8 Specifications
Application
Remote electrical circuit measurements using a web browser via WiFi. Replaces
DIN Rail Terminals. Metallic and non-metallic panel suitable.
Environment
Altitude - 0m to 2,000m
Temperature - 0C to 70C, 32F to 158F
Humidity
– 0% to 80%
Use
– Indoor
Pollution Degree
– 2
Power Supply
Fixed - 12VDC, 0.10A or 24VDC, 0.06A
Portable
– 9V Battery, battery life approximately 2.5hrs continuous
Power Supply Terminals
(Fixed Unit)
Conductors - 0.2 to 2.5mmsq, 24 to 12AWG.
Tightening Torque - 0.5Nm to 0.6Nm.
Rated Temperature - -40C to 105C, -40F to 221F
Inputs
8 Voltage, Non Isolated
Voltage Measurement Range - 0 to 300VAC/DC, 50Hz-400Hz
Current Feedthrough Maximum
– 12A
Input Safety
CAT III, 300VAC (Line to Neutral)
Input Terminals
(Fixed Unit)
Conductors - 0.2 to 2.5mmsq, 24 to 12AWG.
Tightening Torque - 0.5Nm to 0.6Nm.
Rated Temperature - -40C to 105C, -40F to 221F
Test Leads
(Portable Unit)
1 x 3 Terminal, Rd, Bk, Gr, CAT III, 1kV
1 x 2 Terminal, Bu, Yl, CAT III, 1kV
1 x 3 Terminal, Bu, Yl, Gr, CAT III, 1kV
1 x 2 Terminal, Rd, Bk, CAT III, 1kV
4 x Terminal Plugs
4 x Crocodile Clips
4 x Magnet Electrodes
WiFi Capacity
Maximum 4 simultaneous clients
Minimum WiFi range (external to panel) = 10m
Web Browser
Compatibility
W3C compliant web browsers as follows:
Chrome (Android mobile devices & PCs)
Safari (Apple mobile devices & Macs)
Firefox (Mobile devices)
Note: Internet Explorer currently not supported
Web Browser
Configuration
Panel Name (unique WiFi Access Point)
Module Name
Terminal Name
Voltage Mode (module configurable)
– AC or DC
Voltage Level (individually configurable)
– 12, 24, 32, 48, 110, 120, 220, 230, 240,
277
Web Browser Operation
8 Voltages
Resolution
– 0 decimal point
Accuracy
– ±2% FS ±1 digit @ 25C, 77F
Thermal Drift
– 0.005V/degC, 0.015V/degF
Background Colours
o
Green = 0 to 20% Vnom
o
Yellow = 21 to 79% Vnom
o
Red = 80 to 120% Vnom
o
Yellow > 120% Vnom
CPU Temperature
Update Time - 1 second
Size
(Fixed Unit)
(Portable Unit)
45W x 1
21H x 45D, 1.75”W x 4.75”H x 1.75”D
45W x 186H x 45D, 1.75”W x 6.50”H x 1.75”D
Degree of Protection
Terminals = IP2X (IEC 60529 not certified by UL)
Approvals
Australia
Nil
Europe
Nil
USA/Canada
Designed to UL 61010-1 2nd Ed
Designed to CSA 22.2 No. 61010-1-04
Summary of Contents for CircuitSpy 80