2

Optional Remote Setpoint input (0/4 to 20 mA) allows for cascade control 

loops, where tighter control is required; and allows for remotely driven setpoint 

signal from computers or other similar equipment. Straightforward end point 

scaling with independent filtering and local/remote transfer option expand the 

controller’s flexibility.

The optional RS485 serial communication interface provides two-way 

communication between a T48 and other compatible equipment such as a 

printer, PLC, HMI, or a host computer. In multipoint applications (up to thirty-

two), the address number of each T48 on the line can be programmed from 0 to 

99. Data from the T48 can be interrogated or changed, and alarm output(s) may 

be reset by sending the proper command code via serial communications. PC 

software, SFCRM, allows for easy configuration of controller parameters. 

These settings can be saved to disk for later use or used for multi-controller 

down loading. On-line help is provided within the software.

The unit is constructed of a lightweight, high impact plastic case with a tinted 

front panel. The front panel meets NEMA 4X/IP65 specifications when properly 

installed. Multiple units can be stacked horizontally or vertically. Modern 

surface-mount technology, extensive testing, plus high immunity to noise 

interference makes the controller extremely reliable in industrial environments.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the 

manual or on equipment must be observed to ensure personal safety and to 

prevent damage to either the instrument or equipment connected to it. If 

equipment is used in a manner not specified by the manufacturer, the protection 

provided by the equipment may be impaired.

Do not use the T48 to directly command motors, valves, or other actuators not 

equipped with safeguards. To do so can be potentially harmful to persons or 

equipment in the event of a fault to the controller. An independent and redundant 

temperature limit indicator with alarm outputs is strongly recommended.

SPECIFICATIONS

1. 

DISPLAY:

 Dual 4-digit

Upper Temperature Display

: 0.4" (10.2 mm) high red LED

Lower Auxiliary Display

: 0.3" (7.6 mm) high green LED

Display Messages

:

 

“OLOL”  -  Appears when measurement e sensor range.

 

“ULUL”  -  Appears when measurement exceeds - sensor range.

 

“OPEN”  -  Appears when open sensor is detected.

 

“SHrt” 

-  Appears when shorted sensor is detected 

(RTD only)

 

“...” 

-  Appears when display values display range.

 

“-..” 

-  Appears when display values exceed - display range.

LED Status Annunciators

:

 

%P 

-  Lower auxiliary display shows power output in (%).

 

MN 

-  Flashing: Controller is in manual mode.

 

 

 

On: Local Setpoint (Remote Setpoint option)

 

 

 

Off: Remote Setpoint

 

DV 

-  Lower auxiliary display shows deviation 

(error)

 from  

 

 

   temperature setpoint or shows heater current.

 

O1 

-  Main control output is active.

 

A1 

-  Alarm #1 is active 

(for A1 option.)

.

 

A2 

-  Alarm #2 is active 

 

OR

 

 

-  Cooling output (O2) is active 

2. 

POWER:

AC Versions

: 85 VAC min. to 250 VAC max., 50 to 60 Hz, 8 VA max.

DC Versions

:

DC Power

: 18 to 36 VDC; 7 W

AC Power

: 24 VAC 

± 

10%; 50 to 60 Hz, 9 VA

3. 

CONTROLS:

 Four front panel push buttons for modification and setup of 

controller functions and one external input user for parameter lockout or 

other functions.

4. 

MEMORY: 

Nonvolatile E

PROM retains all programmable parameters and 

values.

5. 

MAIN SENSOR INPUT:

Sample Period

: 100 msec

Response Time

: Less than 300 msec typ., 400 msec max.

 (to within 99% of 

final value w/step input; typically, response is limited to response time of 

probe)

Failed Sensor Response

:

Main Control Output(s)

: Programmable preset output

Display

: “OPEN”

Alarms

: Upscale drive

Normal Mode Rejection

: 40 dB @ 50/60 Hz (improves with increased 

digital filtering.)

Common Mode Rejection

: Greater than 120 dB, DC to 60 Hz

Protection

: Input overload 120 VAC max. for 15 seconds max.

6. 

THERMOCOUPLE INPUT:

Types

: T, E, J, K, R, S, B, N, Linear mV, software selectable

Input Impedance

: 20 M

Ω 

all types

Lead resistance effect

: 0.25 µV/

Cold junction compensation

: Less than ±1°C (

±

1.5

°

C max), error over 0 

to 50°C max. ambient temperature range. Defeated for Linear mV 

indication mode.

Resolution

: 1° for all types, or  0.1° for T, E, J, K, and N only.

7. 

RTD INPUT:

 2 or 3 wire, 100 

 platinum, alpha = 0.00385 (DIN 43760), 

alpha = 0.0039162

Excitation

: 150 µA typical

Resolution

: 1 or 0.1 degree

Lead Resistance

:

 

15 

 max. per input lead

8. 

INDICATION ACCURACY:

 ±(0.3% of Span +1°C.) includes NIST 

conformity, cold junction effect and A/D conversion errors at 23°C after 20 

min. warm-up.

9. 

USER INPUT:

 Internally pulled up to +5 VDC (1 M

).

V

IN  MAX

 = 5.25 VDC

V

IL 

= 0.85 V max., V

IH 

= 3.65 V min.,

I

OFF

 = 1µA max.

Response Time

: 120 msec max.

Functions

:

10. 

CONTROL AND ALARM OUTPUTS: 

(Heating, Cooling or Alarm)

Relay outputs with Form A contacts

:

Contact Rating

: 3 A @ 250 VAC or 30 VDC (resistive load).

Life Expectancy

: 100,000 cycles at max. load rating.

(Decreasing load and/or increasing cycle time, increases life 

expectancy.)

Logic/SSR Drive Outputs

Rating

: 45 mA @ 4 V min., 7 V nominal

Triac Outputs

:

Type

: Isolated, Zero Crossing Detection

Rating

:

Voltage

: 120/240 VAC

Max. Load Current

: 1 Amp @ 35°C

0.75 Amp @ 50°C

Min Load Current

: 10 mA

Offstate Leakage Current

: 7 mA max. @ 60 Hz

Operating Frequency

: 20 to 400 Hz

Protection

: Internal transient snubber

11. 

MAIN CONTROL:

Control

: PID or ON/OFF

Output

: Time proportioning or Linear DC

Cycle time

: Programmable

Auto-tune

: When selected, sets proportional band, integral time, and 

derivative time values.

Probe Break Action

: Programmable

12. 

ALARMS:

 1 or 2 alarms (optional)

Modes

: Absolute high acting

Absolute low acting

Deviation high acting

Deviation low acting

Inside band acting

Outside band acting

RTD TYPE

RANGE

385

-200 to +600°C 

-328 to +1100°F

392

-200 to +600°C 

-328 to +1100°F

OHMS

1.0 to 320.0

Program Lock

Integral Action Lock

Auto/Manual Mode Select

Setpoint Ramp Enable

Reset Alarms

Setpoint 1/Setpoint 2 Select

Local/Remote Setpoint Select Serial block print

TC TYPE

RANGE

mV

WIRE COLOR

ANSI

BS 1843

T

-200 to +400

°

-328 to +752

°

F

blue (+) 

red (-)

white (+) 

blue (-)

E

-200 to +750°C 

-328 to +1382°F

violet (+) 

red (-)

brown (+) 

blue (-)

J

-200 to +760°C 

-328 to 1400°F

white (+) 

red (-)

yellow (+) 

blue (-)

K

-200 to +1250°C 

-328 to +2282°F

yellow (+) 

red (-)

brown (+) 

blue (-)

R

0 to 1768°C 

+32 to +3214°F

black (+) 

red (-)

white (+) 

blue (-)

S

0 to 1768°C 

+32 to 3214°F

black (+) 

red (-)

white (+) 

blue (-)

B

+149 to +1820°C 

+300 to +3308°F

grey (+) 

red (-)

no standard

N

-200 to +1300°C 

-328 to +2372°F

orange (+) 

red (-)

orange (+) 

blue (-)

-5.00 to +56.00

no standard

no standard

Summary of Contents for T48

Page 1: ...esponse without excessive overshoot The unit can be transferred to operate in the manual mode providing the operator with direct control of the output The controller may also be programmed to operate in the ON OFF control mode with adjustable hysteresis A second setpoint is available on select models to allow quick selection of a different setpoint setting Dual 4 digit displays allow viewing of th...

Page 2: ...ROLS Four front panel push buttons for modification and setup of controller functions and one external input user for parameter lockout or other functions 4 MEMORY Nonvolatile E2 PROM retains all programmable parameters and values 5 MAIN SENSOR INPUT Sample Period 100 msec Response Time Less than 300 msec typ 400 msec max to within 99 of final value w step input typically response is limited to re...

Page 3: ...e 300 to 9600 Data Format 7O1 7E1 7N2 8N1 Node Address 0 99 max of 32 units per line Transmit Delay 2 100 msec or 100 200 msec Data Encoding ASCII Isolation w r t Main Input Common 500 Vrms for 1 min 50 V working Not isolated w r t Remote Setpoint or Heater Current inputs or Analog Output common Note RS485 and the Analog Output commons are not internally isolated within the controller The terminat...

Page 4: ...on The output can be set for 0 to 10 V 0 to 20 mA or 4 to 20 mA ranges and can be configured for control or for transmission of temperature or setpoint values A Second Linear DC output is dedicated for retransmission of input temperature The output can be scaled and converted independent of the input and Main Linear DC output This output is isolated from the input SETPOINT FEATURES The controller ...

Page 5: ...t higher limit SPrP Enter setpoint ramp rate InPt Select user input function Configuration 2 Outputs 2 OP CYCt Enter time proportioning cycle time OPAC Select output control action OPLO Enter output power low limit OPHI Enter output power high limit OPFL Enter probe fail power preset OPdP Enter output control dampening CHYS Enter ON OFF control hysteresis tcOd Select auto tuning dampening ANtP Mai...

Page 6: ... the Heater Current Monitor Part Number CT005001 Current Ratio 50 0 1 Amperes Operation Frequency 50 to 400 Hz Insulation Class 0 6 KV BIL 10 KV full wave Terminals Brass studs No 8 32 UNC with flat washer and hex nuts Window Diameter 1 13 28 7 mm Weight 8 oz 226 0 g 1 2 3 4 5 6 7 8 9 10 13 14 12 11 2 39 60 7 MAX 1 96 49 8 MAX PANEL LATCH INSTALLED FOR VERTICAL UNIT STACKING HORIZONTAL UNIT STACKI...

Page 7: ... than 12 outside the manufacturer s specifications of 140 to 150 F 11 12 14 13 10 9 8 7 6 5 4 3 2 1 USER INPUT COMM TC RTD AL2 O2 COMM AL1 O1 N O COMM AC POWER 85 250 VAC AC POWER POWER AC NO GO GO 13 14 12 11 10 9 8 7 6 5 4 3 2 1 OUT OUT 02 A2 COMM 01 A1 USER INPUT COMM TC RTD IN IN SLAVE CONTROLLER 1 TC COMM 4 9 01 A1 5 MASTER CONTROLLER 11 12 10 RTD IN 02 A2 OUT OUT 3 2 1 USER INPUT 13 14 IN 8 ...

Page 8: ...OG OUTPUT HEATER CURRENT INPUT DEDICATED MAIN CONTROL O1 OUTPUT DEDICATED ALARM 1 A1 OUTPUT RS485 This output is programmable as either Control PID or as an Alarm This output is jumper and program selectable for either a current or voltage Linear DC output These part numbers are equipped with a second setpoint 1 Replacement Output Board RBD48100 may be used 2 Replacement Output Board RBD48111 may ...