Redlion CUB 5P Manual Download Page 5

5

4.3  INPUT WIRING

CAUTION

: Power input common is NOT isolated from user and input 

commons. In order to preserve the safety of the meter application, the 

power input common must be suitably isolated from hazardous live 

earth referenced voltage; or input common must be at protective earth 

ground potential. If not, hazardous voltage may be present at the signal 

or user inputs and input common terminals. Appropriate considerations must then 

be given to the potential of the user and input commons with respect to earth 

ground; and the common of the plug-in cards with respect to input common.
Before connecting signal wires, the Input Range Jumper should be verified for 

proper position. 

4.4  SETPOINT (OUTPUT) WIRING

COM

N.C.

N.O.

SINGLE SETPOINT RELAY PLUG-IN CARD

Input Signal (self powered)

Series Loop (must use separate supply for sensor power 

and each CUB5)

2 Wire With External Power

2 Wire With MLPS Power

2 Wire With Separate Sensor And CUB5 Power

-

+

COMM

INP+

2 WIRE TRANSMITTER

INP 

+

CO

M

M

EXTERNAL POWER

COMM

+VDC

+

_

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

RED LION CONTROLS

YORK, PA.      MADE IN U.S.A.

MLPS1

!

2 WIRE TRANSMITTER

CO

M

M

INP 

+

_

+

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

RED LION CONTROLS

YORK, PA.      MADE IN U.S.A.

MLPS1

!

2 WIRE TRANSMITTER

INP 

+

COMM

EXTERNAL POWER

COMM

COMM

+VDC

+VDC

_

+

CO

M

M

INP 

+

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

RED LION CONTROLS

YORK, PA.      MADE IN U.S.A.

MLPS1

!

CO

M

M

INP 

+

+VDC

COMM

EXTERNAL POWER

2 WIRE TRANSMITTER

+

_

MODEL 

INPUT POWER:

OUTPUT POWER:

85-250 VAC, 50/60Hz, 14VA

OPERATING TEMP: 0° TO 60°C

12VDC UNREG.  

      

 @ 400mA

+12V

DC COMMON

M3424B

TERMINAL

AC INPUT

RED LION CONTROLS

YORK, PA.      MADE IN U.S.A.

MLPS1

!

COM

N.O.

N.C.

ELECTRICAL CONNECTIONS

DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD

OSNK1

OSNK2

COM

ELECTRICAL CONNECTIONS

Output Common is not isolated from DC Power Common. Load 

must be wired between OSNK terminal and V+ of the load supply.

30 VDC

150 mA

10 VDC

20/50 mA DC

MAX SIGNAL 

INPUT 

JUMPER 

POSITION

COM

OSNK 1(2)

(30 V MAX.)

4.5  SERIAL COMMUNICATION WIRING

N/

C

RS485

2

COMM

A+

B-

N/

C

5

3

4

N/

C

RS232

5

N/

C

TX

N/

C

4 3

COMM

COMM

2

RX

6

1

6

1

4.6  USB PROGRAMMING

USB PROGRAMING PLUG-IN CARD

SERIAL COMMUNICATIONS PLUG-IN CARD

RJ11 CONNECTOR PIN OUTS

20/50 mA DC

JUMPER 

POSITION

20/50 mA DC

JUMPER 

POSITION

20/50 mA DC

JUMPER 

POSITION

20/50 mA DC

JUMPER 

POSITION

Summary of Contents for CUB 5P

Page 1: ...n be powered from an optional Red Lion Micro Line Sensor Power Supply MLPS which attaches directly to the back of a CUB5 The MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the unit and sensors INPUT The CUB5P is a DC Process meter It features voltage and current input ranges that are selected by the user via a programming jumper and software input range selection The ranges ...

Page 2: ...FICATIONS AND COMPLIANCES CE Approved EN 61326 1 Immunity to Industrial Locations Emission CISPR 11 Class A Safety requirements for electrical equipment for measurement control and laboratory use EN 61010 1 General Requirements EN 61010 2 030 Particular Requirements for Testing and Measuring Circuits RoHS Compliant UL Recognized Component File E179259 UL Listed File E137808 Type 4X Indoor Outdoor ...

Page 3: ...85 SERIAL COMMUNICATIONS CARD Type RS485 multi point balanced interface non isolated Baud Rate 300 to 38 4k Data Format 7 8 bits odd even or no parity Bus Address 0 to 99 max 32 devices per line Transmit Delay Selectable refer to CUB5COM bulletin RS232 SERIAL COMMUNICATIONS CARD Type RS232 half duplex non isolated Baud Rate 300 to 38 4k Data Format 7 8 bits odd even or no parity USB PROGRAMMING CA...

Page 4: ...2010 1 07 Red Lion Controls LFIL0000 6 To protect relay contacts that control inductive loads and to minimize radiated and conducted noise EMI some type of contact protection network is normally installed across the load the contacts or both The most effective location is across the load a Using a snubber which is a resistor capacitor RC network or metal oxide varistor MOV across an AC inductive l...

Page 5: ...N U S A MLPS1 2 WIRE TRANSMITTER COMM INP _ MODEL INPUT POWER OUTPUT POWER 85 250 VAC 50 60Hz 14VA OPERATING TEMP 0 TO 60 C 12VDC UNREG 400mA 12V DC COMMON M3424B TERMINAL AC INPUT RED LION CONTROLS YORK PA MADE IN U S A MLPS1 2 WIRE TRANSMITTER INP COMM EXTERNAL POWER COMM COMM VDC VDC _ COMM INP MODEL INPUT POWER OUTPUT POWER 85 250 VAC 50 60Hz 14VA OPERATING TEMP 0 TO 60 C 12VDC UNREG 400mA 12V...

Page 6: ... pressing the SEL button with Pro NO displayed This will commit any stored parameter changes to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify recent parameter changes PROGRAMMING TIPS It is recommended to start with Module 1 and proceed through each module in sequence When programming is complete it is recommended to record the par...

Page 7: ...ut Values have to be derived from the actual input signal source or simulator the Apply APLY scaling style must be used KEy APLY 0 000 INP 1 INPUT VALUE FOR SCALING POINT 1 For Key in KEY style enter the known first Input Value using the front panel buttons The Input Range selection sets the decimal location for the Input Value For Apply APLY style the meter shows the previously stored Input Value...

Page 8: ...ow FACTORY SERVICE OPERATIONS yES NO YES NO Enables the Maximum Display Capture capability Enables the Minimum Display Capture capability The CUB5P uses stored calibration values to provide accurate voltage and current measurements Over time the electrical characteristics of the components inside the meter could slowly change therefore the stored calibration values may no longer accurately define ...

Page 9: ...Backlight Unit Only 3 dSP dSP t SEL rSt ZErO UNItS COLOr CodE Display Intensity Level d LEV ScroL Display Scroll Enable PARAMETER MENU The yES selection allows the SEL button to toggle through the enabled displays FRONT PANEL DISPLAY SELECT ENABLE SEL This selection allows the RST button to reset the selected value s FRONT PANEL RESET ENABLE RST The yES selection allows the display to automaticall...

Page 10: ...nced are affected by the hysteresis When the setpoint is a control output usually balanced hysteresis is used For alarm applications usually unbalanced hysteresis is used For unbalanced hysteresis modes the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints Note Hysteresis eliminates output chatter at the switch point while time d...

Page 11: ...active when one of the optional serial communications programming cards is installed in the meter Refer to the CUB5COM bulletin for details and setup for the CUB5 RS232 or RS485 serial communications Refer to the CUB5USB bulletin for details on the CUB5 USB programming and programming requirements PARAMETER MENU button or user input manual reset serial reset command or meter power cycle When the u...

Page 12: ...n tOF n rSt n rEn n ChC n Standby Operation Stb n Front Panel Reset Enable Front Panel Display Select Enable Display Update Time dSP t SEL rSt 3 dSP Display Intensity Level COLOr Units Indicator Selection UNItS Display Color d LEV Programming Security Code CodE rANGE dECPt 1 INP FILtr bANd USrIN INP 1 dSP 1 INP 2 U ASN LO En Min Display Enable Max Capture Delay Time Max Display Enable HI En HI t 2...

Reviews: