulations Advisory Scheme listed isolating valve is fitted between the rising main and the unit This will allow the unit to be serviced or exchanged without having to turn off the water at the water stop valve 3 The heater can be fed from a header tank provided this has a minimum head of 7 metres 23ft 4 Ø15mm copper or stainless steel pipe should be used To avoid cross...

Page 9: ...ype B MCB 27m Max 45m Max 8 5 7 8kW 240 230V 6 0mm 10 0mm 45A BS 1361 fuse 12m Max 21m Max 6 0mm 10 0mm 40A Type B MCB 27m Max 45m Max 9 5 8 7kW 240 230V 6 0mm 10 0mm 45A BS 1361 fuse 12m Max 21m Max Remember to upgrade the cable if it runs in thermal insulation in a loft or for a longer distance 2 A means for disconnection in all poles must be incorporated in the fixed wiring in accordance with t...

Page 10: ...low can be adjusted by inner control knob B c Power selection operates in all 3 positions giving a change in water temperature and that the neon light functions correctly d Check again for leaks e That the holes in the shower handset are not blocked 8 DEMONSTRATE OPERATION TO USER Please Note The fitting of Spare Parts must be supervised by a suitably qualified person White 2 metre Shower Hose Cat...

Page 11: ... of terms and conditions are available on request from APPLIED ENERGY PRODUCTS LIMITED MORLEY WAY PETERBOROUGH PE2 9JJ TEL 44 0 1733 456789 FAX 44 0 1733 310606 Website www redring co uk GUARANTEE AND CONTACT DETAILS ...

Page 12: ... need to adjust inner knob B 5 Water will continue to flow for approximately 7 seconds before switching off This reduces the temperature of the water in the tank for the next user The neon indicator light will go out 6 Switch off the electricity supply at the ceiling switch or local isolator Notes Wait 20 seconds for the temperature to stabilise after each adjustment The neon indicates when the he...

Reviews: