background image

MOUNTING INSTRUCTIONS

This operator interface is primarily designed for 

through-panel mounting. Four VESA mount tapped 

screw-holes (M4 x 0.7, 5 mm deep) are present on the rear 
of the panels to allow for stand or wall mounting. Care 

should be taken to remove any loose material from the 
mounting cut-out to prevent that material from falling into 

the operator interface during installation. A gasket is 
provided to enable sealing to NEMA 4X/IP66 specification. 
Install the fourteen mounting clips provided and tighten to 

6.0 pound-force inch [96 ounce-force inch] (0.68 N m) 
evenly for uniform gasket compression. 

Provisions should be made to prohibit the product from 

being exposed to UV radiation while in use. Care should be 

taken not to rub or buff the touchscreen surface in a way that 

might cause the accumulation of static charges.  

CONNECTING TO EARTH GROUND

Each operator panel has a chassis ground terminal on the back of the unit. 

Your unit should be connected to earth ground (protective earth).

The chassis ground is not connected to signal common of the unit. 

Maintaining isolation between earth ground and signal common is not required 
to operate your unit. But, other equipment connected to this unit may require 
isolation between signal common and earth ground. 

To maintain isolation 

between signal common and earth ground care must be taken when connections 
are made to the unit.

 For example, a power supply with isolation between its 

signal common and earth ground must be used. Also, plugging in a USB cable 
may connect signal common and earth ground.

1

1

 USB’s shield may be connected to earth ground at the host. USB’s shield in 

turn may also be connected to signal common.

FOOT MAY BE REMOVED

FOR THICKER PANEL

INSTALLATIONS

For hazardous location installation, this device 
must be mounted in a suitable ATEX/IECEx 
certified end-enclosure with a minimum 
ingress protection rating of at least IP66 as 

defined in EN/IEC 60529 and used in an environment of 
not more than Pollution Degree 2 per EN 60664-1. Must 
be wired using Division 2 wiring methods as specified in 
article 501-4 (b), 502-4 (b), and 503-3 (b) of the National 
Electrical Code, NFPA 70 for installation within the United 
States, or as specified in section 19-152 of Canadian 
Electrical Code for installation in Canada.

PANEL CUT-OUT

10.197 (259.0)

7.931

(201.4)

4X R.10 (2.5)

MAX.

All tolerances ±.059" (±1.5 mm)

The protective conductor terminal is bonded to conductive 
parts of the equipment for safety purposes and must be 
connected to an external protective earthing system.
Steps should be taken to eliminate the buildup of 
electrostatic charges including but not limited to 
connecting to earth ground.

O

peratOr

 I

nterface

 I

nstallatIOn

.87

(22.1)

2.95 (75)

1.48 (37.5)

2.95

(75)

VESA MOUNT (MIS-D 75) DIMENSIONS

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: -20 to 60 °C
Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g
Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant

ATEX Approved

 II 3 G Ex ic nA IIC T4 Gc
 II 3 D Ex tc IIIC T135°C Dc

DEMKO 14 ATEX 1387X

EN 60079-0, -11, -15, -31

IECEx Approved

Ex ic nA IIC T4 Gc
Ex tc IIIC T135°C Dc
IECEx UL 15.0035X

IEC 60079-0, -11, -15, -31

UL Listed: File #E302106
UL Hazardous: File #E317425
Type 4X Indoor / IP66 Enclosure rating (Face only) for all models
Type 4X Outdoor Enclosure rating (Face only) for G10Sxxxx models

CONNECTIONS

: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: One 14 AWG (1.63 mm) solid, 

two 18 AWG (1.02 mm) or four 20 AWG (0.81 mm)

CONSTRUCTION

: Cast aluminum enclosure with NEMA 4X/IP66 rating for 

indoor use only when correctly fitted with the gasket provided. Installation 
Category II, Pollution Degree 2 as defined in IEC 60664-1. These devices 
have only been evaluated for low risk of mechanical impact.

WEIGHT

: 4.8 lb. (2.18 Kg)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Summary of Contents for G10C0000

Page 1: ...DC powered additional ethernet port G10R1000 10 color touch screen indoor outdoor use 24 VDC powered G10S0000 10 color touch screen indoor outdoor use 24 VDC powered additional ethernet port G10S1000 SPECIFICATIONS POWER 24 VDC 20 G10C R G10S Typical Power HMI only 12 W 18 W Maximum Power HMI only 19 W 24 W Available Power for Modules 29 W 29 W HMI With Module s 48 W 53 W Must use a Class 2 circui...

Page 2: ...f not more than Pollution Degree 2 per EN 60664 1 Must be wired using Division 2 wiring methods as specified in article 501 4 b 502 4 b and 503 3 b of the National Electrical Code NFPA 70 for installation within the United States or as specified in section 19 152 of Canadian Electrical Code for installation in Canada PANEL CUT OUT 10 197 259 0 7 931 201 4 4X R 10 2 5 MAX All tolerances 059 1 5 mm ...

Page 3: ... the modules order in the Crimson database Torque screws to 6 0 pound force inch 96 ounce force inch 0 68 N m REMOVE RUBBER MODULE PLUG WARNING Disconnect all power to the unit before installing or removing modules POWER SUPPLY REQUIREMENTS The G10 requires a 24 VDC power supply Your unit may draw considerably less than the maximum rated power depending upon the features being used As additional f...

Page 4: ...nner that complies with your local waste regulations The battery must not be disposed of in fire or in a manner whereby it may be damaged and its contents could come into contact with human skin The battery used by the panel is a lithium type BR2032 WARNING EXPLOSION HAZARD DISCONNECT POWER AND ENSURE THE AREA IS KNOWN TO BE NON HAZARDOUS BEFORE SERVICING REPLACING THE UNIT AND BEFORE INSTALLING O...

Reviews: