background image

BATTERY & TIME KEEPING  

A battery is used to keep time when the unit is without power. Typical 

accuracy (at 25°C) of the Graphite time keeping is less than one minute per 
month drift. The battery of a Graphite unit does not affect the unit’s memory, all 
configurations and data is stored in non-volatile memory.

Changing the Battery

To change the battery of a Graphite, first remove power to the unit. Remove 

the battery cover. Grasp the top edge of the battery and push to the left to remove 
the battery from the holder. Lift the battery out and replace with a new battery.

Replace the battery cover, and re-apply power. Using Crimson or the unit’s 

keypad, enter the correct time and date.

* Please note that the old battery must be disposed of in a manner that

complies with your local waste regulations. The battery must not be disposed of 
in fire, or in a manner whereby it may be damaged and its contents could come 
into contact with human skin.

The battery used by the panel is a lithium type BR2032.

WARNING - EXPLOSION HAZARD - DISCONNECT POWER 
AND ENSURE THE AREA IS KNOWN TO BE NON-HAZARDOUS 
BEFORE SERVICING/ REPLACING THE UNIT AND BEFORE 
INSTALLING OR REMOVING I/O WIRING AND BATTERY.

+

-

TYPE B

USB

ST

AT

US USB HOST

ST

AT

US

PORT B

PORT A

COMM

RT

S  (PIN 6)

Tx

CTS  (PIN 1)

Rx

COMM

RT

S  (PIN 6)

Rx

COMM

Tx

COMM

CTS  (PIN 1)

(NIC)

ETHERNET

RxB

Tx

 (PIN 8)

COMM

TxB

TxEN

TxB  (PIN 1)

RxA TxA

AUXILIARY

ETHERNET

(NIC)

COMMS PORT

PGM PORT

COMMS PORT

RS232

RS485

RS232

DEVICE

USB

POWER

-

+

USB HOST

PORT A (PGM)

RS232

RS232

PORT B

PORT A

RS485

AUXILIARY

ETHERNET

POWER

CHASSIS

COMMON

+DC VO

LT

AGE

1

2

3

CONNECTOR

[OPTIONAL]

A

B

ETHERNET

G10 PORT PIN OUTS

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Summary of Contents for G10C0000

Page 1: ...DC powered additional ethernet port G10R1000 10 color touch screen indoor outdoor use 24 VDC powered G10S0000 10 color touch screen indoor outdoor use 24 VDC powered additional ethernet port G10S1000 SPECIFICATIONS POWER 24 VDC 20 G10C R G10S Typical Power HMI only 12 W 18 W Maximum Power HMI only 19 W 24 W Available Power for Modules 29 W 29 W HMI With Module s 48 W 53 W Must use a Class 2 circui...

Page 2: ...f not more than Pollution Degree 2 per EN 60664 1 Must be wired using Division 2 wiring methods as specified in article 501 4 b 502 4 b and 503 3 b of the National Electrical Code NFPA 70 for installation within the United States or as specified in section 19 152 of Canadian Electrical Code for installation in Canada PANEL CUT OUT 10 197 259 0 7 931 201 4 4X R 10 2 5 MAX All tolerances 059 1 5 mm ...

Page 3: ... the modules order in the Crimson database Torque screws to 6 0 pound force inch 96 ounce force inch 0 68 N m REMOVE RUBBER MODULE PLUG WARNING Disconnect all power to the unit before installing or removing modules POWER SUPPLY REQUIREMENTS The G10 requires a 24 VDC power supply Your unit may draw considerably less than the maximum rated power depending upon the features being used As additional f...

Page 4: ...nner that complies with your local waste regulations The battery must not be disposed of in fire or in a manner whereby it may be damaged and its contents could come into contact with human skin The battery used by the panel is a lithium type BR2032 WARNING EXPLOSION HAZARD DISCONNECT POWER AND ENSURE THE AREA IS KNOWN TO BE NON HAZARDOUS BEFORE SERVICING REPLACING THE UNIT AND BEFORE INSTALLING O...

Reviews: