Pub. 42004-545A
telephone VoIP WiFi Telephone Manual
Page 8 of 29
P:\Standard IOMs - Current Release\42004 Instr. Manuals\42004-545A.docx
03/20
Conduit Installation (Surface-Mount Models)
GAI-Tronics recommends installing power lines in conduit to protect against accidental damage and
vandalism. To prevent moisture from entering the enclosure, we strongly recommend the following:
•
Conduit should enter the enclosure from the bottom.
•
Sealed fittings should be installed at all cable entry points.
•
Silicone sealant or equivalent should be applied around and inside all conduit entries.
Please refer to the examples below for the recommended conduit installation details for surface-mount
telephones.
Figure 1. Bottom entry conduit recommended for
non-metallic enclosures
Figure 2. Top entry conduit installation for non-
metallic enclosures (NOT recommended)
Figure 3. Bottom entry conduit installation details
for metallic enclosures
Figure 4. Top entry conduit installation details for
metallic enclosures (NOT recommended)