16
2
USER GUIDE
2.1.6 AC Output Interface
WARNING
ALL ELECTRICAL WORK MUST BE PERFORMED IN ACCORDANCE WITH THE LOCAL AND NATIONAL ELECTRICAL
CODES. THESE INSTRUCTIONS ARE FOR USE BY QUALIFIED PERSONNEL WHO MEET ALL LOCAL AND GOVERNMENT
CODE REQUIREMENTS FOR LICENSING AND TRAINING FOR THE INSTALLATION OF ELECTRICAL POWER SYSTEMS
WITH AC AND DC VOLTAGE UP TO 600 VOLTS. INSTALLATION, MAINTENANCE AND CONNECTION OF INVERTERS
MUST BE PERFORMED BY QUALIFIED PERSONNEL, IN COMPLIANCE WITH LOCAL ELECTRICAL STANDARDS AND
CODES, WIRING RULES AND THE REQUIREMENTS OF LOCAL POWER AUTHORITIES AND/OR COMPANIES. SAFETY
REGULATIONS RELEVANT TO THE LOCATION SHALL BE FOLLOWED DURING INSTALLATION, OPERATION AND
MAINTENANCE
IMPROPER OPERATION MAY HAVE A RISK OF ELECTRIC SHOCK OR DAMAGE TO EQUIPMENT AND PROPERTY.
L
N
FG
FIGURE 2.1.6.1:
AC Output Interface for
1000 / 1500 / 2000 W Models
FIGURE 2.1.6.2:
Standard Hard Wire Socket for
3000 W Models
R-12-3000RS-NA Output Interface
Terminal
Wire color
Wire length/gauge
AC terminal
Line (L)
Black
Within 6 feet / AWG8
Neutral (N)
White
FG (Ground)
Green / Yellow or Bare
copper
26 ~ 32 feet / AWG#
10 ~ 8
In order for R-12-3000RS-NA to be UL 458 compliant it requires to be used with one or more of the
following GFCI connectors:
• HUBBELL INC WIRING DEVICE DIV, Type GF20 and GFRST20 Rated 125 V, 20 A
• COOPER WIRING DEVICES, Type VGF20 and SGF20. Rated 125 V, 20 A
• LEVITION MFG CO INC, Type 7899 - W and GFNT2. Rated 125 V, 20 A
• PASS AND SEYMOUR INC, Type 2097. Rated 125 V, 20 A
Additional breakers suitable for 20 A branch circuit protection shall be provided for the GFCI receptacles.
Branch rated overcurrent protection for the AC output circuit is to be provided at the time of installation