12
3 INSTALLATION
3.2
Ventilation Fan
The fan is load and temperature controlled and will engage when the AC Power Consumption reaches a
certain level and when the unit gets hot. Ensure that the fan is not obstructed and is at a distance of at
least 0.98” (25 mm) from surrounding objects.
NOTICE
Install the inverter in a well-ventilated area with reasonable clearance. Do not install the inverter in a
zero-clearance compartment or obstruct the ventilation openings. Doing so may result in the inverter
overheating and ultimately damage the inverter.
3.3
Safety Before Installing DC Wiring Connections
3.3.1 Loads Are Disconnected
Make sure all loads are disconnected from the inverter’s AC output and ensure that the inverter main
switch is set to the OFF position before connecting DC cables.
FIGURE 3.3.1:
Ensuring loads are disconnected
FIGURE 3.3.2:
Switch is set to OFF position
WARNING
RISK OF ELECTRICAL SHOCK. BEFORE PROCEEDING, CAREFULLY CHECK THAT THE INVERTER IS NOT CONNECTED TO
ANY BATTERIES AND THAT ALL WIRING IS DISCONNECTED FROM ANY ELECTRICAL SOURCES. DO NOT CONNECT THE
OUTPUT TERMINALS OF THE INVERTER TO AN INCOMING AC SOURCE.